because its much safer to switch the hot wire then the neutral wire because if you are working on a light fixture for example and the switch is off if you ground yourself out to the neutral you become the load or return. a neutral shock can me more dangerous at times
One. A typical "two way" ON-OFF light switch is a Single Pole Single Throw (SPST) switch with two terminals. It is wired in series with the fixture: that is, the power circuit is routed from the breaker to one side of the switch. The other side of the switch is connected to the "phase" or "power" terminal of the fixture. In a 115VAC single phase circuit, the other terminal of the fixture is connected to neutral. A "three way" switch circuit consists of two switches in different locations, each of which is a Single Pole Double Throw (SPDT) switch with three terminals. A typical use would have one switch at the top and the other at the bottom of a set of stairs. For the sake of clarity, we can label the "common" terminal on a SPDT switch the "C" terminal. This terminal is internally connected to one of the other two terminals, call them "A" and "B", depending of the position of the switch. A three way switch is connected with the circuit breaker connected to the "C" terminal on either switch. Conductors connect the "A" terminal on one switch the the "A" terminal on the other switch and the "B" terminal on one switch the the "B" terminal on the other switch. The remaining "C" terminal is connected to the "phase" or "power" terminal of the fixture. The other terminal of the fixture is connected to neutral. Note that, in either case, there is no neutral wire connected to the switch. Ground conductors do connect to the chassis of the switch box and the fixture, but they do not carry current and do not affect the operation of the circuit.
First of all, the correct term is 'line' and not'phase' wire. The reason a switch is always placed in the line conductor, rather than in the neutral conductor, is that its function is not simply to break the circuit, but also to ensure that the circuit's load is disconnected from the line potential. If the switch were to be placed in the neutral conductor, it would still break the circuit, but the load will still be at line potential and present a shock hazard to anyone attempting to work on the load (e.g. to remove a lamp from its holder).
It depends on whether you are wye or delta connected. A transformer is a transformer, and a three phase transformer is simply three transformers. The key is in how you hook them up.AnswerIt depends on how the transformer is connected. If one set of windings is connected in star (or wye), then the star point is/canbe earthed and becomes the neutral for that particular connection; this is the standard connection for the secondary (low-voltage) of European distribution transformers. In North American three-phase distribution transformers, the secondary windings are connected in delta, and one phase is centre tapped, earthed, and that becomes the neutral point for a 240/120-V split-phase supply to a residence.This answer applies to both three-phase transformers, and to single-phase transformers which have been connected to form a three-phase transformer bank. (It is incorrect to say that a three-phase transformer is simply three single-phase transformers!)
The reading on the 3-ph meter would equal the sum of the three separate readings on the single-phase meters. The neutral sides of the single phase meters do not need to be connected to the neutral wire as long as they are connected together.
In a three phase system, connected wye, neutral is the common return, and it is grounded. In a delta connection, there is no neutral.
IF Neutral is connected to the Switch then Live still exists on the socket even if the Switch is OFF.In such a situation a person can get a shock as Live can form a circuit thru the body to Ground.
A phase leg connects to the neutral through the connected load.
As far as I understand, you don't need neutral line for connecting appliances that is 3-phase compilant. You only need the neutral line to connect a single phase appliance, which you connect along with one of the three lines.
A delta-connected system is described as being a three-phase, three-wire, system, and doesn't have a neutral. But a balanced star (wye) connected load (e.g. a three-phase induction motor) doesn't actually require a neutral.
TPN stands for Triple Pole With a neutral link.normally this are the switches which are used in case of three phase connections and as main switch......gonecase17@gmail.com
Switches are used to isolate the supply voltage from the connected load. This isolation is needed to be able to work on equipment in the de-energized state. Without the switch in the circuit this could not be accomplished.
Earthing point is where conductor is directly connected to ground and its potential is always zero. Neutral is a return path in single phase system and in three phase system Neutral point will have zero potential if all the loads are balanced in the system. In un balanced three phase system even neutral point will have some potential
TPN Load break switch: Is basically a main switch used in three phase system and know as Three pole neutral or Three phase neutral having four connectors for three phases and one neutral.
There is no neutral in a delta connection, because that is the definition of delta, a power configuration where current flows from phase hot to phase hot. The loads are A-B, B-C, and C-A. Contrast this with star, where there is a neutral, and the loads are A-N, B-N, and C-N.
One. A typical "two way" ON-OFF light switch is a Single Pole Single Throw (SPST) switch with two terminals. It is wired in series with the fixture: that is, the power circuit is routed from the breaker to one side of the switch. The other side of the switch is connected to the "phase" or "power" terminal of the fixture. In a 115VAC single phase circuit, the other terminal of the fixture is connected to neutral. A "three way" switch circuit consists of two switches in different locations, each of which is a Single Pole Double Throw (SPDT) switch with three terminals. A typical use would have one switch at the top and the other at the bottom of a set of stairs. For the sake of clarity, we can label the "common" terminal on a SPDT switch the "C" terminal. This terminal is internally connected to one of the other two terminals, call them "A" and "B", depending of the position of the switch. A three way switch is connected with the circuit breaker connected to the "C" terminal on either switch. Conductors connect the "A" terminal on one switch the the "A" terminal on the other switch and the "B" terminal on one switch the the "B" terminal on the other switch. The remaining "C" terminal is connected to the "phase" or "power" terminal of the fixture. The other terminal of the fixture is connected to neutral. Note that, in either case, there is no neutral wire connected to the switch. Ground conductors do connect to the chassis of the switch box and the fixture, but they do not carry current and do not affect the operation of the circuit.
With three windings, you have six terminals. Call them A1, A2, B1, B2, C1, and C2, representing phase A, B, and C. In the delta configuration, A1 is connected to C2, C1 is connected to B2, and B1 is connected to A2. Power is from phase to phase - A1C2, C1B2, and B1A2. In the wye configuration, A2, B2, and C2 are connected together, and are usually connected to neutral. Power is from phase to neutral - A1, B1, and C1.
If there is a voltage differential from phase to phase, and a conductance (inverse of resistance) between them, then current (amperes) flows. This is no different than phase to neutral, i.e. voltage across conductance generates current, (I = EC, or I = E/A) except that neutral current is zero in a true phase to phase connection.Note that phase angle is always relative. In phase to neutral, it is relative to (typically) neutral; while in phase to phase, it is relative to the other phase. By Fourier Analysis, the difference between two phases of the same frequency, but of different phase angles, is still a sine (or cosine) wave. Also, by Kirchoff's Current Law, (implied, and I will (sort of) not repeat it here), current entering from one phase and equally leaving via another phase will not reflect at all in the neutral conductor.The simple answer is that connecting phase to phase is a short circuit, just like connecting phase to neutral.CommentThere is no such thing as 'phase to phase' or 'phase to neutral'. The correct terms are 'line to line' and 'line to neutral'.