What is the difference between the dry or direct expansion type of evaporator to the Flooded type evaporator?

Evaporator is said to be flooded type if liquid refrigerant covers the entire heat transfer surface. This type of evaporator uses a float type of expansion valve. An evaporator is called dry type when a portion of the evaporator is used for superheating the refrigerant vapour after its evaporation.


What is a direct expansion evaporator?

Refrigerant enters a direct expansion evaporator as a saturated liquid vapor mix and leaves as a superheated vapor.


What is the expected temperature drop through a direct expansion evaporator coil is?

The expected temperature drop through a direct-expansion evaporator coil is 20°F. The evaporator coil became clogged during the adjustment period.


What are the advantages of flooded type cooler over direct expansion type cooler in chiller?

flooded type cooler is a cooler that is being flooded while direct expansion type is a type that is being directly expanded.


What is the full form of DX?

direct expansion system


What is a Direct-expansion coil air conditioner?

In a direct-expansion (DX) unitary system, the evaporator is in direct contact with the air stream, so the cooling coil of the airside loop is also the evaporator of the refrigeration loop. The term "direct" refers to the position of the evaporator with respect to the airside loop. The term "expansion" refers to the method used to introduce the refrigerant into the cooling coil. The liquid refrigerant passes through an expansion device (usually a valve) just before entering the cooling coil (the evaporator). This expansion device reduces the pressure and temperature of the refrigerant to the point where it is colder than the air passing through the coil. The components of the DX unitary system refrigeration loop (evaporator, compressor, condenser, expansion device and even some unit controls) may be packaged together, which provides for factory assembly and testing of all components, including the electrical wiring, the refrigerant piping, and the controls. This is called a Packaged DX system. Alternatively, the components of the refrigeration loop may be split apart, allowing for increased flexibility in the system design. This is called a Split DX system. Separating the elements has the advantage of providing the system design engineer with complete flexibility to match components in order to achieve the desired performance. One of the most common reasons for selecting a DX system, especially a packaged DX system, is that, in a smaller building, it frequently has a lower installed cost than a chilled-water system because it requires less field labor and has fewer materials to install. Packaged DX systems that use air-cooled condensers can be located on the roof of a building, in a small equipment room, or even within the perimeter wall of the building. Additionally, if the tenants are paying the utility bills, multiple packaged DX units may make it easier to track energy use, as only the specific unit serving that tenant would be used to meet the individual cooling or heating requirements.


What helped bring a end to the cattle drives?

The expansion of railways was the direct cause of this.


Which of these factors had a direct influence on the spread of post classical empires?

Expansion of transcontinental trade routes


What factors had a direct influence on the spread of post-classical empires?

Expansion of transcontinental trade routes


When do policemen step in to direct traffic?

Several incidences include the failure of a street signal, bush fires ahead, road flooded accident or in case of a wreck .


Is there a difference between evaporator coils and cooling coils in air conditioner unit?

usually both the same thing just different names. Most hydronic (water) systems are referred to as cooling coil and heating coil. Direct refrigerant system is an evaporator coil. Also depends on who your talking to.


Why you undertake such a project?

Response to competition Response to customers Expansion Direct profit