Could be anything At Fault. Unplug the compressor and try using your washer. If it works, then you have a fault with your compressor. If it still doesn't work, do what should have been done in the first place: call an electrician.
First impressions would be failure in the compressor internal circuitry, wire gauge too small, outlet underrated, and/or breaker size to high for compressor rated load. Additionally, a loose connection at the outlet could have caused arcing.
The inlet side is the low side - this will have the larger hose. On a Thermal Expansion Valve system, this hose will run from the evaporator outlet to the compressor inlet. On a Fixed Orifice Tube system, this hose will run from the accumulator outlet to the compressor inlet. The outlet side is the high side, and the hose will run from the compressor outlet to the condenser inlet.
If the GFI outlet is tripped (the outlet, not the breaker) then it is telling you there is a ground fault which must be fixed. If the GFI outlet is not tripped, and the breaker is not tripped, but it is still not providing power, then you have a loose connection or a wiring error.
Electric motors and GFI's do not get along. the initial draw to get the compressor going is usually enough to trip the GFI. Turn the breaker off and switch the GFI for a regular outlet and you will solve your problem.
You need to remove everything connected to the breaker and see if it still trips. If it does it is in the wiring or possibly a bad breaker. Disconnect load from breaker and see if it still trips. If so replace the breaker. If it still trips and is not the breaker then you will have to start pulling each outlet from wall and checking after disconnecting each outlet.
It depends on which temperature you have at the place where the air compressor is placed. But a normal air compressor takes 300 watt to run. The standard outlet which comes with your air compressor when you buy it will be good.
Not if the GFCI breaker is supplying the circuit you are wanting to put the GFCI receptacle into.
If it is a 30 amp breaker then it is a 240 volt outlet.
If there is any additional load on the outlets greater than 2.5 amps the breaker will trip. Loads of 1500 watts should be on a dedicated breaker. If the total load exceeds 15 amps the breaker will operate. However many of the outlets might supply only lights, TVs or nothing at all, so in those conditions it's OK.
It means the breaker has been tripped. There are two possible ways to reset it - some have a button on the outlet (there may be several outlets on one circuit, so you may have to look around) the other is the main breaker in your breaker box. You'll need to find a reset the breaker.
no. the breaker is 40amps.fire hazard
Compressor outlet to metering device inlet.