to inreases or decreases n. of turns of a transformer
AnswerAn 'off-load' tap changer is a tap-changing mechanism that can only be used when the transformer is disconnected, as opposed to an 'on-load' tap-changing mechanism that can operate when the transformer is energised and on load.
Tap changing is performed to slightly change the turns ratio of a transformer in order to keep the secondary voltage within the statutory limits (e.g. in the UK, 230 V +10% -6%) should there be a substantial change in load.
A tap changer is used to vary the turns ration between the windings of a transformer to make minor changes to the secondary voltage. An on-load tap changer enables the turns ratio to be altered without disconnecting the transformer. An off-load tap changer requires the transformer to be temporarily diconnected. On-load tap changers are installed on the high-voltage side of the transformer, where the current is lower.
Tap changer is a device that is used to change the secondary voltage on transformers. It is normally on the HV winding of the transformer. Off load tap changer is designed to change the taps only when the transformer is not charged, while on load tap changer is capable of changing the tap on load too.
depending on the amount of the load of transformer as well as the power factor of it, there is a transformer specific voltage drop at its terminals, due to the internal impedances. The on-load tap changer can / will be used to compensate this voltage drop or rise.
OCTC means off circuit tap changer (off load tap changer) and OLTC means on load tap changer. in octc we can change the tap position while the transformer is in off condition only. we can not change the tap position of octc in charged condtion of the transformer. the tap position of octc can be change in deenrgise condion of transformer only means if you nwant to chang the tap position firstly you will have to deenrgise the power transformer then you can change the tap position of octc.while in oltc we can change the tap position of OLTC in charged condition of power transformer. This is the basic diffirence between OCTC and OLTC.generally the OCTC used in single phase generating transformer (G.T.Power Transformer) and OLTC used in three phase powwer transformers like standby transformer and auto transformer in power plants and switch yards. for any other question please mail me at (ashu_uit2007@yahoo.co.in )
The ratio of a shell type transformer does not change based on load, unless a load tap changer is used. The primary windings to secondary winding ratio is a constant. The voltage on the secondary may be dragged down if loading is heavy, specifically if the transformer has poor voltage regulation. If this is the case, you can infer the voltage on the secondary may float higher than desired under no load conditions.
Tap changers are used to change transformer winding ratios by a specified amount (+/- 10%, for example). This allows more voltage control of one side with respect to the other. For a distribution transformer, as load increases, the voltage will sag. If it sags too far, a tap changer will be required to raise the voltage to acceptable values.
An on-load tap changer (OLTC) is a device used in transformers to adjust the voltage output while the transformer is still energized, without interrupting the power supply. It enables the regulation of voltage levels to ensure stable electrical supply and efficient operation of the power system. OLTCs operate by changing the transformer’s turns ratio through a series of taps on the winding, allowing for real-time voltage adjustments based on load conditions. This helps maintain optimal voltage levels and improves the overall reliability of the electrical grid.
No because that transformer can only supply a ½ amp so it would seriously overheat if a 1-amp load was connected to it.
No load current is energizing current. This is effectively "lost" power, power used in the transformer to energize the core. It, therefore, should be small!
A tap changer is used on the high voltage (HV) side of a transformer to adjust the voltage ratio and maintain a desired voltage level under varying load conditions. It allows for voltage regulation and compensates for voltage fluctuations in the power system. By changing the number of turns in the transformer winding, the tap changer can increase or decrease the voltage output, ensuring a stable and reliable power supply.
If the line impedance is Z0 and the load is ZL then connect the load using a transformer with N turns ration. N=sqrt(Z0/ZL)
An On-Load Tap Changer (OLTC) is a device used in transformers to automatically adjust the voltage levels while the transformer is in operation. Its primary function is to regulate the output voltage to maintain it within desired limits despite variations in load or input voltage. By changing the transformer’s tap settings under load, the OLTC ensures efficient power distribution and enhances the stability of the power system. This capability helps to minimize voltage fluctuations and improve overall system reliability.