1HP = 746 watts
15 HP = 11190 watts = 11.19 kW
You would need a generator of at least 13kW.
UPS Distributor for 15 Years.
What KVA generator is needed to run 1 ton split?Read more:What_KVA_generator_is_needed_to_run_1_ton_split
10 AC
Are you planning to build a perpetual motion machine in which the power generated by an AC generator is used to run an AC motor which is used to run the same AC generator which provides it with power? Because that won't work. Yes, you can use a motor to generate electricity, and you can use electricity to run a motor, but the process is not 100% efficient and if you try to make it a closed loop, it will run down fairly quickly. So, what do we actually do? We use fuel to run an AC generator, or we use waterfalls or wind, or some other energy source, and then we use the power to run our motor.
A simple Rotary phase converter is just a motor generator set. An electric motor running on the input voltage/current/phase/frequency. it drives a generator that supplies a different voltage/current/phase/frequency. So an electric motor and an electric generator connected together mechanically, either on the same shaft, or via gears, constitutes a Rotary phase converter. the above is incorrect, the motor/generator is the same motor, just one 3 phase motor is needed, it will run on T1 and T2, and put out L1, L2, and L3. You just need to know how to wire it up and what to do to get it to spin over on simple single phase 220, it will create three phase 220.
When the power factor is leading, the capacitive kVAr is more than the Inductive kVAr and this still has to be supplied by the source. As kVA is the vector sum of kW and kVAr, still for the given kW, you have to produce more kVA. Alternately, for the given kVA, you can only convert partially into useful work. Secondary effects are voltage boost in the system, availability of stored energy to feed the fault in case of a fault, increase in the asymmetrical component of fault current, increasing thus the peak value of the fault current, etc.
To answer this question the voltage of the motor is needed.
What KVA generator is needed to run 1 ton split?Read more:What_KVA_generator_is_needed_to_run_1_ton_split
How much KVA generator is required to run two AC of 1.5 tone
No, the generator is too small.
There is 746 watts per HP. So a 350 hp motor with a power factor of roughly 0.8 would require 261,000 W 261KW generator or 326 KVA.
You need a 5.5kw generator to run a 5.5kw motor.
all the electrical machines can be run either as a motor or as a generator. but dc machines, A motor can be run as generator and vice versa with little modification
10 AC
I think it can work with a certain type of generator and an electric motor like one that uses 300w/h The idea is to run a generator that can produce more electricity than needed to run the motor that is powering it.
The electrical code book states that a single phase 3 HP motor at 230 volts draws 17 amps. This equates to 3910 watts. Allowing for starting inrush current a 5000 watt generator will run the motor but the generator will labor a bit until the motor gets up to speed. Generators with a higher wattage rating would have less trouble with the starting of the 3 horse power motor. <<>> One hp is 746 watts. 3*746=2238. It takes 3 to 6 times as much energy to start as it does to run.
A 15 KVA - Generator operating at 380 Volts can cater to only 22.79 Amps. It cannot cater to a 60 Amps breaker
To answer this question a voltage must be stated.