In Short circuit test High Voltage side is feeded with 2-5% of the High Voltage rating to circulate approximately full load current in low voltage winding by short circuiting it. Low voltage is generally short circuited to facilitate measurements because it is more difficult to measure the quantities at high voltages.
A high current flows through a short circuit even if there is no voltage change because the resistance across the short circuit is zero.
1)Short circuit test is performed at rated current. As the rated current on high voltage side is much less than low voltage side, so the rated high voltage side current is easily achieved compared to low voltage side. 2)Also because we cannot short circuit high voltage side, as, if we short circuit high voltage side, voltage of high voltage side essentially falls to zero and since VI=constant, so the high voltage side current will be very high and will burn the winding.
Since a short circuit is, essentially, a zero impedance connection between nodes, the current in a short circuit is limited only by the ability of the source. In the case of an ideal voltage source connected to an ideal short circuit, you would have infinite amperes.
Through a relay or some other kind of high voltage switching device.
In this case current flows from a high voltage to a lower voltage in a circuit.
A high current flows through a short circuit even if there is no voltage change because the resistance across the short circuit is zero.
Most likely a short circuit will cause no voltage. Due to the high current on a short circuit fault the over current protection of the circuit will trip. This will cut the voltage supply off completely.
1)Short circuit test is performed at rated current. As the rated current on high voltage side is much less than low voltage side, so the rated high voltage side current is easily achieved compared to low voltage side. 2)Also because we cannot short circuit high voltage side, as, if we short circuit high voltage side, voltage of high voltage side essentially falls to zero and since VI=constant, so the high voltage side current will be very high and will burn the winding.
in the short circuit test we applied supply voltage on L.V side and short circuit the H.V side and connect the ammeter in H.V circuit to measure the short circuit current. with the help of s.c test we measure the copper losses in the transformers.
This is describes the condition at the location a short-circuit fault.
Since a short circuit is, essentially, a zero impedance connection between nodes, the current in a short circuit is limited only by the ability of the source. In the case of an ideal voltage source connected to an ideal short circuit, you would have infinite amperes.
The circuit voltage is too high. Could be a failed sensor, wiring short, or PCM problem.
I assume "tension" in this question should be replaced with "voltage". Short circuit tests are often performed from the lower voltage side of the transformer, since a lower voltage source is then required to perform the test. Often times the test lab may not have a source that can output a high enough voltage to perform from the high voltage winding.
A bulb gets fused when short circuit occurs or high voltage passes
Map sensor circuit voltage highMap sensor circuit voltage high
An open-circuit test is done with the transformer running at its rated voltage but with no load. This measures the power lost in the magnetic core. (IR Losses) A short-circuit test is done with the transformer running at its full rated current in all windings but at a low voltage. The secondary is shorted and the primary voltage is adjusted to give the rated current. This measures the power lost in the copper windings. (Copper losses)
The supply is given on the high voltage side of transformer because the supply voltage required to circulate rated current through the transformer is usually very small So energy is saved.