Best Answer

There are a few causes for this but basically in 90 % of the cases it will boil down to improper combustion, caused by air/water/dirt in oil getting caught with in the strainer, gummed up filter and or nozzle, loss of flame rectification proving/sensing. IE. If the eye, located within burner tray is bad or dirty, and finally the draft and venting of the flue needs to be at a 0.02" IWGH.

I have found that almost always that if I know the Oil filter and canister are is clean, the oil tank is full,

First I will set up and bleed any air out of oil furnaces fuel line/lines to pump, Turn off the power to burner, remove the bolts in the top of electrode section of burner, mark very clearly with a Sharpie the current position of copper oil feed line into tray for gun burner and I also out line the position of the flared retaining nut

I then loosen retaining nut on feeder line, reach in and remove tray from burner @ this time inspect and or replace nozzle, place plastic Orange for Beckett, red for Reiello cheater Z dimension cap on nozzle

replace into burner and push it true and lined up flat and sound. we then remove the tray again, retrieve plastic z dim cheater off of nozzle, set electrode ends to gap the correct distance on z dim cap and once again reinsert into tray. Next unscrew port at bottom of burner and affix oil gauges and test pumps inlet oil psi. You should then adjust the psi to what it is listed for on burners data plate to start, this can be raised to make fuel mix more or less lean by adjusting amount of oil and at what pressure it is passing through nozzles screening. If the pressure is raised the amount of oil used during lite off is increased, but the flash point of said oil is actually being lowered by breaking apart the fuel molecules at a higher pressure through screening of nozzle there is a greater Atomization of oil, thus a larger concentration O2 molecules around the oil molecule, causing a hotter more efficient flame.

Located on the data plate on the furnace or boiler is the other important info for your reference, here are the set up requirement's of the furnaces data plate the nozzles GPM and angle of spray pattern.

If this is all set up prior to initial firing, then after the furnace is fired, the smoke should be close to a zero.

This you must test with a hand pump and smoke paper. The combustion process should continue on with out bogging out long enough to let you fine tune the primary air and make any minor air shutter adjustments to secondary air side that are always needed.

You need to both monitor and record the carbon dioxide, O2 % as well as the normal monitoring and recording the CO Levels and temperature of gasses within flue.

As a Professional, reputable and safe tech you need to get comfortable with combustion Analysis as well as the levels that your combustion budget require in order to assess and fine tune any combustion product not only no 2 fuel oil furnaces and boilers but all natural gas and LP combustion appliances.

You will need to drill not one but two holes into the flue in this case. The first hole drilled should be located below the Barometric damper, this is the hole for your combustion testing, the next should be about 12" if possiable beyond the Barometric damper. This port is for your draft measurement, it is taken here so as to account for the damper in the drafting process, and it allows you to set up the counter weight within damper accuratly. If analisys of combustion is done after damper the numbers will be off set with extra O2 being introduced through barometric damper.

These tests require a combustion analyzer and a digital or Analogue Manometer for flue side of process and a smoke pump w/ clean paper, ring gauge for smoke test, and an oil pressure gauge. I use 2 oil gauges so that I can take my return oil or back pressure at same time as the inlet pump pressure is assessed.

I know these tools arnt cheep but after doing it this way I would'nt go back to not using a combustion analyzer.

I personally am certified as a Combustion analyst and am most comfortable using N.C.I combustion Guide lines as my standards. My Analyzer is a Bacarach Fyre-rite Pro, But you may also have used or currently use the I.F.G standards combustion charts and A Field-Piece combustion Analyzer or whichever is your personal standards for excelence and your local municipalities requirements.

User Avatar

Wiki User

11y ago
This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: What causes having to reset a furnace fuel oil heater?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Related questions

You are having to reset your electric water heater breaker daily?

Likely one of the two electric elements is going out which creates very high resistance in the circuit and therefore draws very high current (amps) and causes the breaker to trip.


What should I do if my heater does not work after power outage?

I'm not sure why your furnace would shut off after a power outage but first check your breaker in the breaker box to make sure it is in the on position. If this is not the problem remove the cover on furnace and look for a red reset button on the pump. Press this button and hold for a second or two and you furnace should restart. If however it shuts down again you have other problems and will need a furnace repairman.


Is there a heater core reset switch on a 1993 Lincoln continental?

No.


On your 2002 ZX2 why are the OBD monitors not ready?

There are two main causes for the readiness monitors being set to not ready: One, your battery was disconnected and reset the monitors; or your monitors were reset intentionally, such as having your check engine light (MIL) reset by someone using a scanning tool


I Filled my empty oil tank today and still no heat or hot water why?

Reset on the furnace or breaker tripped?


How do you Restart a Furnace After Running out of Oil?

Make sure you press reset button on oil burner longer than forty seconds because that is the manufacturers way of idiot-proofing the furnace against the homeowner.


How can i reset my ceramic fan heater model number ptc-903b?

Model number ptc -903b. Ceramic fan heater, by climate keepers. Do it have a rest button


How do you reset the Mainten?

hold reset botton with the key off then turn the key to the on position and that's it you will see ------ on your odometer while it reset takes about 5 secs. What causes light to go from green to yellow? why reset?


How do you reset the light?

hold reset botton with the key off then turn the key to the on position and that's it you will see ------ on your odometer while it reset takes about 5 secs. What causes light to go from green to yellow? why reset?


What can we do if our Curcuit breaker tripped on the heater and will not reset?

shut off the power to the box, switch out the breaker and resture the power


Where is the fuel pump reset switch on a 1998 ford explorer?

passenger side floorboard under the heater unit


Can I unhook battery cables and install new battery in a 2008 chrysler town and country without having to reset a computer?

Yes, no reset is required.Yes, no reset is required.