answersLogoWhite

0

What is The Connection in three phase transformer?

Updated: 8/17/2019
User Avatar

Wiki User

14y ago

Best Answer

the connection here meant for the connection of windings in three core or limbs of a transformer. it might be delta or star connected.

User Avatar

Wiki User

14y ago
This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: What is The Connection in three phase transformer?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Related questions

Is there a neutral on a three phase transformer?

It depends on whether you are wye or delta connected. A transformer is a transformer, and a three phase transformer is simply three transformers. The key is in how you hook them up.AnswerIt depends on how the transformer is connected. If one set of windings is connected in star (or wye), then the star point is/canbe earthed and becomes the neutral for that particular connection; this is the standard connection for the secondary (low-voltage) of European distribution transformers. In North American three-phase distribution transformers, the secondary windings are connected in delta, and one phase is centre tapped, earthed, and that becomes the neutral point for a 240/120-V split-phase supply to a residence.This answer applies to both three-phase transformers, and to single-phase transformers which have been connected to form a three-phase transformer bank. (It is incorrect to say that a three-phase transformer is simply three single-phase transformers!)


Why is the Neutral fundamental in a three phase Y-Y Transformer connection?

Suppression of harmonics


What is the xo terminal on a transformer used for?

The XO denotes the joined secondary terminal connection of three single coils of a three phase transformer. It is the common return on any unbalanced current of a three phase system.


Why vector group is required?

There are various ways in which you can connect a three-phase transformer's primary and secondary windings, or in which you can connect three single-phase transformers to create a three-phase transformer bank. For example: wye-wye, wye-delta, delta-delta, delta-wye, etc.For each connection, there is a natural phase shift between the primary and secondary line voltages. This is called the angular displacement (or 'phase displacement') of the transformer connection.If you wish to parallel two three-phase transformers, or two three-phase transformer banks, then their angular displacements must be the same (there are also other requirements not relevant to this answer).A vector group is a method of specifying a three-phase transformer (or transformer bank) method of connection and its angular displacement. Transformer connections from the same group can be paralleled. Those in different groups cannot


What is the advantage of an open delta transformer?

An open-delta connection is a method of providing a three-phase supply, using two single-phase transformers. It is particularly useful if , say, one single-phase transformer, part of a three single-phase transformers forming a three-phase transformer bank, becomes damaged -allowing the two remaining transformers to provide a temporary three-phase supply to the load. The drawback with this connection is that the capacity of the transformer bank is reduced, and it can only provide a lower load current.


On a stup down transformer what does the xo symbol mean?

On a step down transformer XO symbol denotes the secondary split phase grounding point. This is also where the neutral of the three wire secondary is connected. The transformer connection is known as a single phase - three wire - with one secondary winding.


Why is star connection used in a three phase transformer?

The power of all three phases can be transmitted on three conductors.A star connection, as opposed to a delta, provides a grounding reference. Also, for ground faults on the secondary (assuming no delta third winding, or source third winding) will be a direct ratio similar to phase faults, instead of 57%. Another reason is to avoid the inherent phase shift involved in a delta/star configured transformer.Another AnswerA 'star-connected' secondary is the standard European connection for a three-phase distribution transformer, as it provides a line voltage of 400 V together with a phase voltage (i.e. line to neutral) of 230 V.


What is phase shift in three phase transformer?

The phase shift in three-phase transformer from winding of Transformer and determine by vectorgroup of transformer such as YNd1 High voltage connect to wye Low Voltage connect to delta so L.V. lag H.V 30 degree.Answer'Phase shift' or, more accurately, 'angular displacement', is the angle between the secondary line voltages and primary line voltages of a three-phase transformer.


Is home electricity 3 phase?

No, in North America most homes are wired to a single phase transformer. That transformer is connected to a three phase power grid. Some of the newer apartment buildings and condominium complexes have three phase systems in them. Their voltages are 120/208 as compared to a homes single phase connection of 120/240 volts.AnswerSome European countries, such as here in Cyprus, have three-phase residential supplies as standard for some reason -can't quite figure out why it should be necessary, though!


What is the current of 1MVA transformer?

This depends on the voltage, and whether it is a three phase or single phase transformer.


What is this system called with three single phase transformer?

Your question is rather vague. If you are asking what do you call a group of single-phase transformers, connected to supply three phase, then the answer is a 'three-phase transformer bank'.


Would you install three-phase transformer or bank of three single phase transformer in a large power station and justify by comparing the two schemes?

A three-phase transformer bank is often used in power stations because it is easier to construct and transport very large single-phase transformers, compared with constructing and transforming an equivalent-capacity three-phase transformer.