Phase to phase, two wire is classed as single phase. If the voltage from the phase to phase match the device's operating voltage, then connecting the device will allow it to operate.
The standard nominal voltage in Canada for a single-phase residential supply is 240/120-V split-phase supply.
In three phase: I = (three phase VA) / (sqrt(3) x (phase to phase voltage)) for single phase: I = (single phase VA) / ((phase to neutral voltage)) keep in mine three phase VA = 3 x (single phase VA), and phase to phase voltage = 1.732 x (phase to neutral voltage) Therefore the single phase and three phase currents are the same (ie, the three phase currents are the same in all three phases, or balanced). But don't get available current and available power confused (KVA is not the same as KW).
To answer this question the motor's voltage must be stated and whether the supply voltage is single phase or three phase.
Yes 230 volts is classed as single phase but it is not the only single phase voltage. If you take any two legs from a three phase system, the voltage from these legs is also classed as single phase. The 230 volt single phase is the output of a transformer whose primary is one leg of a three phase primary high voltage system. The 230 volt secondary is center tapped to give 115 volts before the tap and 115 volts after the tap, hence the common voltage of 115/230 that is used in North America.
This depends on what voltage the range is rated for and if it is single phase or three phase. At 220 volts single phase it is about 60 amps, 240 v single phase , 53 amps and at 480 v three phase about 15 amps.
The single phase voltage in India is 230v when we check with the phase and the nutral single line
Lead the voltage waves
Single phase and three phase voltages are not related to the frequency at which the voltage is generated. The frequency at which voltages are generated is governed by the speed of rotation of the generating device.
Three-phase voltage in Germany is 400V, single-phase voltage is 230V.
To obtain a single-phase supply from a three-phase supply, the single-phase load must be connected either (a) between any pair of line conductors, or (b) between any line conductor and the neutral conductor. Of course, the voltage obtained from either of these connections must match the voltage rating of the load.
It is 230V single phase and 440V in 3 phase system at 50 Hz.AnswerIf the single-phase voltage is 230 V, then the three-phase voltage must be 400 V, not 440 V. The line voltage is 1.732 times the phase voltage.
Ac voltage
The same as in single phase with the same RMS voltage.
The standard nominal voltage in Canada for a single-phase residential supply is 240/120-V split-phase supply.
The single phase voltage in India is 230v when we check with the phase and the nutral single line
No.
Single phase voltages vary throughout the world. To answer this question a basic voltage or country voltage has to be stated.