answersLogoWhite

0


Best Answer

A reverse current relay senses Power in (uses both voltage and current, and looks at the phase angle between these), and operates if power is flowing in the reverse direction, and the current is above a set point. An overcurrent relay looks at only current, and operates if it is above a set point regardless of power flow direction. Reverse current relays are often referred to as reverse power relays.

User Avatar

Wiki User

12y ago
This answer is:
User Avatar
More answers
User Avatar

Wiki User

11y ago

it is the short circuit condition.it is provided by using circuit breakers and relays.

Answer

An overcurrent is either an overload current or a short-circuit current. Overload currents occur when the load draws more current than the circuit is designed to handle on a continuous basis. Short-circuits occur when the line and neutral or the line and earth (ground) conductors make accidental contact. Overcurrent protection is provided by using either a fuse or a circuit breaker.

This answer is:
User Avatar

User Avatar

Wiki User

9y ago

A circuit can be protected from current overload with the help of circuit breakers. A high load can be carried by them without excessive heating.

This answer is:
User Avatar

User Avatar

Wiki User

13y ago

A breaker or fuse with an appropriate current and voltage rating.

This answer is:
User Avatar

User Avatar

Wiki User

12y ago

Fuse and open circuit

Ps u guys r losers

This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: What is the difference between reverse current and overcurrent protection?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Continue Learning about Engineering

What are electrical fuses?

Safety devices used in electrical circuits.AnswerA fuse is an overcurrent protection device, and will operate in the event of a sustained overload current or a short-circuit current.


Difference between overcurrent relay and fuse?

Current is flow of electricity charge. Voltage is a measure of potential energy or charge. Fuse. Is a device that opens when the current rating is exceeded this stopping the flow of current.


Differetiate between solid earthing and ELCB?

ELCB is the connection to the direct earth path using protective device.while solid earthing is without protective device.A form of ELCB should be installed when direct earth path of low enough impendance can not be obtained.


Why Normal time-overcurrent relays are not adequate for generator backup protection?

Setting the time-overcurrent relays high enough to prevent tripping for normal overloads may result in them not tripping at all due to the decaying characteristic of the generator fault current. Using the system voltage to control the overcurrent characteristic resolves this problem, since the voltage should drop very little for overloads, but will collapse to a small value for external faults. The 51V protection function uses the system voltage to adapt the operation of a time overcurrent element, using either voltage-restraint (51VR) or voltage-control (51VC).


What is the difference between over current and overload condition?

The term, 'overcurrent', describes either an 'overload current' or a 'short-circuit current'.An 'overload current' is a current that is higher than a circuit's 'rated current'. For example, if you have too many loads plugged into the same circuit, then the resulting current is an 'overload current'.A 'short-circuit current' is a large current resulting when a line ('hot') conductor accidentally makes contact with either a neutral conductor or an earth (ground) conductor.

Related questions

What is the difference between overload and overcurrent?

Overcurrent protection is protection against excessive currents or current beyond the acceptable current rating of equipment. It generally operates instantly. Short circuit is a type of overcurrent. Overload protection is a protection against a running overcurrent that would cause overheating of the protected equipment. Hence, an overload is also type of overcurrent. Overload protection typically operates on an inverse time curve where the tripping time becomes less as the current increases.


Do you choose a breaker for wire or equipment protection?

Overcurrent current protection is for the wires


What does OPD mean in electric terms?

'Overcurrent protection devices' are used to protect conductors from excessive current flow... a fuse


What is over current protaction?

'Overcurrent protection' is a means of protecting a cable and its load from damage due to an overcurrent. An 'overcurrent' is defined as either an 'overload current' (due to an excessive load) or a 'short-circuit current'. In its simplest form, overcurrent protection is provided by means of a fuse, but it can also be provided by means of a circuit breaker. In the case of high-voltage systems, the circuit breaker is tripped by the operation of one or more overcurrent protection relays which monitor the circuit using current transformers.


What is the difference between voltage restrained overcurrent protection and voltage controlled overcurrent protection?

The voltage-restrained overcurrent relay adjusts the pickup setting and characteristic curve of the overcurrent function based on the system voltage. The relay is set pickup greater than overload, and sensitivity increases as the voltage drops. The voltage-controlled overcurrent relay uses an undervoltage element to supervise the operation of the overcurrent element. When the voltage drops below a predetermined level, the undervoltage element permits the operation of the time overcurrent units. Voltage-restrained overcurrent relays can provide faster backup protection than voltagecontrolled overcurrent relays, particularly in cases where the generator voltage does not drop significantly below rated voltage during fault conditions. If the generator voltage always drops below a given voltage level for all faults in which operation is required, the voltage-controlled overcurrent unit may be set to provide faster overall clearing speed


Can a numerical relay give protevtion to over current over voltage and short circuit current at the same time?

Yes. Most microprocessor based relays that have both voltage and current inputs can provide overcurrent and over voltage protection simultaneously. Short circuit current is the same as overcurrent.


A fuse has low melting point why?

This is necessary because a fuse is a protection against an overcurrent; excessive current produce melting.


What is meant by residual overcurren?

Residual overcurrent protection is often provided in modern microprocessor based relays that have three phase inputs, and no neutral input. Sometimes this is provided even if a neutral input is present. It is similar to neutral overcurrent, where the neutral current is directly measured through the neutral input of the relay. for residual overcurrent, the three phase currents are vectorially summed together to form the residual overcurrent. This relay measured 3I0 current, or ground current.


What are electrical fuses?

Safety devices used in electrical circuits.AnswerA fuse is an overcurrent protection device, and will operate in the event of a sustained overload current or a short-circuit current.


What are the functions of an electrical circuit beaker?

A: Its function is to trip if the current across it coil is its tripping pointAnswerA circuit breaker is an overcurrent protection device which can break a fault current.


Difference between overcurrent relay and fuse?

Current is flow of electricity charge. Voltage is a measure of potential energy or charge. Fuse. Is a device that opens when the current rating is exceeded this stopping the flow of current.


What is Over Current fault?

In electricity supply, overcurrent or excess current is a situation where a larger than intended electric current exists through a conductor, leading to excessive generation of heat, and the risk of fire or damage to equipment. Possible causes for overcurrent include short circuits, excessive load, and incorrect design. Fuses, circuit breakers, temperature sensors and current limiters are commonly used protection mechanisms to control the risks of overcurrent.