The voltage range should be marked on the case but without that information a 5% increase can be assumed, so 504 v.
if check voltage is 2000v then acceptable range is 400
Only one neutral conductor is typically in a 3 phase panel.
208 v. equipment is a little smaller and cheaper, and 208v. is slightly safer to use. However, 480v. runs on half the amperage 208v. equipment does, which means equipment or devices cost almost 50% less to operate. With respect to energy consumption, the answer above is incorrect. It is true that equipment that operates at 480v does operate at roughly half the amperage vs. 208v, however, it operates at over twice the voltage. Your local power company charges you per kilowatt hour (voltage x amperage), not on amperage alone. Example, a 208v motor that draws 10 amps would consume (208v x 10a) 2.080 kilowatts per hour. The same motor on 480v would draw roughly half, 4.3 amps (480v x 4.3a) and would also consume 2.080 kilowatts per hour. So in terms of power consumption, they are virtually the same. The main reasons one would opt for higher is the fact that you can install smaller wire and you can run longer distances. It's a ratio that is directly proportional (at least with electric motors/inductive loads). If you were comparing a 240v motor to a 480v motor the ratio would be exact, if a 480v motor draws 5 amps, the same motor on 240v would draw 10 amps.
1kw=1.25kvaby this relation 75kva=60kwp=1.732*380*I*1I=60000/1.732*380*1I=91AmpsCommentPower factor is irrelevant to this question. You don't need to convert the kV.A rating to kilowatts, simply divide 75 000 V.A by (1.732 x 380). The answer is 114 A.This, of course, assumes that the question refers to a three-phase generator and that 380 V is the line voltage.
Divide the amount of turns in the secondary into 32 V and you'll get 8. Now multiply 8 times 60 turns and you'll get 480V.
if check voltage is 2000v then acceptable range is 400
When people talk about 480V systems, they mean 480 is the RMS voltage.
480V.
Line voltage equals phase voltage multiplied by the square root of three. a.k.a. E l = E p X 1.73 In a 3 phase 480v system the phase voltage is 277v. Therefore E l = 277 X 1.73 = 480v
in low voltage connection in wye (star conncetion) 415v high voltage connection in delta 480v
NEC recommends a maximum 3% drop for branch circuits. 5 volts is well within this range. So, yes 5v drop is normally fine, unless the motor manufacturer has a more stringent requirement.
100 amps to a 3 phase load. Power = 100A x Voltage x 1.73 ((line to line voltage)(1.73=SQRT(3)). 173 amps to each of 3 single phase (line to line) loads. Power = 173A x Voltage (line to line voltage). or... 100 amps to each of 3 single phase (line to neutral) load. Power = 300A x Voltage (line to neutral voltage). Example: - 3 phase, 480v, 100amp to a 3 phase heater. 100A x 480V x 1.73 = 83040 watts. - 3 single phase 480v (L-L voltage) heaters, 100amp. 173A x 480V = 83040 watts. - 3 single phase 277v (L-N voltage) heaters, 100amp. 300A x 277V = 83100 watts.
480v for the small motors,1340v mediums. 3160v for the pretty big ones..and a few others in between
Mathematically, just divide 480 by the square root of three. Electrically, 480V refers to the line-to-line value of a three phase system. For example, measure the voltage across A-phase and B-phase and you'll get 480V. 277V is the line-to-neutral value. Measure the voltage across A-phase and the neutral conductor and you should get 277V.
Only one neutral conductor is typically in a 3 phase panel.
It is an extremely expensive way of utilizing the deep fat fryer. You should look into changing the heating coils in the fryer to utilize the new voltage. That said it can be done.
208 v. equipment is a little smaller and cheaper, and 208v. is slightly safer to use. However, 480v. runs on half the amperage 208v. equipment does, which means equipment or devices cost almost 50% less to operate. With respect to energy consumption, the answer above is incorrect. It is true that equipment that operates at 480v does operate at roughly half the amperage vs. 208v, however, it operates at over twice the voltage. Your local power company charges you per kilowatt hour (voltage x amperage), not on amperage alone. Example, a 208v motor that draws 10 amps would consume (208v x 10a) 2.080 kilowatts per hour. The same motor on 480v would draw roughly half, 4.3 amps (480v x 4.3a) and would also consume 2.080 kilowatts per hour. So in terms of power consumption, they are virtually the same. The main reasons one would opt for higher is the fact that you can install smaller wire and you can run longer distances. It's a ratio that is directly proportional (at least with electric motors/inductive loads). If you were comparing a 240v motor to a 480v motor the ratio would be exact, if a 480v motor draws 5 amps, the same motor on 240v would draw 10 amps.