Generally a single-phase transformer will have twowindings. One of the Low voltage side and one on the high voltage side. North-American distribution Transformers will have three: one high-voltage winding, and two low-voltage windings connected in series.
However...
...a single-phase transformer can also have several primary and several secondary windings. The primary windings can be connected in series or in parallel with each other, as can the secondary windings. For example, taking the primary winding as an example, it could consist of two 120-V rated windings: if connected in series, it could be supplied with 240 V without exceeding its voltage rating; if connected in parallel, it could be supplied with 120 V without exceeding its voltage rating. Multiwinding single-phase transformers allow for a variety of connections.
When working on a current transformer the secondary windings must be shorted. <<>> Properly loaded
A step-up transformer needs more turns on the secondary windings than on the primary windings to increase the voltage.
The dc tests that can be done on a transformer are to measure the resistance of each windings and to measure the insulation resistance between the windings and between each winding and the transformer case.
If this refers to a wire wound transformer, as it sounds then there is likely only two possibilities : the input voltage has dropped prier to entering the primary windings or there is a short in the windings some where within.The only other possibility I can think of is : This is a trick question and the transformer is a step down transformer.
The changing magnetic flux in the iron core of the transformer induces a voltage in the windings.
Transformer has windings
The # of windings in a transformer are based on the primary and secondary voltages the transformer is rated for not the way the windings are connected.
When working on a current transformer the secondary windings must be shorted. <<>> Properly loaded
it has three primary windings & three secondary windings.
There are normally only one set of primary windings in a transformer. Some may have multiple windings though so that they can cover a wider range of input voltages.
The container the transformer core and windings are placed inside is the tank.
If a transformer has 20 primary windings and 100 secondary windings, it is a step up transformer. If the secondary voltage is 25v, the primary voltage will be 5v, because the turns ratio is 20 to 100, or 1 to 5.
They have both.
A step-up transformer needs more turns on the secondary windings than on the primary windings to increase the voltage.
Transformer step-up/step-down voltage is turns-ratio, so if a transformer has 20 primary windings and 100 secondary windings (a turns-ratio of 1 to 5) and the secondary voltage is 25, then is the primary voltage is 5.
Physicially it has transformer tank, conservator, bucholz relay , windings, oil
Actually it depends on the air gap between the core and the windings of the transformer. This is the reason why stepped core is used in medium and large transformers as it decreases the air gap between the windings and the core of the transformer.