Based on the numbers in your question, I assume you're in the US. If the 240V comes from a utility transformer feeding the building, you're pretty much stuck with what you've got. 208V normally comes from 208/120 three-phase service. If you have 240V, that means you have single-phase service. 208V single-phase wouldn't work, because the receptacles would end up with 104V instead of the required 120, so what you're really asking is can you get 3-phase, 208/120V service. If this is a home, almost certainly the answer will be no. If it is a small commercial building, then it may be possible, but the utility will probably make you foot the bill, and it will cost plenty. And Transformers (3 of them) would be involved.
See Discussion Page
Yes a transformer should be used. The steam table needs its correct voltage otherwise on 240 volts it will operate over its given specified nameplate wattage. A 208 volt heating element run off of 240 volt will have an output increase by 75 percent.
What size breakers are needed for a 30kva transformer 208 volt feed 600 volt out put
45000 / 208 /sqrt(3) = 125A per phase this is probably called a boiler unless it has a 2000Gallon tank
i think you just have to change the breaker from a 277 to a 120. 277 breakers are usually a 2 pole breaker and 120 is a single pole breaker. NO. 277v is not two poles, it is one pole, one single pole breaker in a 480 volt 3 phase system (typically). If you want 120 volts from a 277 volt source you need a step down transformer 277 volt to 120 volt , or 480/277 to 120/208 .
See Discussion Page
You need to mention the Load connected to find the current.
200 and 100
Yes a transformer should be used. The steam table needs its correct voltage otherwise on 240 volts it will operate over its given specified nameplate wattage. A 208 volt heating element run off of 240 volt will have an output increase by 75 percent.
What size breakers are needed for a 30kva transformer 208 volt feed 600 volt out put
Yes by using a 3-phase transformer. The size depends on how much power has to be converted.
First of all there is no common three phase 120 volt service. There is in North America a three wire 120/240 volt single phase service. That being said, if you want to change a 120 volt source to 240 volts it must be done with a transformer. Its classification is a step up transformer. The primary side of the transformer H1 - H2 will be connected to the 120 volts. The secondary side of the transformer X1 - X2 will be connected to the 240 volt load. The transformer is sized by the current required by the 240 volt load.
No a 208 volt outlet does not need a neutral. 208 volts is the line voltage between any two legs of a three phase 208 volt system.
The transformer will act as a step down transformer in the ratio of 240 to 208. This will reduce the 208 input to 180.
Because its designed to operate at 230-460, not 120-208.
It should be ok
45000 / 208 /sqrt(3) = 125A per phase this is probably called a boiler unless it has a 2000Gallon tank