An air circuit breaker, or air-blast circuit breaker, is a type of circuit breaker used in high-voltage transmission/distribution systems. It uses compressed air to (a) operate its tripping mechanism, and (b) to extinguish the arc created by a fault current.

A miniature circuit breaker is a type of circuit breaker used in low-voltage applications, such as the protection of lighting and power circuits in a domestic residence. It uses a spring to operate its tripping mechanism, and relies on the speed of operation to extinguish the arc created by a fault current.

Apart from the fact they are both designed to interrupt a fault current, there is really no other similarity.

User Avatar

Wiki User

12y ago
This answer is:
User Avatar
More answers
User Avatar

Wiki User

12y ago

it is circuit breaker used as safety device whenever large rating current flows through it it trapped and breaks the circuit and avoid the accident,its basic principle based on mechanically.

This answer is:
User Avatar

User Avatar

Wiki User

13y ago

Physical size, current rating and voltage rating. Also the means by which over-current can vary may change.

This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: What are the differences between a Miniature Circuit Breaker and normal Circuit Breaker?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Continue Learning about Natural Sciences

What are the differences between a vacuum breaker and a SF6 gas circuit breaker breaker and a sf6 gas circuit breaker?

vcb is have vaccume and sf6 cb is filled with sf6 gas which will have good arc quencing property


Need of isolator on both side of circuit breaker?

Before anyone is allowed to work on a high-voltage circuit breaker, it must be tripped, electrically isolated, earthed (grounded), barriers/warning notices put in place, and a permit to work document issued by an engineer to the senior member of the maintenance crew. 'Isolation' means a physical (and visible) break in the conductors between the circuit breaker and any potential source of supply -and this is provided by placing isolator switches on each side of the circuit breaker. Without these isolators, the circuit breaker would remain energized, even though the circuit has been broken by the circuit breaker.


Working principle of air circuit breaker?

circuit breaker is a switch that turned off when there is a short circuitAnswerAn air circuit breaker is a high-voltage circuit breaker whose tripping and closing mechanisms are (usually) operated pneumatically, and whose arc is extinguished by a blast of air -hence the alternative name 'air-blast circuit breaker'.


What is the difference between b type c type and d type miniature circuit breakers?

The different types are rated by how much current above its rated current will trip the breaker instantly (less than 100ms). Type B 3-5 times. Type C 5-10 times. Type D10-20 times. For example a 10amp type B breaker will instantly trip (less than 100ms) at between 30-50amps.


What is the Difference between circuit breaker and a relay?

A circuit breaker is designed to break a circuit which is carrying current at the time. Where large currents and/or voltages are present, the opening of the circuit may induce dangerous arcing, so means such as air blast must be used to "blow out" the arc. Air breakers are being phased out and replaced with vacuum or SF6 breakers. An isolator is only designed to isolate a circuit or other component after the current has already ceased, so it doesn't need to have any means to stop the arc. Thus in high voltage/high current installations such as in power stations or grid switching stations, the initial operation to isolate the circuit, whether planned or as a result of a fault, is by the circuit breaker, the isolator is then used to isolate the circuit breaker for maintenance or repair. The difference between a circuit breaker and a contactor is that a circuit breaker can break fault current while a contactor cannot. A contactor is typically implemented in series with a fuse which serves to interrupt fault current. An isolator and a contactor are not synonymous.

Related questions

What is the difference between fuse and MCB?

what is the difference between miniature circuit breaker and fuse


What are the differences between a vacuum breaker and a SF6 gas circuit breaker breaker and a sf6 gas circuit breaker?

vcb is have vaccume and sf6 cb is filled with sf6 gas which will have good arc quencing property


How does a vacuum circuit breaker operate?

In a vacuum breaker the moving contact and fixed contact are sealed inside a vacuum chamber. Electrons cannot flow in a vacuum, therefore as soon as the moving contact seperates from the fixed contact the arc meets an infinite resistance and is immediately extinguished. Because of this, the gap between the fixed and moving contacts when the breaker is open need only be a tiny amount.


What is difference between spn and tpn mcb db?

TPN MCB means Triple pole Neutral Miniature Circuit Breaker where as SPN MCB means single phase Neutral MCB.


What is difference between the mcb and rcb?

MCB stands for miniature circuit breaker , which provides protection against over current. the setting is not adjustable. RCB stands for residual circuit breaker which provides protection against earth fault as well as over current. It monitors the current difference between phase and neutral and if the difference is more than rated value say 200 milli amps it will trip.


Is there continuity between a three pole circuit breaker terminals?

No, the three individual poles of a three phase circuit breaker are not electrically connected to each other. If they were, a fault would develop internal to the breaker.


What is the difference between MCB and MCCB?

MCB (Miniature Circuit Breaker)-rated current not more than 100 A. Trip characteristics normally not adjustable. Thermal or thermal-magnetic operation. Breakers illustrated above are in this category.MCCB (Molded Case Circuit Breaker)-rated current up to 2500 A. Thermal or thermal-magnetic operation. Trip current may be adjustable in larger ratings. MCB (Miniature Circuit Breaker)-rated current not more than 100 A. Trip characteristics normally not adjustable. Thermal or thermal-magnetic operation. Breakers illustrated above are in this category.MCCB (Molded Case Circuit Breaker)-rated current up to 2500 A. Thermal or thermal-magnetic operation. Trip current may be adjustable in larger ratings.from Manu anand


Need of isolator on both side of circuit breaker?

Before anyone is allowed to work on a high-voltage circuit breaker, it must be tripped, electrically isolated, earthed (grounded), barriers/warning notices put in place, and a permit to work document issued by an engineer to the senior member of the maintenance crew. 'Isolation' means a physical (and visible) break in the conductors between the circuit breaker and any potential source of supply -and this is provided by placing isolator switches on each side of the circuit breaker. Without these isolators, the circuit breaker would remain energized, even though the circuit has been broken by the circuit breaker.


What are the differences between a parallel and a series circuit?

.


What is a difference between 10KA and 22KA circuit breakers?

The previous answer is incorrect, and I would advise that user to not give out information if they are going to give completely misguided information. The interrupting rating of a breaker is the maximum current that the breaker is designed to handle, at the breaker's rated voltage, before damage will occur to the breaker. A breaker will trip at FAR LESS than the interrupting rating, but it is extremely dangerous to expose the breaker to any situation where it will have more than the rated interruption current. the breaker is designed for. The reason some breakers are rated at 22kA instead of 10kA is because they typically have far larger conductors hooked up to them, so with the lowered impedance on the circuit there is more of a chance for the breaker to experience a higher fault current at the breaker. So electricians install 22kA breakers to handle the higher "available fault current."


What is different Circuit Breker And Isolater?

I think that the questioner is asking what is the difference between an isolator and a circuit breaker.A circuit breaker is a switching device designed to interrupt a fault current.An isolator is not intended to break a live circuit but, rather, to provide a visible separation between a circuit component and live conductors.For example, isolators (or 'disconnectors' in US parlance) are located on either side of a high-voltage circuit breaker. If the circuit breaker requires maintenance, then the procedure is to:a. trip the circuit breaker.b. open the isolators on each side of the circuit breaker, so there is a visible gap between the circuit breaker and the 'hot' conductors.c. apply temporary earths (grounds) between each isolator and the circuit breaker.d. complete a 'permit to work' card.e. begin work.


What is Vacuume Circuit Breaker?

A vacuum circuit breaker is a high-voltage circuit breaker whose contacts separate within a vacuum dielectric. The vacuum contributes to extinguishing the resulting arc because ionisation cannot take place while the arc is stretched between the separating contacts.