You really should be asking what is 'line' and neutral.
In Europe, the secondary winding of a distribution transformer has a pair of terminals. One is connected to earth and, therefore, has a potential of approximately 0 V with respect to earth. This terminal is termed the neutral, and the conductor connected to this terminal is called the neutral conductor. The other terminal is termed the line, and the conductor connected to this terminal is called the line (not 'phase'!) conductor. A distribution transformer's line conductor has a nominal potential of 230 V with respect to the neutral.
In North America, distribution Transformers' secondary windings have three terminals. The centre terminal is grounded, and provides the neutral. Each of the outer terminals acts as a line terminal. The nominal potential difference between each of these two line terminals is 240 V, while the nominal potential between either line terminal and the neutral terminal is 120 V.
In the United States, neutrals are white or gray. Phases can be anything else except green. General practice in my experience is black/red/blue/white for 120/208v 3 phase and brown/orange/yellow/gray for 277/480v(and higher) 3 phase.
Additional AnswerYour question should read, 'What colours are used to identify a line and neutral conductor?', because phases aren't identified by colour.
In Europe, a single-phase line conductor is brown and the neutral is blue. For three-phase supplies, the line conductors are brown, black, and grey, and the neutral is blue. Protective (earth) conductors are green/yellow stripes.
The formula to use is, phase voltage /1.73 = phase to neutral (ground) voltage.CommentThere is no such thing as a 'phase to phase', or 'phase to neutral' voltage. The correct terms are 'line to line' and 'line to neutral'. So the above answer should read: line voltage/1.73= line to neutral voltage = phase voltage.
A phase leg connects to the neutral through the connected load.
As far as I understand, you don't need neutral line for connecting appliances that is 3-phase compilant. You only need the neutral line to connect a single phase appliance, which you connect along with one of the three lines.
Only one neutral conductor is typically in a 3 phase panel.
If the heater is rated as a 3 phase 480 volt heater then a neutral is not needed. If the voltage stated is 277 volts three phase then a neutral is needed.
The formula to use is, phase voltage /1.73 = phase to neutral (ground) voltage.CommentThere is no such thing as a 'phase to phase', or 'phase to neutral' voltage. The correct terms are 'line to line' and 'line to neutral'. So the above answer should read: line voltage/1.73= line to neutral voltage = phase voltage.
A three phase system will have 3 phase branch circuits and no neutral.
The current carried by the neutral of a three phase four wire system is the un balanced current. If the three phase system was completely balanced on all three phases there would be no need for a neutral, eg a three phase motor. This neutral current will be less that the phase current so a reduction in the neutral size is allowed.
If there is a voltage differential from phase to phase, and a conductance (inverse of resistance) between them, then current (amperes) flows. This is no different than phase to neutral, i.e. voltage across conductance generates current, (I = EC, or I = E/A) except that neutral current is zero in a true phase to phase connection.Note that phase angle is always relative. In phase to neutral, it is relative to (typically) neutral; while in phase to phase, it is relative to the other phase. By Fourier Analysis, the difference between two phases of the same frequency, but of different phase angles, is still a sine (or cosine) wave. Also, by Kirchoff's Current Law, (implied, and I will (sort of) not repeat it here), current entering from one phase and equally leaving via another phase will not reflect at all in the neutral conductor.The simple answer is that connecting phase to phase is a short circuit, just like connecting phase to neutral.CommentThere is no such thing as 'phase to phase' or 'phase to neutral'. The correct terms are 'line to line' and 'line to neutral'.
A phase leg connects to the neutral through the connected load.
As far as I understand, you don't need neutral line for connecting appliances that is 3-phase compilant. You only need the neutral line to connect a single phase appliance, which you connect along with one of the three lines.
Only one neutral conductor is typically in a 3 phase panel.
It is the same as phase to neutral. As the neutral is earthed at the electricity suppliers transformer.
A three phase delta system does not use a neutral in its operation.
If the heater is rated as a 3 phase 480 volt heater then a neutral is not needed. If the voltage stated is 277 volts three phase then a neutral is needed.
Neutral is a return path.
Floating neutral in 3 phase supply is undesirable as if the same thing occurs then there will be bad effect for all single phase equipment which we are using as phase to neutral voltage will exceed from its normal value and it will harm the equipments.