Because a short-circuit test is done at very low voltage to check the transformer windings on their maximum current. The low voltage ensures that the magnetic flux in the transformer's iron core is very low so that the eddy-current losses, usually known as iron losses, are negligible.
A short circuit test is performed with a low voltage applied to the primary winding. A low voltage results in low iron losses.
The transformer can be tested on open and short circuit to find the iron losses and copper losses separately, which uses a fraction of the power than having to run the transformer on full-load.
1)Short circuit test is performed at rated current. As the rated current on high voltage side is much less than low voltage side, so the rated high voltage side current is easily achieved compared to low voltage side. 2)Also because we cannot short circuit high voltage side, as, if we short circuit high voltage side, voltage of high voltage side essentially falls to zero and since VI=constant, so the high voltage side current will be very high and will burn the winding.
in short circuit test we apply rated current with the LV side shorted.so the applied voltage will be very low. iron loss depends on the applied voltage.so it is neglected
There is no power loss in open circuit test. Actually there is iron loss also known as magnetic losses. These include hysteresis and eddy-current losses. This can be described as V1^2/Rc Where V1 is the primary voltage and Rc is the resistance of the magnetic core.
A Linear power transformer coil? use an Ohm meter and check the resistance of the coils. No resistance is an open circuit. Also check for a cross circuit from one side of the transformer to the other.
The transformer can be tested on open and short circuit to find the iron losses and copper losses separately, which uses a fraction of the power than having to run the transformer on full-load.
In a short-circuit test the normal load current is passed through the transformer with minimal voltage applied. This means that the magnetic flux density in the core is also minimal, so that the only losses are the resistive losses of the transformer windings.
An open-circuit test is done with the transformer running at its rated voltage but with no load. This measures the power lost in the magnetic core. (IR Losses) A short-circuit test is done with the transformer running at its full rated current in all windings but at a low voltage. The secondary is shorted and the primary voltage is adjusted to give the rated current. This measures the power lost in the copper windings. (Copper losses)
1)Short circuit test is performed at rated current. As the rated current on high voltage side is much less than low voltage side, so the rated high voltage side current is easily achieved compared to low voltage side. 2)Also because we cannot short circuit high voltage side, as, if we short circuit high voltage side, voltage of high voltage side essentially falls to zero and since VI=constant, so the high voltage side current will be very high and will burn the winding.
in short circuit test we apply rated current with the LV side shorted.so the applied voltage will be very low. iron loss depends on the applied voltage.so it is neglected
An open-circuit test measures a transformer's iron losses. With no current flowing in the secondary windings, and only a tiny 'magnetising' current flowing in the primary windings, there is no significant energy lost due to the resistance of the winding conductors. So a wattmeter attached to the primary of the transformer will not read any 'copper losses', only the 'iron losses' that occur in the core.
Iron losses are termed as core losses. There are mainly two losses - Copper loss and iron loss. Iron loss is no load loss.
In case of open circuit test of transformers we measure iron losses and hence the power lost here is being measured by the wattmeter.
Open circuit test on a transformer is usually performed to measure the IRON losses.Iron losses are produced due to eddy current and hysteresis losses. In open circuit test, the LV side, generaly the secondary winding, is kept open and the HV side, generaly the primary winding is fed with the rated voltage and frequency. The rated voltage is applied in order to setup normal flux in the transformer, which in return further produces the normal iron losses at rated voltage. the wattmeter connected at the primary side will show the power consumed due to iron losses. this calculation further utilized for determing the efficiency of transformer.
In short circuit test very low voltage at primary approx 5 % of the rated voltage is given and secondary is short circuited by an ammeter. Due to low voltage very low flux is developed in core of the transformer and due to that iron losses are very low which can be neglected. By Rizwan: actually it is operated at (10-15)% of the rated voltage and as you know n case of low voltage low magnetic flux is produced and then there will be low magnetic field density(B). and we know hysteresis and eddy current losses depend on (B).as in case of : hysteresis depends on B^1.2 and eddy current depends on B^2 So if B is low then both losses(collectively called constant losses) will be very very low.
There is no power loss in open circuit test. Actually there is iron loss also known as magnetic losses. These include hysteresis and eddy-current losses. This can be described as V1^2/Rc Where V1 is the primary voltage and Rc is the resistance of the magnetic core.
A Linear power transformer coil? use an Ohm meter and check the resistance of the coils. No resistance is an open circuit. Also check for a cross circuit from one side of the transformer to the other.