Current is always flowing in the phase due to the continuous voltage application.
the current in phase can be used when it is given a - ve terminal or earth the current would complete the circuit.
A phase current is the current passing through a phase, whereas a line current is the current flowing through a line.
4/4+4*4=20 is it correct by any means or not ? No this garbage has got nothing to do with negative phase sequence current in 3 phase electrical systems.
Yes. It is identical to the line current.
any more load will add to that phase ,over current protection will trip the generator.
How do you zero phase current transformer test
As with any IDMT relay the higher the fault current the quicker the trip time.
Because if you apply Kirchhoff's Current Law to the junction between the line current and the two phase currents, the line current is the phasor (vector) sum of two phase currents. For a balanced load (only), this works out to 1.732 x phase current.
For proper working of any 3 phase induction motor it must be connected to a 3 phase alternating current (ac) power supply of rated voltage ...
The current is the same in the three live wires. The voltage can be described as the line voltage (phase to neutral) or the phase voltage (phase to phase) which is larger by a factor of sqrt(3). So a line voltage of 230 v corresponds to a phase voltage of 400 v.
Add them upAnswerThere is no 'total' current in a three-phase system. The current flowing in each line (not 'phase') is considered separately. And you most definitely don't 'add them up'!
Balanced Star (Wye) Connected Systems:Line Voltage = 1.732 x Phase VoltageLine Current = Phase CurrentBalanced Delta Connected Systems:Line Voltage = Phase VoltageLine Current = 1.732 x Phase Current
In a three-phase generator, the currents in the three phases are 120 degrees out of phase with each other. This phase displacement means that when one phase current is at its peak positive value, the other two are at lower values, thereby balancing the overall current. As a result, the sum of the currents in a balanced system is zero at any instant, which minimizes the overall neutral current and reduces losses in the system. This cancellation allows for efficient power distribution and minimizes the need for additional neutral conductors.