Best Answer

48" from floor to the middle of the pull station

User Avatar

Wiki User

11y ago
This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: What is the ADA height requirement of fire alarm pull stations placement in NJ?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Related questions

What is ADA height requirement for fire alarm pull Stations in Texas?

To the best of my knowledge, ADA says to follow NFPA 72 standards. NFPA 72 Standards state that the operable part of the pull station shall be between 3-1/3 ft and 4-1/2 ft.


What is the requirement of fire alarm pull stations placement in Washington dc?

You must follow NFPA 72:Chapter 17 Initiating Devices17.14 Manually Actuated Alarm-Initiating Devices.17.14.1 Manual fire alarm boxes shall be used only for fire alarm initiating purposes.17.14.1.1* Unless installed in an environment that precludes the use of red paint or red plastic, manual fire alarm boxes shall be red in color.17.14.1.2 Manual pull stations for initiating other than fire alarm shall be permitted if the devices are differentiated from the manual fire alarm boxes by a color other than red and labeling.17.14.1.3 Manual fire alarm boxes shall be mounted on a background of contrasting color.17.14.2 Combination manual fire alarm boxes and guard's signaling stations shall be permitted.17.14.3 Each manual fire alarm box shall be securely mounted.17.14.4 The operable part of each manual fire alarm box shall be not less than 42 in. (1.07 m) and not more than 48 in. (1.22 m) above floor level.17.14.5 Manual fire alarm boxes shall be installed so that they are conspicuous, unobstructed, and accessible.17.14.6 Manual fire alarm boxes shall be located within 60 in. (1.52 m) of the exit doorway opening at each exit on each floor.17.14.7 Manual fire alarm boxes shall be mounted on both sides of grouped openings over 40 ft (12.2 m) in width, and within 60 in. (1.52 m) of each side of the opening.17.14.8* Additional manual fire alarm boxes shall be provided so that the travel distance to the nearest fire alarm box will not be in excess of 200 ft (61.0 m), measured horizontally on the same floor.


What height to install a fire alarm strobe light?

140cm.from floor line


What is the height of the fire alarm Knox box?

There is no standard height but they are generally mounted at eye-level or above, to deter juvenile vandalism.


What was the first alarm clock How did it work?

The first alarm clock was powered by water where if the water was at a certain height, it would go off with a beeping sound.


What are the benefits of docking stations?

Most docking stations will not only charge the iPod but will allow you to play music through the speakers in the docking station as well.Most docking stations will have other neat features as well such as using the music on the ipod for an alarm or give you a remote to control the ipod from the couch.


Is installing a carbon monoxide alarm a do-it-yourself project?

Yes, carbon monoxide alarms can be easily installed without the use of professional assistance. One can be purchased online or from local hardware stores. The packaging will include instructions regarding the placement of the alarm within the home.


Are manual fire alarm pull stations required?

Check with your local building department of your city or county. They will be able to tell you exactly what is required in your community.


Are giraffes like alarm systems for other animals?

The height of a Giraffe's head makes them ideal lookouts for approaching predators.


What is inefficacy in public liability insurance?

Cover against a product to perform it's intended function or task. A critical requirement for alarm/CCTV installers etc


What is the proper height to mount a fire pull station?

The correct answer will depend on your local codes and ordinances, which may reference national fire or life-safety standards, which reference national fire alarm standards. NFPA 72, the National Fire Alarm and Signalling Code, requires the operating switch of manual pull stations to be located between 42 and 48 inches from the floor. NFPA 72: 17.14.4 (2010). Where I live, we are subject to ADA (Americans with Disabilites Act), and it requires manual pull stations (and other things containing an operable control, like light switches) to be mounted at 48 inches. The operating handle height must not exceed 48", so the electrical box is usually mounted 48" to the center of the box. Your municipality may have other specific rules, so check with your AHJ (Authority Having Jurisdiction) to be sure.


How does one protect their home from burglary?

The best way to protect a home from burglary is to have an alarm system. This should deter most potential burglars and an alarm can even be linked to police stations to offer extra protection. Good secure locks and gates are also advisable to prevent burglars from entering ones building.