answersLogoWhite

0


Best Answer

three phases

User Avatar

Wiki User

11y ago
This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: Why the capacitive voltage transformer and voltage transformer both are used in a substation?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Related questions

What is the main different between the power transformer and voltage transformer?

Voltage Tarnsformer transforms only voltage. While power transformer transforms both voltage and current.


What is difference between substation and transformer?

AnswerIt is a large encased group of metal plates about the size of a small house with 2 sets of insulated copper wires wrapped around the plates -an input and output - to convert a very high supply line voltage - maybe 44 thousand volts to a lower voltage of 2200 volts that runs down the power line poles in your neighborhood. Look at your street's power poles and you will see a mini substation that converts he 2200 volt to 220 volts and may supply several homes. Actually a substation transformer for a distribution substation will reduce the incoming voltage from 115,000 volts or 69,000 volts to a lower voltage closer to 7200 volts that runs down the power poles in your neighborhood. At your house there will be a small transformer that reduces the voltage from 7200 volts to 240 volts to meet the needs in your home.Actually both are wrong !!


How do you establish no of turns in both high voltage and low voltage windings of a 3 phase transformer?

Through the use of the basic transformer voltage equation.


What do electric substations do?

Electric substations either step up voltage or step down voltage for electric power distribution. For example, power being generated at a power plant would be stepped up in voltage for transmission over the electric grid. On the other hand, power coming into a residential neighborhood from the electric grid would be stepped down in voltage for distribution to individual homes. This increasing or decreasing of voltage will be accomplished by using transformers in the substation. There will also be electric circuit breakers in the substation located on both the high and low voltage sides of the transformer. These circuit breakers are used to be able to isolate the transformer from the electric grid for maintenance purposes or in case of an electrical fault that could damage the transformer. Most substations will also contain a Control House that contains all of the control equipment for the substation as well as battery backups in case of loss of power. Type your answer here...


What difference's between potential transformer and voltage transformer?

Both are same. This is an instrument transformer used for metering & protections.


How can you tell if a transformer is a set up or set down?

The same transformer can be both. It must be operated at the correct voltage on both windings.


What is the amp rating of 100va transformer?

The amp rating for a 100VA transformer will vary depending on the actual voltage of the transformer. Transformers have both a primary and a secondary voltage.


What are three requirement for connecting the transformer in paralle?

Transformer capacity (kvA) shall be identical, Both transformer impedance, secondary voltage and frequency shall be identical.


How do you discharge a flyback transformer?

you touch both of it's high voltage outputs together.


Does a transformer boost electric energy?

The transformer doesn't "boost" energy. If the voltage on the output side is higher than the voltage on the input side, then the current is lower. The power (energy every second) on either side is the product of (voltage) times (current), and that product is the same on both sides of the transformer.


What happens to the current as the voltage is increased by the step up transformer?

Compare a transformer to a balancing act. Both side need to remain equal.The primary side of the transformer is the supply side and the load is connected to the secondary side of the transformer.The load governs the current of the secondary side of the transformer and the voltage of the secondary side must match the voltage that the load required to operate.The ratio of the transformer will determine what the voltage of the secondary side is as compared to the voltage that has to be applied to the primary.The current of a step up transformer will be higher on the primary side that that of the secondary.Apply voltage and current to this concept and you will see that the transformer will remain balanced.The size of the transformer is always calculated from the secondary side of the transformer and the value is written in VA or KVA where V = voltage and A = amperage. Power factor is also taken into consideration when calculating the size of the transformer to be used.


Why at resonance the voltage drop across inductance and the voltage drop across capacitance is greater than the source voltage?

This isn't necessarily the case. It depends upon the value of resistance (which, at resonance, determines the current), and the values of the inductive- and capacitive-reactance.At resonance, the impedance of the circuit is equal to its resistance. This is because the vector sum of resistance, inductive reactance, and capacitive reactance, is equal the the resistance. This happens because, at resonance, the inductive- and capacitive-reactance are equal but opposite. Although they still actually exist, individually.If the resistance is low in comparison to the inductive and capacitive reactance, then the large current will cause a large voltage drop across the inductive reactance and a large voltage drop across the capacitive reactance. Because these two voltage drops are equal, but act the opposite sense to each other, the net reactive voltage drop is zero.So, at (series) resonance:a. the circuit's impedance is its resistance (Z = R)b. the current is maximumc. the voltage drop across the resistive component is equal to the supply voltaged. the voltage drop across the inductive-reactance component is the product of the supply current and the inductive reactancee. the voltage drop across the capacitive-reactance component is the product of the supply current and the capacitive reactancef. the voltage drop across both inductive- and capacitive-reactance is zero.