answersLogoWhite

0


Want this question answered?

Be notified when an answer is posted

Add your answer:

Earn +20 pts
Q: How can calculate Dy1 Dy11 vector group of transformer?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Related questions

How can calculate Dd6 Dy11 vector group of transformer?

By calculate do you mean calculate the connections required or phasor diagrams? full question would be helpful


Can a Dy11 vector group transformer be connected to a Yd1 vector group transformer source?

In series, yes. In parallel, nope! Putting a Yd1 transformer in series with a Dy11 transformer would result in the output of the Dy11 transformer being identical to the input of the Yd1 transformer with the exception of the voltage magnitude - this will change depending on the winding ratio's on both transformers. But, in regards to other properties of the voltage, the phases will in be in phase, with the voltage in-between the two transformers lagging by 30 degrees.


What is the meaning of DY 11 on a transformer nameplate?

there is no specification of Dy11.. it will be Dyn11.. it is the vector group of the transformer. capital d means primary winding is delta secondary winding is star(y) and the secondary current lags voltage by 30degree this angle when shown in clock will be looking like 11 o clock


What is DY11 transformer?

d:delta connection primary windingy :star connection secondary winding


Synchronize the transformer dy11 and dy1?

synchronise means parallel operation. to do so first you must understand the winding level chaos. what is 30 deg and -30 deg. then automatically you can come to a conclusion


How we select a transformer by vectorgroup?

A Vector group is the International Electrotechnical Commission (IEC) method of categorizing the primary and secondary winding configurations of three-phase transformers. Within a polyphase system power transformer it indicates the windings configurations and the difference in phase angle between them. The phase windings of a polyphase transformer can be connected together internally in different configurations, depending on what characteristics are needed from the transformer. For example, in a three-phase power system, it may be necessary to connect a three-wire system to a four-wire system, or vice versa. Because of this, transformers are manufactured with a variety of winding configurations to meet these requirements. Different combinations of winding connections will result in different phase angles between the voltages on the windings. This limits the types of transformers that can be connected between two systems, because mismatching phase angles can result in circulating current and other system disturbances. Symbol designation The vector group provides a simple way of indicating how the internal connections of a particular transformer are arranged. In the system adopted by the IEC, the vector group is indicated by a code consisting of two or three letters, followed by one or two digits. The letters indicate the winding configuration as follows: * D: Delta winding, also called a mesh winding. Each phase terminal connects to two windings, so the windings form a triangular configuration with the terminals on the points of the triangle. * Y: Wye winding, also called a star winding. Each phase terminal connects to one end of a winding, and the other end of each winding connects to the other two at a central point, so that the configuration resembles a capital letter Y. The central point may or may not be connected outside of the transformer. * Z: Zigzag winding, or interconnected star winding. Basically similar to a star winding, but the windings are arranged so that the three legs are "bent" when the phase diagram is drawn. Zigzag-wound transformers have special characteristics and are not commonly used where these characteristics are not needed. * III: Independent windings. The three windings are not interconnected inside the transformer at all, and must be connected externally. In the IEC vector group code, each letter stands for one set of windings. The HV winding is designated with a capital letter, followed by medium or low voltage windings designated with a lowercase letter. The digits following the letter codes indicate the difference in phase angle between the windings, with HV winding is taken as a reference. The number is in units of 30 degrees. For example, a transformer with a vector group of Dy1 has a delta-connected HV winding and a wye-connected LV winding. The phase angle of the LV winding leads the HV by 30 degrees. The point of confusion is in how to use this notation in a step-up transformer. As the IEC60076-1 standard has stated, the notation is HV-LV in sequence. For example, a step-up transformer with a delta-connected primary, and star-connected secondary, is not written as 'dY11', but 'Yd11'. The 11 indicates the LV phase lags 30 degree behind the HV side. Transformers built to ANSI standards usually do not have the vector group shown on their nameplate and instead a vector diagram is given to show the relationship between the primary and other windings.


What type of transformer is best suited in generating end Dy11 or Dy1 and Why?

The difference between a Dy11 (delta winding lags the wye winding by 30 degrees) and a Dy1 (delta winding leads the wye winding by 30 degrees) is a phase shift. One is not better than another in a general sence. Depending on the configuration of the plant and surrounding power lines and transformers, one may be more beneficial than the other by allowing the plant to sync to the grid through multiple sources without first disconnecting.


What is the difference between Dyn-11 and Ynd-11?

Winding connection designations High Voltage Always capital letters Delta - D Star - S Interconnected star - Z Neutral brought out - N Low voltage Always small letters Delta - d Star - s Interconnected star - z Neutral brought out - n Phase displacement Phase rotation is always anti-clockwise. (international adopted convention) Use the hour indicator as the indicating phase displacement angle. Because there are 12 hours on a clock, and a circle consists out of 360°, each hour represents 30°. Thus 1 = 30°, 2 = 60°, 3 = 90°, 6 = 180° and 12 = 0° or 360°. The minute hand is set on 12 o'clock and replaces the line to neutral voltage (sometimes imaginary) of the HV winding. This position is always the reference point. Because rotation is anti-clockwise, 1 = 30° lagging (LV lags HV with 30°)and 11 = 330° lagging or 30° leading (LV leads HV with 30°) To summarise: Dd0 Delta connected HV winding, delta connected LV winding, no phase shift between HV and LV. Dyn11 Delta connected HV winding, star connected LV winding with neutral brought out, LV is leading HV with 30° YNd5 Star connected HV winding with neutral brought out, delta connected LV winding, LV lags HV with 150° " So there is no specification of Dy11.. it will be Dyn11 "