An open-circuit test is done with the transformer running at its rated voltage but with no load. This measures the power lost in the magnetic core. (IR Losses)
A short-circuit test is done with the transformer running at its full rated current in all windings but at a low voltage. The secondary is shorted and the primary voltage is adjusted to give the rated current. This measures the power lost in the copper windings. (Copper losses)
to prevent overload/overheat. this test is similar to a high-pot test to look for defects in wire insulation and undesirable conducting paths
Short circuit test gives copper loss and open circuit gives iron losses in a transformer
Short circuit test and open circuit test are widely used to test the efficiency of the transformer.
For open circuit test of transformer, the secondary is open circuit and the circuit impedance is largely inductive due to the core impedance having high L as compared to R. hence the power factor is reduced, thus , we use low power factor wattmeters.
Since this is an open circuit test, there is no load attached, thus all losses must be internal to the transformer.
A secondary current of 0 would suggest to me that the secondary circuit is open. A normally operating circuit with zero current flow would be very unusual. No load in secondary circuit. No secondary current can also be attributed to the primary power source open or an open primary winding.
A voltage transformer takes a primary voltage and steps it down to a smaller secondary voltage. This type of transformer will attempt to keep the secondary voltage at a specific ratio of the primary voltage. If you short it, massive current flow in the secondary is required to do this. For a similar reason a CT should never be open circuited - because it attempts to push a specific ratio of primary current through the secondary. If you open circuit the secondary, it takes a massive voltage on the secondary to accomplish this.
Short circuit test and open circuit test are widely used to test the efficiency of the transformer.
The open/short-circuit test on a transformer isn't 'needed'. It's only used if you want to find out the efficiency of a transformer.
The transformer can be tested on open and short circuit to find the iron losses and copper losses separately, which uses a fraction of the power than having to run the transformer on full-load.
Open circuit and short circuit tests are performed to determine transformer characteristics. In the case of a single phase transformer, SC tests would be performed to determine the impedance. The open circuit test will give excitation information (% excitation at specific voltages, often 90%, 100% and 110%, and no load losses).
transformer is busted; if input voltage is normal you have short circuit or open circuit somewhere
The resistance of the winding in the primary of a transformer constitutes a load. As long as there is resistance then there is no short circuit. A short circuit is considered no resistance which develops an instantaneous high current. That is why fuses and breakers are inserted into the circuit to open the high current flow under a short circuit condition.
A no-load test is done with the normal supply connected in the way the transformer is intended to be used. It is also known as an open-circuit test to distinguish it from a short-circuit test, and its purpose is to measure the power loss in the iron core of the transformer and the no-load current drawn from the supply.
A short-circuit test is done to determine the power lost in the resistance of the primary and secondary windings of the transformer. It is done at full load current but with only enough voltage to give the required current with the secondary short circuited. An open-circuit test is done at full load voltage but no current is taken from the secondary, and this enables the power lost in the magnetic core of the transformer to be measured. As well a power, the tests also allow the inductances to be measured as well as the resistances, in order ot characterise the transformer fully.
Short circuit voltage is the voltage that has to be applied to the primaries of a transformer, so that the nominal current flows through the secondaries, when they are shorted. This value is important, if transformer secondaries shall be used in parallel. Ideally all transformers with parallel secondaries should have the same short circuit voltage. When their short circuit voltages are different, the transformer with the lower short circuit voltage will be loaded more than their relationship of power ratings would predict. The short circuit voltage is also important in the design of a transformer, because it predicts, how much the secondary voltage will drop at nominal output current. This knowledge helps the designer to find out, how many further windings the secondary needs for a certain voltage in relation to an ideal transformer. Short circuit voltage is also known as impedance voltage.
Because of fire
To calculate the no load current from transformer & core loss is also calculated.
An open circuit or a short-circuit (if that circuit is complete).