answersLogoWhite

0


Best Answer

A delta connection should cause a 30 degree phase shift. It is necessary to know the configuration to tell whether this is +30 or -30 degrees.

Also, if you invert the connection, you can end up with [-30 + 180] 150 or [30 + 180] 210 degree phase shifting.

I've seen one transformer that had a delta connection that was phase shifted 150 degrees, but this is definitely NOT the norm.

Comment

Since the current is determined by the load, the answer to this question is that it depends upon

a. the nature of the load (resistive, R-L, R-C, R-L-C), and

b. whether the load is balanced or unbalanced.

In other words, it depends....

User Avatar

Wiki User

13y ago
This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: What is phase angle between line and phase currents in delta?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Continue Learning about Engineering

What is phase shift in three phase transformer?

The phase shift in three-phase transformer from winding of Transformer and determine by vectorgroup of transformer such as YNd1 High voltage connect to wye Low Voltage connect to delta so L.V. lag H.V 30 degree.Answer'Phase shift' or, more accurately, 'angular displacement', is the angle between the secondary line voltages and primary line voltages of a three-phase transformer.


What is phase angle error of current transformer?

The angle between the expected and actual secondary current is known as phase error.


What are the effects to the transformer insulation of single phasing on a three phase Delta-Wye connection?

The effect of the insulation is to stop electric currents flowing where they should not.


What is the phase angle difference between inductive load and resistive load?

The phase angle is defined as the angle by which the load current leads or lags the supply voltage.For a purely-resistive load, the phase angle is zero, because the load current is in phase with the supply voltage.For a purely-inductive load, the phase angle is 90 degrees lagging.But few loads are either purely-resistive or purely-inductive; typically, most loads are resistive-inductive. This means that, typically, the phase angle lies somewhere between zero and 90 degrees.


What is the kv phase to phase for 13.8kv?

There is no such thing as a 'phase-to-phase' voltage; the correct term is 'line-to-line' voltage. Whenever you mention a value of voltage for a three phase system, it is considered to be a line-to-line voltage unless it is stated clearly that this is phase voltage (line to neutral) voltage.(The reason that there is no such thing as a 'phase-to-phase' voltage is because phases exist between, or 'across', line conductors or between a line conductor and a neutral.) That is a world wide practice for electrical power engineers.

Related questions

Why line current is greater than phase current in delta connection?

Because if you apply Kirchhoff's Current Law to the junction between the line current and the two phase currents, the line current is the phasor (vector) sum of two phase currents. For a balanced load (only), this works out to 1.732 x phase current.


What is the return path in delta connection?

The return path in a delta connection is simply the other hot's. The three load windings are connected between AB, BC, and CA. In essence, each phase conductor is supplying power to two different phase windings. Assuming the winding currents are balanced, you can calculate the phase conductor currents by multiplying the winding currents by the square root of 3. (1.732) Its not that different from the return path for a single phase 240V appliance, such as a hot water heater, in a 120/240V split phase system. Neutral is not involved. The current flows from hot to hot.


How the phase angle of currents changes from primary winding to secondary winding in star delta transformer?

Measure the input and output voltages and currents with DMM (true RMS) and Amp-clamp, with reference to ground, nuetral, and to each other. The values plotted out graphically in the three phase triangle will indicate the phase shift.Another AnswerIt's normal to compare the secondary line voltageswith the primary line voltages, rather than currents, and we call any phase shift the 'angular displacement' of the transformer. For a star-delta transformation, the angular displacement is either +30 degrees or -30 degrees, depending on how they are wired.


What is phase shift in three phase transformer?

The phase shift in three-phase transformer from winding of Transformer and determine by vectorgroup of transformer such as YNd1 High voltage connect to wye Low Voltage connect to delta so L.V. lag H.V 30 degree.Answer'Phase shift' or, more accurately, 'angular displacement', is the angle between the secondary line voltages and primary line voltages of a three-phase transformer.


What is the difference between Load Current Line Current and Phase Current?

A load current is a current drawn by an electrical load. In other words, it is the current flowing from the source to the load.For a single-phase system, a line current is a current flowing through the line, or 'hot', conductor, while the current through the neutral conductor is called the neutral current.For a three-phase system, the three 'hot' conductors between the load and the source are called 'lines' and, so, the currents passing through them are called 'line currents'. For a three-phase system, loads are either connected between line conductors (delta-connected system) or between each line and the neutral (star- or wye-connected system), and represent the phases -so the currents passing through the loads are called 'phase currents'.For a balanced three-phase system, the line current is 1.732 times the value of a phase current, where the phases (loads) are connected in delta. For phases (loads) connected in star (or 'wye') the line current is numerically-equal to the phase currents.


What is the difference between phase angle and phase difference?

Although we use the term 'Phase angle' it's also an angle referred to another phasor (voltage or current).For example,conventionally when expressing power factor, we use 'voltage' as the reference. So the 'phase angle' of a particular phasor is the phase difference between our reference (voltage) & the phasor.As the gist, both mean the same except that 'phase angle' is the direction of the phasor w.r.t. positive x direction (reference)..AnswerBy definition, phase angle is the angle by which a load current leads or lags a supply voltage.Phase difference is the angle between any two electical quantities -for example, the angle two phase voltages of a three-phase system.


What is difference between line current and phase current?

A phase current is the current passing through a phase, whereas a line current is the current flowing through a line.In the case of a balanced delta-connected load, IL = 1.732 IP. In the case of a balanced star-connected load, IL = IP.For unbalanced loads, these relationships don't hold true, and must be individually calculated.


What is phase angle error of current transformer?

The angle between the expected and actual secondary current is known as phase error.


What is the phase angle between voltage and current in a purely resistive circuit?

The phase angle between voltage and current in a purely resistive circuit is zero. Voltage and current are in phase with each other.


What are the effects to the transformer insulation of single phasing on a three phase Delta-Wye connection?

The effect of the insulation is to stop electric currents flowing where they should not.


Angle between three phases?

The generated angle between phases in a three phase system is 120 degrees.


What is the phase angle difference between inductive load and resistive load?

The phase angle is defined as the angle by which the load current leads or lags the supply voltage.For a purely-resistive load, the phase angle is zero, because the load current is in phase with the supply voltage.For a purely-inductive load, the phase angle is 90 degrees lagging.But few loads are either purely-resistive or purely-inductive; typically, most loads are resistive-inductive. This means that, typically, the phase angle lies somewhere between zero and 90 degrees.