answersLogoWhite

0


Best Answer

#6 3 conducter

User Avatar

Wiki User

12y ago
This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: What size wire to feed a panel with 50A breaker for hot tub and 20A branch circuit?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Related questions

I have a Transformer 480 primary 208 secondary feeding 1 200amp mb 42 space panel I need to feed a subpanel 6 ft away I'm thinkin feed through lug at top of bus or at feed through MB suggestions?

The sub-panel need to be fed from the main panel, by way of a circuit breaker connected to one of the breaker locations. Or if your sub-panel has a main breaker installed you can feed from the main panel with a sub-feed lug kit. This looks like a breaker, but is only a point where you can branch off the sub panel.


Will manually turning off a shunt trip breaker set off the fire alarm?

Manually turning off a shunt trip breaker should not set off the fire alarm. The only way that the breaker could set off the fire alarm when turned to the off position is if there is an auxiliary contact on the breaker connected to the fire alarm circuit. This is not usually done because the breaker should be able to be turned off when doing maintenance on the breakers circuit. If the breaker is a mandatory feed breaker to a piece of fire alarm equipment and shouldn't be left in the off position it might have a trouble circuit connected to the fire alarm panel. A trouble alarm on a fire alarm panel is different from an alarm circuit alarm.


What are breakers?

A breaker is a device that is used to connect and disconnect the buss bars of an electrical panel to the feed end of wires that feed an electrical load. The function of a breaker is to protect the wires from an overload by the use of an internal thermal trip, and to protect the load and wires from a short circuit by use of an internal magnetic trip.


Which terminal on a 15 amp household breaker does the hot wire feed into and which one does it come out?

On a 15 amp household breaker there is no terminal on the in feed of the breaker. The breaker either plugs into the distribution panel's bus bar or it bolts to the distribution's bus bars. The feed conductor connects to the load side of the breaker at its terminal lug.


What is different between feeder breaker and motor breaker?

You have to be careful with terms in the electrical field, Example: Main Feeder Circuits will feed a Transformer for distribution and each of those main circuits might feed numbeous Motor control centers. However each of those circuits could be called a main feeder for the motor control center. Confusing. We have High Voltage Transmittion tansformered down for Distribution. So normally a Feeder Breaker will feed Main circuits that will be used for distribution. Example Your home panel will have a main feeder circuit to the whole panel and distribution breakers to you home.


Where would a 100 amp breaker be used?

In a residential application it would most likely be used as the breaker for the entire main electric panel or a subpanel feed.


What size in amperage circuit breaker should be used for a pool pump?

The sizing of the circuit breaker and hence the wire size to feed the pump are all dependant upon the amperage of the pump. This question can not be answered without that information.


Can you use a 2 pole 60 amp breaker to feed one circuit?

No, you cannot use one in place of the other.


How do you read breaker box amps?

The main breaker will have marking indicating size of electrical service, or if it is a fuse system....the fuses will have current ratings. If it is a subpanel, it might not have a main breaker. In this case you would have to look in the panel that the feed is coming from and find the size of the breaker that is feeding it. In either case you must look for the manufacturer's label that will have the maximum current the panel can handle, make sure the breaker feeding the panel doesn't exceed this rating.


Can you feed a 208v 200amp panel from 480v 20amp circuit?

Not directly, you would need to transform 480v circuit to 120v with a transformer first.


Where is main breaker switch?

a circuit breaker trips on overload,if this breaker has tripped many times it may be worn out,if there is a overload happening the breaker is doing it s job keeping you safe.Main breaker needs to be replaced when your meter has been pulled(removed from metersocket)Have a electrician look at it and verify problem, you should not attempt to change out yourself it will be live.......


Why would power go off and on in 3 rooms and no circuit breaker tripped?

You have a loose connection somewhere. May be at the service panel itself. Check the circuit feeding those rooms at the breaker and check the neutral wire connection. If they are good these rooms may be feed out of a junction box which should be accessible if it was wired to code. Find that junction box and check all the connections. These are sometimes very hard to find.