Want this question answered?
Protective devices - relays, CT,PT, isolators, circuit breakers are used for fault protection. Fault protection means If there is a fault in the circuit, the circuit must be cut off before any damage occurs due to fault.
An 'inter-turn' fault occurs when adjacent turns of the same winding are short circuited (due, for example, to insulation breakdown). This affects the turns ratio of the transformer. An 'inter-winding' fault occurs when there is a short circuit between adjacent windings (coils) due to insulation breakdown, and can lead to a catastrophic failure of the transformer.
Short circuit fault.
Lt cables has own impedance which reduce the short circuit fault level
A short circuit is a condition whereby a point or section of the circuit offer a short path for current to return to the power supply. It occurs when two or more points or sections of the circuit touches each others (but only and only if that results in drop in resistance to such an extent that it causes excessive current to flow through.
What is the question? Assuming you're talking about short circuiting the live circuit, as soon as a phase to ground fault occurs protection will operate, opening a circuit breaker.
For answering this question we have to consider the constant voltage drop model of the diode which says that if voltage across diode is less then its cut in voltage than assume diode to be open circuit and if it is greater then assume diode to be short circuit.Till the input voltage is less than the cut in voltage, diode is open circuit(thus no current through the circuit). Thus entire input voltage appears across the diode as output.When input voltage is greater than or equal to cut in voltage, then short circuit the diode. Thus, there will be no voltage drop across the diode as output.Thus cut in voltage decides when to consider the diode open circuit and when short circuit. It decides when the diode will have output when it will not.
Protective devices - relays, CT,PT, isolators, circuit breakers are used for fault protection. Fault protection means If there is a fault in the circuit, the circuit must be cut off before any damage occurs due to fault.
An 'inter-turn' fault occurs when adjacent turns of the same winding are short circuited (due, for example, to insulation breakdown). This affects the turns ratio of the transformer. An 'inter-winding' fault occurs when there is a short circuit between adjacent windings (coils) due to insulation breakdown, and can lead to a catastrophic failure of the transformer.
If the word unconnected was changed to uninsulated then this type of scenario would be known as a short circuit.
Short circuit fault.
Short circuit occurs when positive and negative terminals are connected directly.
1. That if a short circuit occurs we will get a sign before short circuit will happen or not ? 2. what we can do ? 3. how fuse can get a short circuit ? 4. which wires we have to use from preventing short circuit ?
short circuit occurs when two wire which consist of one live and neutral wire are in contact with the main and the other end of the wire are touched each other short circuit occurs
Lt cables has own impedance which reduce the short circuit fault level
A short circuit is a condition whereby a point or section of the circuit offer a short path for current to return to the power supply. It occurs when two or more points or sections of the circuit touches each others (but only and only if that results in drop in resistance to such an extent that it causes excessive current to flow through.
A short circuit occurs when the hot side of the supply comes in contact with ground.