Best Answer

If the load is balanced across all three phases, and the power factor is 1.0, the line current would be about 76 amps at full load. For a more typical power factor of 0.85, the current would be closer to 89 amps.

User Avatar

Wiki User

15y ago
This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: What is the line current of a 3 phase 63kw 277 480 vac trasformer?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Continue Learning about Engineering

In delta connection what is formula for phase current?

Line current = 1.732 x Phase CurrentCommentOnly for balanced loads.


How do you calculate 3 phase kWh from measuring the total phase current current?

In a balanced 3-phase system, if the three loads are star connected, the line current is equal to the load current. If the loads are delta connected, the line current is less than the load current by a factor of 1/sqrt(3).


What is neutral negetive sequence current?

Negative sequence current is defined as 3I2 = (phase 1)*(1angle 0) + (phase 2)*(1angle 240) + (phase 3)*(1angle 120) Negative sequence current is seen in three phase power systems due to natural system imbalance. Also during unbalanced fault conditions such as line to line, Line to ground, and line to line to ground faults. It is not seen in purely balanced three phase faults.


What is a line to line voltage?

In a 3 phase system, the voltage measured between any two phase is called line to line voltage.And the voltage measured between line to neutral is called phase to neutral (line to neutral) voltage.AnswerThere is no such thing as a 'phase-to-phase' or a 'phase-to-neutral' voltage. The correct terms are 'line-to-line' and 'line-to-neutral'.The voltage between any two line conductors is called a line voltage.In a three-phase, three-wire, system, the line voltage is numerically equal to the phase voltage.In a three-phase, four-wire, system, the voltage between any line conductor and the neutral conductor is called a phase voltage. The line voltage is 1.732 times larger than the phase voltage.


How three phase line current convert in single phase?

The current is the same in the three live wires. The voltage can be described as the line voltage (phase to neutral) or the phase voltage (phase to phase) which is larger by a factor of sqrt(3). So a line voltage of 230 v corresponds to a phase voltage of 400 v.

Related questions

What is phase current?

A phase current is the current passing through a phase, whereas a line current is the current flowing through a line.


Why line current is greater than phase current in delta connection?

Because if you apply Kirchhoff's Current Law to the junction between the line current and the two phase currents, the line current is the phasor (vector) sum of two phase currents. For a balanced load (only), this works out to 1.732 x phase current.


How do you convert line current to phase current?

The current is the same in the three live wires. The voltage can be described as the line voltage (phase to neutral) or the phase voltage (phase to phase) which is larger by a factor of sqrt(3). So a line voltage of 230 v corresponds to a phase voltage of 400 v.


In delta connection what is formula for phase current?

Line current = 1.732 x Phase CurrentCommentOnly for balanced loads.


Write dowen the relationshipbetween line and phase the 3phase system if voltageline and currentline are line value voltage power and current power are phase value?

A-for star connectionE(line)=1.73E(Phase)I(line)=I(Phase)&B-for delta connectionE(line)=E(Phase)I(line)=1.73I(Phase)


What is difference between line current and phase current?

A phase current is the current passing through a phase, whereas a line current is the current flowing through a line.In the case of a balanced delta-connected load, IL = 1.732 IP. In the case of a balanced star-connected load, IL = IP.For unbalanced loads, these relationships don't hold true, and must be individually calculated.


What is the connection of normal wire star or delta?

normally delta connection wired in 3 phase induction motor. during starting wiring is in Star and after running normal speed changeover to delta .beacause starting time its phase voltage equals less root3 times of line voltage ,line current and phase current equals. in Delta phase voltage and line voltage equals, and phase current equals root3 times line current


What is the difference between Load Current Line Current and Phase Current?

A load current is a current drawn by an electrical load. In other words, it is the current flowing from the source to the load.For a single-phase system, a line current is a current flowing through the line, or 'hot', conductor, while the current through the neutral conductor is called the neutral current.For a three-phase system, the three 'hot' conductors between the load and the source are called 'lines' and, so, the currents passing through them are called 'line currents'. For a three-phase system, loads are either connected between line conductors (delta-connected system) or between each line and the neutral (star- or wye-connected system), and represent the phases -so the currents passing through the loads are called 'phase currents'.For a balanced three-phase system, the line current is 1.732 times the value of a phase current, where the phases (loads) are connected in delta. For phases (loads) connected in star (or 'wye') the line current is numerically-equal to the phase currents.


How do you calculate 3 phase kWh from measuring the total phase current current?

In a balanced 3-phase system, if the three loads are star connected, the line current is equal to the load current. If the loads are delta connected, the line current is less than the load current by a factor of 1/sqrt(3).


What is neutral negetive sequence current?

Negative sequence current is defined as 3I2 = (phase 1)*(1angle 0) + (phase 2)*(1angle 240) + (phase 3)*(1angle 120) Negative sequence current is seen in three phase power systems due to natural system imbalance. Also during unbalanced fault conditions such as line to line, Line to ground, and line to line to ground faults. It is not seen in purely balanced three phase faults.


What is a line to line voltage?

In a 3 phase system, the voltage measured between any two phase is called line to line voltage.And the voltage measured between line to neutral is called phase to neutral (line to neutral) voltage.AnswerThere is no such thing as a 'phase-to-phase' or a 'phase-to-neutral' voltage. The correct terms are 'line-to-line' and 'line-to-neutral'.The voltage between any two line conductors is called a line voltage.In a three-phase, three-wire, system, the line voltage is numerically equal to the phase voltage.In a three-phase, four-wire, system, the voltage between any line conductor and the neutral conductor is called a phase voltage. The line voltage is 1.732 times larger than the phase voltage.


What happens when phase to phase line is connected?

If there is a voltage differential from phase to phase, and a conductance (inverse of resistance) between them, then current (amperes) flows. This is no different than phase to neutral, i.e. voltage across conductance generates current, (I = EC, or I = E/A) except that neutral current is zero in a true phase to phase connection.Note that phase angle is always relative. In phase to neutral, it is relative to (typically) neutral; while in phase to phase, it is relative to the other phase. By Fourier Analysis, the difference between two phases of the same frequency, but of different phase angles, is still a sine (or cosine) wave. Also, by Kirchoff's Current Law, (implied, and I will (sort of) not repeat it here), current entering from one phase and equally leaving via another phase will not reflect at all in the neutral conductor.The simple answer is that connecting phase to phase is a short circuit, just like connecting phase to neutral.CommentThere is no such thing as 'phase to phase' or 'phase to neutral'. The correct terms are 'line to line' and 'line to neutral'.