87 amps three phase means 87 amps on each phase.
Additional Answer
It's only 87 A per phase for a wye (star) connected load; for a delta connected load, the current per phase will be 50 A, while each line current will be 87 A. That's assuming a balanced load, of course. Line currents pass through the supply conductors to the load, whereas phase currents pass through the loads themselves.
Next answer: No, 87 amps three-phase means 87 amps on each phase wire, so you can put an ammeter in each wire and it registers 87 amps.
It doesn't matter whether the load is connected delta or star :) But the amount of power is different because the line-to-line voltage is sqrt(3) times as much as the line-to neutral voltage. It isn't the current that is different, it's the voltage.
Another AnswerThis question is rather confusing as we don't really know what the original '87' A is referring to. Is it a line current or a phase current? But it's important that we use the correct terminology if we are to sort it out.
First of all, the 'hot' conductors that connect the generator to its load are called line conductors (or, simply, 'lines'), and the voltages between any pair of line conductors are termed 'line voltages', while the currents flowing through each of them are termed a 'line currents'. (Confusion exists when people call these three interconnecting conductors 'phases', which is common but completely incorrect! Remember, 'line' voltages and currents are so-called because they refer to 'lines', not phases!)
Next, the three windings within the generator, which may be connected either in delta or in star (wye) represent the machine's 'phases'. So the voltage appearing across any one of these internal windings is called a 'phase voltage', while the current through any one of these windings is termed a 'phase current'.
Generally speaking, while its very easy to place a voltmeter and ammeter to measure line voltages and line currents, it's usually very much more difficult to place these instruments so that they can measure phase voltages and currents, This is because the phases are inaccessible, because they are enclosed insidethe generator.
So, in practise, whenever we work with a generator (and the same goes for a motor), we usually measure line values notphase values.
So, returning to the question, if we assume the '87 A' quoted by the questioner is a phase current (that is, as measured in any winding inside the generator) then, for a balanced load, the value of the line current (as measured in any one of the external line conductors) will depend on whether the windings are connected in delta or in star. If the windings are connected in star, then the line currents (i.e. outside the generator) will have exactly the same magnitude as the winding (phase) currents -i.e. they will also be 87 A. If, on the other hand, the windings (phases) are connected in delta, then each line current will be 1.732 times the phase current -that is, about 151 A.
On the other hand, if the '87 A' quoted is a line current (that is, as measured outside the generator) then, for a delta-connected generator, the winding (phase) current will be 0.577 times the line current: i.e. about 50 Awhereas, for a star-connected generator, the winding (phase) current will be exactly the same as the line current, i.e. 87 A.
Next Answer: the longer it gets, the more confusing it gets :) However the wires carrying the three-phase supply can correctly be called 'lines'. Then you can have a 'line-to-line' voltage and a 'line-to-neutral' voltage and those terms are unambiguous. At the generator or load, if it's star-connected, the line current equals the generator or load current. When the generator or load are delta-connected, the line current splits two ways and the generator/load current is 1/sqrt(3) times as much as the line current.
The confusion is based in calling one condition 'line' and the other 'phase'.
All this assumes a perfectly balanced system.
In three-phase systems, we have to measure the current in each of the three line conductors individually. There is no 'overall' current for a three-phase system. So if you know the current in each phase, then that's it! There's nothing else to calculate.
depend upon load .
It's an electrical generator converting mechanical power into electrical power. The electrical power comes out in the form of single-phase alternating current.
You can take three separate single-phase circuits from a 3-ph generator. Just use one of the live wires plus the neutral to make a single-phase supply. <<>> A three phase generator does not have to be converted to single phase. In electrical terminology any two legs from a three phase system are classed as single phase. No matter what voltage the generator is producing, L1 - L2, L2 - L3, L3 - L1 are classed as single phase legs along with L1 - N, L2 - N, L3 - N. If the generator output voltage is not the voltage that you are looking for use any two legs of the generators output voltage and use a transformer to obtain the voltage that you need.
Terminology gets misapplied but a 3-phase converter produces a 3 phase supply from a single phase supply. The only proviso is that generator, converter and motor are all suitably rated and compatible.
yes of course provided you satisfy the principle of generator a coil has to be rotated in a magnetic field. make arrangements to produce a magnetic field in either stator or rotor and also to draw produces current from the lets
If the generator is a 12 lead reconnectable, you can use something called a zig-zag connection.Check the link below. It is an installation manual for a Marathon generator. Zig-zag connections are shown on page 8. For a home, you would use the low zig-zag connection for 120/240V (in the US). One caveat: you can only load a zig-zag single-phase connected generator to a maximum of 66% of its rated load. So, a 15kW 3-phase generator would only provide 10kW single-phase power. If this doesn't quite make sense, hire a pro!IF YOU ARE NOT ALREADY SURE YOU CAN DO THIS JOBSAFELY AND COMPETENTLYREFER THIS WORK TO QUALIFIED PROFESSIONALS. If you do this work yourself, always turn off the power at the breaker box/fuse panel BEFORE you attempt to do any work AND always use a meter or voltage indicatorto insure the circuit is, in fact, de-energized.
There is no such thing as a two phase load any more. Any two legs from a three phase system are classed as single phase. If this single phase load is connected across the generator it will induce an imbalance in the output voltages of the generator. This is one reason that single phase loads on a three phase generator should be shifted around to find the best possible balance.
It's an electrical generator converting mechanical power into electrical power. The electrical power comes out in the form of single-phase alternating current.
yes we can by using one phase and neutral line
No, you can not get three phase power from a single phase generator no matter what internal connections you use. On the other hand you can obtain a single phase supply from a three phase generator by using any two phase legs as a source. <<>> I single phase generator can produce three phase by using a converter but its not efficient and does not work very well. <<>> Well there is an another way too. but one has to be precautious in that...simply short the three phases of the electricity supply n feed them with a single phase of the generator...now when the mains is bak make sure the short phases are separated again and then powered up otherwise you will be hearin blasts here n there...use ATS for automatic switching that gives you automatic transfer and can be programmed when to short and when not to..
No, you can not get three phase power from a single phase generator no matter what internal connections you use. On the other hand you can obtain a single phase supply from a three phase generator by using any two phase legs as a source. <<>> I single phase generator can produce three phase by using a converter but its not efficient and does not work very well. <<>> Well there is an another way too. but one has to be precautious in that...simply short the three phases of the electricity supply n feed them with a single phase of the generator...now when the mains is bak make sure the short phases are separated again and then powered up otherwise you will be hearin blasts here n there...use ATS for automatic switching that gives you automatic transfer and can be programmed when to short and when not to..
You can take three separate single-phase circuits from a 3-ph generator. Just use one of the live wires plus the neutral to make a single-phase supply. <<>> A three phase generator does not have to be converted to single phase. In electrical terminology any two legs from a three phase system are classed as single phase. No matter what voltage the generator is producing, L1 - L2, L2 - L3, L3 - L1 are classed as single phase legs along with L1 - N, L2 - N, L3 - N. If the generator output voltage is not the voltage that you are looking for use any two legs of the generators output voltage and use a transformer to obtain the voltage that you need.
Terminology gets misapplied but a 3-phase converter produces a 3 phase supply from a single phase supply. The only proviso is that generator, converter and motor are all suitably rated and compatible.
yes of course provided you satisfy the principle of generator a coil has to be rotated in a magnetic field. make arrangements to produce a magnetic field in either stator or rotor and also to draw produces current from the lets
If the generator is a 12 lead reconnectable, you can use something called a zig-zag connection.Check the link below. It is an installation manual for a Marathon generator. Zig-zag connections are shown on page 8. For a home, you would use the low zig-zag connection for 120/240V (in the US). One caveat: you can only load a zig-zag single-phase connected generator to a maximum of 66% of its rated load. So, a 15kW 3-phase generator would only provide 10kW single-phase power. If this doesn't quite make sense, hire a pro!IF YOU ARE NOT ALREADY SURE YOU CAN DO THIS JOBSAFELY AND COMPETENTLYREFER THIS WORK TO QUALIFIED PROFESSIONALS. If you do this work yourself, always turn off the power at the breaker box/fuse panel BEFORE you attempt to do any work AND always use a meter or voltage indicatorto insure the circuit is, in fact, de-energized.
To answer this question a voltage must be given to find the current output. Also whether the generator is three phase or single phase.
Yes. I have a several power generators for sale. Single phase, Three phase, Diesel and Petrol. What sort of power generator are you looking for exactly? Industrial, residential?
You really can't without replacing the generator end (head) with an end wound for three phase. Three phase ends are not usually made for smaller generators. Of course, once the power leaves the generator, it could be applied to a static or rotary convertor same as is used with utility power. Make sure the generator has sufficient KW to run both the load and the convertor. I agree. You can't without a converter.