answersLogoWhite

0


Best Answer

Generally accuracy at low current values isn't important for protective functions. The burden is taken into account when looking at the saturation curve and available short circuit current to insure the CT doesn't saturate during fault conditions.

User Avatar

Wiki User

12y ago
This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: Why is burden not used in protection ct?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Continue Learning about Engineering

Is it ok to have the dot on a current transformer upside down?

You are probably referring to a 'polarity mark'. This is very important if the CT's burden requires current to flow through it in a particular direction in order to work properly. For example, it won't make any difference if the burden's an ammeter. But if the burden is, say, a wattmeter, then it's very important to observe the CT's polarity mark when it is wired, otherwise the wattmeter might read 'downscale' (backwards). It's also very important when the CT supplies protection relays.


Why secondary windings of current transformers are shorted?

Current transformers (CTs) -together with voltage (or potential) transformers- are 'instrument transformers'. CTs are used to enable large currents flowing in high-voltage systems to be measured, while electrically-isolating the ammeter (termed a 'burden') from the h.v. system. They are also used to monitor h.v. currents for high-voltage protection systems. Before disconnecting its burden, the secondary of a CT must be short-circuited, and remain short-circuited until after the burden has been replaced. This is because a dangerously-high voltage will appear across the open terminals of any energised CT.


How do you calculate burden resistor fo current transformer?

The method I have seen employed is to estimate the maximum current that will flow in the secondary side of the CT due to fault currents on the primary side, and calculate the total load (resistance) on the secondary side, including the CT resistance, cable resistance (2 way for ground faults, 1 way for three phase and L-L), resistance of any meters/relays connected to the CT. Once this is known, the voltage rise in the CT can be determined to see if the CT is likely to saturate.Alternately, you can determine the VA burden by the above, VA = V*I = (I*R)*I, using Ohm's law.The above answers the question of how to calculate the VA burdon on a current transformer. The VA burden of a CT is determined by the resistivity of the CT, multiplied by the current squared through the secondary. In general, this will be provided by the manufacturer in the form of a CT burden characteristic, developed through testing of the CT in question, not through calculations.


What is mean by burden of the current transformers?

The burden on a CT is the sum total impedance connected to the secondary - including the CT secondary winding coil resistance, lead resistance, and any loads attached (relays, meters, etc.).If this is for power calculations and CT saturation in three phase systems, remember you must multiply the lead resistance by two to get the total path resistance.Another AnswerWe use the word, 'burden', to describe the load supplied by the instrument transformer's secondary. This is normally a measuring instrument or protection relay. We use the word 'burden' to distinguish it from the 'load' supplied by the circuit to which the primary winding is connected.


Is CT use high or low voltage and if it depends on application or not?

A current transformer (CT) is used to reduce a load current to a value that can be read by conventional instruments such as ammeters and wattmeters; it also enables the instruments to be located remotely. In the case of high-voltage circuits, a CT also electrically-isolates its burden (secondary load) from the primary circuit.

Related questions

Where is 5P20 CT used and where is Class PS CT used?

5P20 CT give more accuracy than PS class CT. 5P20 cant be used in unit protection. Class PS CT is a protection class ct. It is used for differtial proction,distance (UNIT)proction.


What is CT burden in electrical engineering?

CT (current transformer) Burden is the maximum load that the CT secondary can drive (e.g. meters or protection relays) Why do you care about burden when ordering current transformers? The burden is the termination impedance of the measuring instrument. The measuring instrument can be an analog or digital energy meter, a data logger or a recorder. All instruments that use a current transformer to measure line current must terminate the CT with a resistance (impedance in same case which means there is some inductance involved). A CT supplier should be given the burden when ordering. Technically, the total burden for a CT is the internal winding resistance, the connecting lead resistance and the measuring instrument input resistance. Some Ct's are installed a long distance from the measuring instrument and the connecting leads can have a resistance as much as 0.002 ohms per foot (both ways because the current makes a complete round trip). This resistance will cause an error if not taken into account.


Is it ok to have the dot on a current transformer upside down?

You are probably referring to a 'polarity mark'. This is very important if the CT's burden requires current to flow through it in a particular direction in order to work properly. For example, it won't make any difference if the burden's an ammeter. But if the burden is, say, a wattmeter, then it's very important to observe the CT's polarity mark when it is wired, otherwise the wattmeter might read 'downscale' (backwards). It's also very important when the CT supplies protection relays.


What is a ct of burden?

This is not understandable. Please rephrase and resubmit. Be specific


Why secondary windings of current transformers are shorted?

Current transformers (CTs) -together with voltage (or potential) transformers- are 'instrument transformers'. CTs are used to enable large currents flowing in high-voltage systems to be measured, while electrically-isolating the ammeter (termed a 'burden') from the h.v. system. They are also used to monitor h.v. currents for high-voltage protection systems. Before disconnecting its burden, the secondary of a CT must be short-circuited, and remain short-circuited until after the burden has been replaced. This is because a dangerously-high voltage will appear across the open terminals of any energised CT.


What is the ISO protection class for Windsor Locks CT 06096?

What is the ISO protection class for Windsor Locks CT


Can a CT drive more than 1 ammeter?

Yes, as long as the burden of these ammeters does not exceed the VA rating of the CT.


Class px ct?

Class PX is the definition in IEC 60044-1 for the quasi-transient CT formerly covered by Class X of BS-3938, commonly used with unit protection schemes. These are Protection CTs used for Earth fault protection. Knee point voltage is an important parameter for these type of CTs. Shaikh


Will REF protect the outgoing cables when the Ct's are fitted at the transformer?

REF protection, when installed and set correctly, will protect everything within the CT's. If the CTs are on breakers, then yes, the cables from the transformer to the breakers will be in the zone of protection. If the CTs used are in the bushings of the transformer, then no.


How do you calculate burden resistor fo current transformer?

The method I have seen employed is to estimate the maximum current that will flow in the secondary side of the CT due to fault currents on the primary side, and calculate the total load (resistance) on the secondary side, including the CT resistance, cable resistance (2 way for ground faults, 1 way for three phase and L-L), resistance of any meters/relays connected to the CT. Once this is known, the voltage rise in the CT can be determined to see if the CT is likely to saturate.Alternately, you can determine the VA burden by the above, VA = V*I = (I*R)*I, using Ohm's law.The above answers the question of how to calculate the VA burdon on a current transformer. The VA burden of a CT is determined by the resistivity of the CT, multiplied by the current squared through the secondary. In general, this will be provided by the manufacturer in the form of a CT burden characteristic, developed through testing of the CT in question, not through calculations.


What is mean by burden of the current transformers?

The burden on a CT is the sum total impedance connected to the secondary - including the CT secondary winding coil resistance, lead resistance, and any loads attached (relays, meters, etc.).If this is for power calculations and CT saturation in three phase systems, remember you must multiply the lead resistance by two to get the total path resistance.Another AnswerWe use the word, 'burden', to describe the load supplied by the instrument transformer's secondary. This is normally a measuring instrument or protection relay. We use the word 'burden' to distinguish it from the 'load' supplied by the circuit to which the primary winding is connected.


Is CT use high or low voltage and if it depends on application or not?

A current transformer (CT) is used to reduce a load current to a value that can be read by conventional instruments such as ammeters and wattmeters; it also enables the instruments to be located remotely. In the case of high-voltage circuits, a CT also electrically-isolates its burden (secondary load) from the primary circuit.