5 kV ac means 5 kV rms, which represents a peak voltage of 5 x sqrt (2) kV, or 7.07 kV. So the dc test should provide 7070 volts.
The test equipment used to test high voltage cables is a hi-pot test where a high DC voltage is a applied to the cable. This voltage can be from 150% to 200% of the working voltage of the cable.See related links below.
Lower voltages are required if connected to the low voltage side. The testing facility may not have a gen set large enough to test from the high voltage side.
no voltage will be induced on the secondary side of the motor as the windings will become saturated.
in short circuit test we apply rated current with the LV side shorted.so the applied voltage will be very low. iron loss depends on the applied voltage.so it is neglected
2500 volts
A high dc voltage would be applied to test the insulation between the windings.
DC
The test equipment used to test high voltage cables is a hi-pot test where a high DC voltage is a applied to the cable. This voltage can be from 150% to 200% of the working voltage of the cable.See related links below.
Lower voltages are required if connected to the low voltage side. The testing facility may not have a gen set large enough to test from the high voltage side.
A test done on a transformer. The voltage at the power frequency is ramped up to verify the transformer is capable of handling the stresses due to switching and natural phenomena (lighting strikes).Withstand Voltage:The voltage which has to be applied to a test object under specified conditions in a "withstand test" is called the "withstand voltage".
the winding would burn....
no voltage will be induced on the secondary side of the motor as the windings will become saturated.
in short circuit test we apply rated current with the LV side shorted.so the applied voltage will be very low. iron loss depends on the applied voltage.so it is neglected
2500 volts
Make sure that the test meter is on the correct voltage scale. Place one lead on one of the conductors to be tested and the other lead on the other voltage source conductor. The reading you obtain will be the voltage potential between the two conductors.
A: It is not fixed to any voltage. The manufacture test them as a sample on a lot and to have a specific breakdown it must not conduct within certain voltage applied. If it fail the testing the whole lot is rejected by default
You always need to apply rated voltage to the primary in open circuit test (oc test helps to find iron loss which depends on the voltage applied which remains constant)so with smaller voltage applied to the low voltage side rated voltage can be achieved in primary.Further,the ammeter ,voltmeter and wattmeter connected to the primary can be of lower rating.