1 HP is 746 watts therefore 5 HP is 3730 watts. Allow 90% efficiency that means 4144 watts are required from the supply, allow a power factor of 0.8 which means that 5180 VA are required. Dividing by the voltage gives a load current of 21.6 amps, so a 30-amp supply should be all right.
In Europe they have both single phase and three phase.
No A intermediate switch can not be used to change three phase to single phase.
Any load that needs three legs from a three phase system can not be considered single phase. Single phase from a three phase system only needs a connection to two legs.
In a typical 3 phase system you have multiple voltages and configurations that can be used in either single phase or 3 phase, depending on how the circuit is designed. A single phase system is just single phase. You can have multiple voltages but it is always single phase.For example, in a typical 277/480v 3 phase system you can power 277v single phase lighting or equipment, 480v single phase lighting or equipment (which uses 2 legs of the 3 phase system but operates like any other single phase circuit), or 480v 3 phase motors.When comparing motors, a 3 phase motor will be substantially smaller than a single phase motor of the same horsepower. You can also reverse a 3 phase motor by switching any 2 leads. A single phase AC motor runs in one direction regardless of how the leads are connected.AnswerFor a given load, a three-phase transmission system requires less volume of copper in terms of conductor size, compared to single phase, so it is more economical to use three-phase.
Phase to phase, two wire is classed as single phase. If the voltage from the phase to phase match the device's operating voltage, then connecting the device will allow it to operate.
If the air conditioner is designed for three phase, then it will not run, and could be damaged, by single phase power. Otherwise, no.
If an air condition is single phase, then it can only be connected to a single phase source. Since any two legs of a three phase source are considered single phase, there is no conflict, except to note that the individual phases of the three phase source match the voltage requirement of the air conditioner.
Most standard residential service is single phase. Therefore, I would say most all residential A/C units are single phase.
Not necessarily. Two single-phase supplies could be supplying the same phase, which means you don't get the same range of voltage options you get with a true two-phase supply.
Depending on who does the work it could be less expensive than getting a different air conditioner. The compressor will also need a capacitor and some rewiring. The old unit could have a 3 phase blower motor also which could run the price up even more. Although the changes can be made, the warranty at best will probably be a one year warranty and a new unit could have a 5-10 year warranty.
Single phase.
There is no such thing as a two phase instrument. There is only single phase and three phase. You can only have: single phase/ one pole single phase/ two pole three phase/ three pole
Yes, there is a difference between single phase and three phase circuits.
In Europe they have both single phase and three phase.
By having a transformer with 3 phase input and single phase out put
There is no difference in horsepower. The manufacturer builds the air conditioner. Engineers calculate and tell the manufacturer how much power is going to be required to make it operate. Smaller units will probably use lower voltage with lower horsepower to operate efficiently. The bigger the unit will take higher horsepower to operate. There comes a point when single phase, low voltage use will not work due to the unavailability of high horsepower, low voltage motors. At this point three phase systems are used with higher voltages to operate the motors. Examples of a 10 HP motor at different voltages. Single phase - 115 volts 100 amps, 230 volts 50 amps. Three phase same HP - 200 volts 32.2, 230 volts 28, 460 volts 14 and 575 volts 11 amps. As you can see if the air conditioner needs a 10 HP motor at single phase 115 volts, a feeder supply of 100 amps would be needed. This compared to the same air conditioner using a three phase 575 volt system which draws 11 amps.
working of single phase preventor