answersLogoWhite

0

The current is the same in the three live wires. The voltage can be described as the line voltage (phase to neutral) or the phase voltage (phase to phase) which is larger by a factor of sqrt(3).

So a line voltage of 230 v corresponds to a phase voltage of 400 v.

User Avatar

Tyree West

Lvl 10
3y ago

What else can I help you with?

Related Questions

What is phase current?

A phase current is the current passing through a phase, whereas a line current is the current flowing through a line.


How three phase line current convert in single phase?

The current is the same in the three live wires. The voltage can be described as the line voltage (phase to neutral) or the phase voltage (phase to phase) which is larger by a factor of sqrt(3). So a line voltage of 230 v corresponds to a phase voltage of 400 v.


Why line current is greater than phase current in delta connection?

Because if you apply Kirchhoff's Current Law to the junction between the line current and the two phase currents, the line current is the phasor (vector) sum of two phase currents. For a balanced load (only), this works out to 1.732 x phase current.


In delta connection what is formula for phase current?

Line current = 1.732 x Phase CurrentCommentOnly for balanced loads.


Can you convert 415v 3 phase to 230v single phase?

415V 3 phase is the line to line voltage. The line to neutral of this supply is 230V single phase. Therefore you use one of the phases and the neutral.


Write dowen the relationshipbetween line and phase the 3phase system if voltageline and currentline are line value voltage power and current power are phase value?

A-for star connectionE(line)=1.73E(Phase)I(line)=I(Phase)&B-for delta connectionE(line)=E(Phase)I(line)=1.73I(Phase)


What is difference between line current and phase current?

A phase current is the current passing through a phase, whereas a line current is the current flowing through a line.In the case of a balanced delta-connected load, IL = 1.732 IP. In the case of a balanced star-connected load, IL = IP.For unbalanced loads, these relationships don't hold true, and must be individually calculated.


What is the connection of normal wire star or delta?

normally delta connection wired in 3 phase induction motor. during starting wiring is in Star and after running normal speed changeover to delta .beacause starting time its phase voltage equals less root3 times of line voltage ,line current and phase current equals. in Delta phase voltage and line voltage equals, and phase current equals root3 times line current


What is the difference between Load Current Line Current and Phase Current?

A load current is a current drawn by an electrical load. In other words, it is the current flowing from the source to the load.For a single-phase system, a line current is a current flowing through the line, or 'hot', conductor, while the current through the neutral conductor is called the neutral current.For a three-phase system, the three 'hot' conductors between the load and the source are called 'lines' and, so, the currents passing through them are called 'line currents'. For a three-phase system, loads are either connected between line conductors (delta-connected system) or between each line and the neutral (star- or wye-connected system), and represent the phases -so the currents passing through the loads are called 'phase currents'.For a balanced three-phase system, the line current is 1.732 times the value of a phase current, where the phases (loads) are connected in delta. For phases (loads) connected in star (or 'wye') the line current is numerically-equal to the phase currents.


How do you calculate 3 phase kWh from measuring the total phase current current?

In a balanced 3-phase system, if the three loads are star connected, the line current is equal to the load current. If the loads are delta connected, the line current is less than the load current by a factor of 1/sqrt(3).


What is neutral negetive sequence current?

Negative sequence current is defined as 3I2 = (phase 1)*(1angle 0) + (phase 2)*(1angle 240) + (phase 3)*(1angle 120) Negative sequence current is seen in three phase power systems due to natural system imbalance. Also during unbalanced fault conditions such as line to line, Line to ground, and line to line to ground faults. It is not seen in purely balanced three phase faults.


What is a line to line voltage?

In a 3 phase system, the voltage measured between any two phase is called line to line voltage.And the voltage measured between line to neutral is called phase to neutral (line to neutral) voltage.AnswerThere is no such thing as a 'phase-to-phase' or a 'phase-to-neutral' voltage. The correct terms are 'line-to-line' and 'line-to-neutral'.The voltage between any two line conductors is called a line voltage.In a three-phase, three-wire, system, the line voltage is numerically equal to the phase voltage.In a three-phase, four-wire, system, the voltage between any line conductor and the neutral conductor is called a phase voltage. The line voltage is 1.732 times larger than the phase voltage.