No, 277 volts is the line to neutral of a 480 volt wye three phase system. L1- N, L2 - N and L3 - N will give you 277 volts. L1 to L2. L2 to L3 and L3 to L1 will give you 480 volts.
In WYE 480 VAC each leg to neutral is equal to 277 volts. 480 / 1.73 (sq root of 3) = 277.
Absolutely not!! 277 volts is developed from a 480 volt power supply employing 1 conductor and a neutral. 240 volt power comprises two hot conductors and NO neutral.
Answer for USA, Canada and countries running a 60 Hertz supply service.The 277 volt heater can be wired to a single pole breaker in a 3 phase 4 wire 480 volt distribution panel. The breaker should be sized to the amperage draw of the heater. 277 volts is the star point (wye) voltage of a 480 3 phase system. 480 / 1.73 = 277 volts. The third answer is not correct, two phase legs of a 480 volt system will give you 480 volts. It is the phase leg to ground (neutral) that gives you the 277 volts.A 277 Volt heater or device may not be wired to a 480 Volt circuit or box. A 277 Volt device may only be wired to a circuit rated for 277V/480V equipment.2 legs of 480 volts will give you 277. But since you don't know the answer you probably shouldn't be doing it! Please don't kill yourself, hire a licensed electrician.Before you do any work yourself,on electrical circuits, equipment or appliances,always use a test meter to ensure the circuit is, in fact, de-energizedIF YOU ARE NOT REALLY SURE YOU CAN DO THIS JOBSAFELY AND COMPETENTLYREFER THIS WORK TO QUALIFIED PROFESSIONALS.
A reading of 145 volts is high. The first thing that I would check is the accuracy of your meter. Check the voltage reading at different locations for example, friends homes, to see if the reading is still high there. If it is check your meter reading against another meter. If you are sure that your meter and reading is correct then call the utility company and get them to check the voltage for you.
I checked with my other meter and get 120 volts!
12.6 volts as read with a digital DC volt meter.
Should read 14 volts.
From a three phase four wire distribution system the voltages would be as follows. From L1 to N - 277 volts. From L2 to N - 277 volts. From L3 to N - 277 volts. From L1 to L2 - 480 volts. From L2 to L3 - 480 volts. From L3 to L1 -480 volts.
14 volts
Commercial lighting. In a facility where 3 phase 480 volts is needed for machinery, 277 is also readily available because each leg of 480 to ground is 277 volts. This way numerous supply transformers are not needed in a commercial building.
All voltage reading are usually read with a volt meter. This volt meter can be a hand held unit like electricians use.
The reason 277v leg to leg does not measure 554 volts is each phase of the system is 120 degrees out of phase with each other and there fore will not read 554v leg to leg but 480v lag to leg. If you take 277 times the square root of 3 it will equal 480. The meters measure Root Mean Square or rms voltages and are designed to take this into their readings.
Not unless it is rated for that voltage. You can likely find a step down transformer from 277 volt sto 120 volts.
A fully charged 12 volt automobile battery will read 12.6 volts with a digital volt meter. It will read 12.4 at 75% charge, 12.2 volts at 50% charge and 12 volts at 25% charge.
No, 277 volts is the line to neutral of a 480 volt wye three phase system. L1- N, L2 - N and L3 - N will give you 277 volts. L1 to L2. L2 to L3 and L3 to L1 will give you 480 volts.
The voltage of 277 is the wye connection of a 480 volt three phase supply. The only way to reduce 277 to 120 volts is with a step down transformer.