Engineers usually spec that the insulation test be 5 Megohms to ground. In reality in outdoor applications 2 Megohms is quite acceptable.
motor energy
You can but the motor may not run, however you will not burn the motor.
It sounds like there may be a partial short in one the the three motor windings. What should be done it to megger the motor. This will tell you if all three winding are not shorting to each other and not shorting or partial shorting to ground. If the reading is over 2 megohms to infinity then the motor is all right. Below .5 megohms (500000 ohms) the motor should be cautiously used and will probably have to go in for a rewind. If the burning is in the motors junction box then the burning could be caused by loose conections between the feeder wires and the motor winding leads.