No, the generator is too small.
Yes, a generator will operate a freezer.
The difference b/w the prime generator & standby generator is that the prime generator is used for 24/7/365, while the standby generators are only used in emergency cases, if we used standby generators for more than 24 hours continuously, then it will be overheated for sure.
There is 746 watts per HP. So a 350 hp motor with a power factor of roughly 0.8 would require 261,000 W 261KW generator or 326 KVA.
A typical tea urn would take 2-3 kW and the kVA would be the same.
Yes, an 8kVA generator can run a small house. A generator this size should be able to adequately power a one ton air conditioner, 18 cubic foot refrigerator, and other small appliances normally found in a small house.
The electrical code book states that a single phase 3 HP motor at 230 volts draws 17 amps. This equates to 3910 watts. Allowing for starting inrush current a 5000 watt generator will run the motor but the generator will labor a bit until the motor gets up to speed. Generators with a higher wattage rating would have less trouble with the starting of the 3 horse power motor. <<>> One hp is 746 watts. 3*746=2238. It takes 3 to 6 times as much energy to start as it does to run.
What KVA generator is needed to run 1 ton split?Read more:What_KVA_generator_is_needed_to_run_1_ton_split
How much KVA generator is required to run two AC of 1.5 tone
10 AC
To answer this question the voltage of the motor is needed.
A 15 KVA - Generator operating at 380 Volts can cater to only 22.79 Amps. It cannot cater to a 60 Amps breaker
To answer this question a voltage must be stated.
3 kva genrator myt be required to run 1.5ton ac.
1HP = 746 watts 15 HP = 11190 watts = 11.19 kW You would need a generator of at least 13kW. UPS Distributor for 15 Years.
Radioisotope thermoelectric generator
The difference b/w the prime generator & standby generator is that the prime generator is used for 24/7/365, while the standby generators are only used in emergency cases, if we used standby generators for more than 24 hours continuously, then it will be overheated for sure.
You can use a software like anti deep freeze and i give you the link run it and it is no virus or trojan :---- http://rapidshare.com/files/257825181/Anti_Deep_Freeze_v0.1.zip
There is 746 watts per HP. So a 350 hp motor with a power factor of roughly 0.8 would require 261,000 W 261KW generator or 326 KVA.