RCD stands - Residual Current Device. Normally It measures current on phase & neutral and if there is any change or difference (Should be Phase I - Neutral I = Zero) even 30mAmps RCD trips to break the circuit to avaoid any damages to equipments as well as human beings. Its same as ELECB / RCCB.
A GFCI trips when it detects a difference in the amperage going to the outlet and what is coming back. Even 4-6 miliamps difference will trip the outlet.
The trip coil has the whole circuit load amperage flowing through it. Thepurpose of the breaker is to only allow current up to its trip point. That is the only way that the breaker can sense if the current is within the limit rating. If the circuit load amperage becomes greater that the breaker rating it will trip. The trip coil that you refer to is a magnetic trip which senses the magnetic field that surrounds the wire. Breakers also have a thermal trip which senses a heat build up on the current flowing through it. If the breaker is in a high ambient temperature it will lower the rating on the breaker.
20 amps on the circuit will trip it unless it is is broken. Then it may trip with a lower current or not at all... Any resistance added to the circuit from a bad or dirty connection will add to the total current causing it to trip sooner than expected.
Current.
GFCI's trip on an un balance between the current on the "hot" wire and the current on the neutral wire
A GFCI trips when it detects a difference in the amperage going to the outlet and what is coming back. Even 4-6 miliamps difference will trip the outlet.
The trip coil has the whole circuit load amperage flowing through it. Thepurpose of the breaker is to only allow current up to its trip point. That is the only way that the breaker can sense if the current is within the limit rating. If the circuit load amperage becomes greater that the breaker rating it will trip. The trip coil that you refer to is a magnetic trip which senses the magnetic field that surrounds the wire. Breakers also have a thermal trip which senses a heat build up on the current flowing through it. If the breaker is in a high ambient temperature it will lower the rating on the breaker.
20 amps on the circuit will trip it unless it is is broken. Then it may trip with a lower current or not at all... Any resistance added to the circuit from a bad or dirty connection will add to the total current causing it to trip sooner than expected.
It is 5 miles per hour.
If you want to know the amperage for each outlet on a power strip then check the nameplate current on the device that is plugged into that outlet on the power strip. Power strips usually have their own breaker that will trip at 15 amps. If you load the strip to its maximum capacity there is a good chance that it will trip before the distribution circuit breaker will trip. You can not simply divide the total amps by the number of outlets as each device will have a different amperage and depending on where it is plugged into the strip these amperage's in a set position will change.
A GFCI measures difference in output to return current. A Overload breaker in your panel is what trips from too much current. many are time delay and will not trip immediately from the less than a second of start up current spike.
An overload trip is due to too much load on a circuit (for example, my wife running a hair dryer and portable heater on the same outlet). An over current trip is the same thing, but it can also refer to an actual fault condition where conductors have come in contact with eachother/shorted.
A standard circuit breaker will sometimes (but not necessarily) trip in such a situation because the amperage exceeds the rating for that breaker. A ground fault interrupt breaker will invariably trip because the amperage on one side of the circuit significantly exceeds the amount returning on the other side of the circuit.
It looks like you are asking if a higher amperage motor can replace a lower amperage motor. It depends on what the amperage difference is. If the amperage is high enough to move the capacity of the wire out of its rated value then it should not be done.Remember motor conductors have to be rated at 125% of the motors nameplate amperage. As the amperage increases so does the HP and the motor's protection will also have to be increased or the motor will trip the lower overload protection settings.Also keep in mind that if the motor is three phase, running a motor with higher HP on a load that does not need the extra HP, it will lower the power factor of the supply distribution.
The cost of a shunt trip breaker depends on the amperage and number of poles the circuit connected to it needs. The cost of the shunt trip over a conventional breaker is substantially more.
Current.
The conjugation makes of the verb to make is used for the present tense, third person singular (he, she, or it makes)."It makes no difference how you dress in your own home.""He makes the game look easy.""She often makes a special trip on the weekend."