answersLogoWhite

0


Best Answer

No. Neutral, by definition, is grounded at the secondary of the service transformer, and again at the distribution panel. It is also carried from pole to pole when there is secondary running between poles, or along other means, and it is grounded at each and every point. It is never connected to ground anywhere else downstream of the distribution panel, and it is not OK to use ground on a branch circuit as a current return.

The reason for this is to ensure that the hot to ground voltage potential at any point in the branch circuit cannot exceed a safe value. It is also used, in GFCI breakers, to detect a ground fault by noting that the current in hot and neutral do not balance each other.

In the worst case, theoretically possible, although highly unlikely because of the multiple grounds located upstream of the distribution panel, if neutral were completely ungrounded, the neutral/hot pair could rise in voltage up to the primary line voltage. In a typical 13.2 KV primary, stepping down to 120/240 V split phase with a neutral, the neutral/hot conductors could rise to 7.62 KV, relative to ground, although not relative to each other, a highly dangerous and lethal situation.

User Avatar

Wiki User

12y ago
This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: Is it ok not to ground the neutral at secondary side of transformer?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Continue Learning about Engineering

Do all electrical power sources flow to earth e.g. Secondary winding of an isolating transformer with no earth connection on the neutral line?

There are situations where the secondary of a transformer is not grounded and the neutral is not connected to the neutral of the primary. This can cause a potential shock hazard so the secondary side needs to be protected.


Why is a transformer's split phase secondary neutral grounded?

The secondary of a transformer is isolated (floating) relative to the primary, so there is no absolute reference relative to earth ground on the secondary side. By connecting the neutral to ground (earth ground that is) this creates an absolute reference. This also creates a leakage path to earth ground, now that the secondary voltage is referenced to earth ground, but that is more desirable than not because otherwise something else in the system might improperly provide that reference.


Does a 3 phase motor starter with a 120 volt coil need a neutral to the coil?

Usually for this type of installation there is a control transformer installed in the starter enclosure. The primary of the transformer is the motors line voltage and the secondary is the control voltage which is usually 120 volts. In Canada the control transformer needs fusing on the secondary side of the transformer. In the US the transformer needs fusing on the primary and secondary sides of the transformer. The secondary side of the transformer's terminals are labeled X1 and X2. The X2 lead is grounded to the starter's enclosure. From this point out the wire is then termed the circuit's neutral wire. This wire then connects to one side of the magnetic starters draw in coil. Yes, 120 volt coil would require a neutral, this could be derived from the control transformer if it has one or from an external source.


Differentiate delta to delta connection of the transformer to delta to Y connection?

In delta to delta there will be no ground on both primary and secondary sides. Leave the primary side but we take care on secondary side. If there any fault occurs on the secondary then there will be unbalanced voltages between the phases results in the flow of current through the secondary windings so only we are using star on the secondary side while having neutral to prevent such a current flow.


What is the use of a transformer with turns ratio 1?

isolation if you are in the usa and must service electronics the neutral is grounded the power supply is a voltage doubler one side is 170v+ to ground the other is 170v negative to ground so if you run the power thru the transformer first you stand a better chance of staying alive these transformers are quite often used to trigger scrs or triacs for the same reason

Related questions

Why is the neutral point grounded on a transformer?

The secondary side (output) of a three phase transformer develops a "separately derived system". That is why you do notsupply a neutral to a three phase transformer. It develops its own reference to ground by being bonded to the transformer casing and to a substantial earth ground, such as a ground rod. The XO tap on a transformer provides the neutral to the secondary line. It will have a double wire lug. The neutral wire going to the panel being supplied goes under one lug and the same size wire is to go to the ground lug on the transformer chassis The ground lug is also a double with the other lug to be wired to the earth ground.


Do all electrical power sources flow to earth e.g. Secondary winding of an isolating transformer with no earth connection on the neutral line?

There are situations where the secondary of a transformer is not grounded and the neutral is not connected to the neutral of the primary. This can cause a potential shock hazard so the secondary side needs to be protected.


What is the difference between an isolation transformer and distribution transformer?

in isolation transformer earthing is not provide on secondary side but in ordinary transformer neutral of secondary side is earthedAnswerAn isolation transformer is a 1:1 ratio transformer; its function is to electrically isolate the secondary side from the primary side without changing the voltage. An example of an isolation transformer is the one used in a shaver socket.A distribution transformer is a step-down transformer, used within the electricity network's distribution system. An example of distribution transformer is a pole-mounted transformer, supplying low voltage to residences.(Of course, all mutual transformers provide electrical isolation between primary and secondary.)


Why is a transformer's split phase secondary neutral grounded?

The secondary of a transformer is isolated (floating) relative to the primary, so there is no absolute reference relative to earth ground on the secondary side. By connecting the neutral to ground (earth ground that is) this creates an absolute reference. This also creates a leakage path to earth ground, now that the secondary voltage is referenced to earth ground, but that is more desirable than not because otherwise something else in the system might improperly provide that reference.


Does a 3 phase motor starter with a 120 volt coil need a neutral to the coil?

Usually for this type of installation there is a control transformer installed in the starter enclosure. The primary of the transformer is the motors line voltage and the secondary is the control voltage which is usually 120 volts. In Canada the control transformer needs fusing on the secondary side of the transformer. In the US the transformer needs fusing on the primary and secondary sides of the transformer. The secondary side of the transformer's terminals are labeled X1 and X2. The X2 lead is grounded to the starter's enclosure. From this point out the wire is then termed the circuit's neutral wire. This wire then connects to one side of the magnetic starters draw in coil. Yes, 120 volt coil would require a neutral, this could be derived from the control transformer if it has one or from an external source.


What is the resistance of the secondary of a 24 volt transformer?

For the 120/24V transformer, the primary side is around 50ohm, the secondary side is 2~


Differentiate delta to delta connection of the transformer to delta to Y connection?

In delta to delta there will be no ground on both primary and secondary sides. Leave the primary side but we take care on secondary side. If there any fault occurs on the secondary then there will be unbalanced voltages between the phases results in the flow of current through the secondary windings so only we are using star on the secondary side while having neutral to prevent such a current flow.


What is the xo connection in a transformer for?

The X terminal identification on a transformer designates the secondary side of the transformer. Depending on the type of secondary windings, the terminals can be designated as X1, X2, X3 and X4. On a single winding secondary the terminals will be X1 and X2. The "hot" wire will be supplied from the X1 terminal and the return wire will use the X2 terminal. On most control transformers the X2 terminal should be grounded to the control panel's chassis.


What wires conductors would go under x lug in a transformer?

The primary side of a transformer is identified as the H side, eg. H1,H2,H3,H4. The secondary side of a transformer is identified as the X side. Eg. X1, X2. Usually X1 goes to a fuse and then to the load, X2 is usually the neutral side and is grounded to the body of the transformer.


What happens to the current as the voltage is increased by the step up transformer?

Compare a transformer to a balancing act. Both side need to remain equal.The primary side of the transformer is the supply side and the load is connected to the secondary side of the transformer.The load governs the current of the secondary side of the transformer and the voltage of the secondary side must match the voltage that the load required to operate.The ratio of the transformer will determine what the voltage of the secondary side is as compared to the voltage that has to be applied to the primary.The current of a step up transformer will be higher on the primary side that that of the secondary.Apply voltage and current to this concept and you will see that the transformer will remain balanced.The size of the transformer is always calculated from the secondary side of the transformer and the value is written in VA or KVA where V = voltage and A = amperage. Power factor is also taken into consideration when calculating the size of the transformer to be used.


What is the term used to describe output side of a transformer?

The secondary.


Which side of a transformer is the load connected to?

It is connected to the secondary side.