answersLogoWhite

0


Best Answer

Because inverters do not produce a pure sinewave AC and you did not use a True RMS digital meter to measure the voltage.

Meters that are not True RMS actually measure the average, then display the value on a scale that assumes the input is a pure sinewave showing what the RMS would be for that average. For waveforms significantly different from sinewaves (as the inverter produces) that displayed value can be seriously wrong.

User Avatar

Wiki User

9y ago
This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: Why ac voltage of inverter measures 95.1 volts?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Related questions

951 in Roman Numerals?

It is: 951 = CMLI


What is 1000000000 plus 951?

1000000000 + 951 = 1000000951


How do you write 951 in roman numerals?

951 = CMLI


Is 951 a prime number?

No, the number 951 is composite.


What is 9.51 as a percent?

951%9.51= 9.51 * 100%= 951%


What is 951 times 357?

951 multiplied by 357 is 339,507


All the letters of the roman numeral for 951?

951 = CMLI


How many times does 3go into 951?

951 divided by 3 is 317 so 3 goes into 951= 317 times


How do you work out the answer to 951 takeaway 672?

951 - 672 = 279951672----279


What is the fractional notation of 649 to 951?

It is 649/951 which cannot be simplified.


how many letters are there for the roman numeral for 951?

951 = CMLI or as DCCCCLI


What is the Roman numeral for 951?

CMLIThe Roman numeral for 951 is CMLI.