answersLogoWhite

0

What else can I help you with?

Related Questions

How much kva is required to run a single phase 5hp motor using generator?

To answer this question the voltage of the motor is needed.


What kva is needed to run a 6 bed room house?

9 megawatts a year


What KVA generator is required to run two AC of 1.5 ton?

How much KVA generator is required to run two AC of 1.5 tone


What all is needed to make a carburated motor run?

Fuel, compression and spark.


How many KVA is required to run 5HP 3 phase motor?

Keeping in mind that there is 746watts per Hp should lead you to the answer. For ex. Power(in KVA) = Voltage (1.73)x CurrentTherefore, if you know the voltage, typically 480Vac, then 150(746) = 480 (1.73) x I150Hp(746w/hp) = Voltage x Current= about 135 amps current. Now you also need to factor in the Power Factor (PF) of the load (150Hp). The power factor depends on the type of load. A motor is mostly Inductive, a heater, or lighting bank is resistive, and capacitive loads aren't that common. Your question is a bit vague. If you'd like to rephrase your answer or send it directly to me, I'd be glad to assist you further. You might also want to check out a site called "Mike Holt's Code Forum'. If you're an EE student, I'm sure the path to your solution is in one of your 'Power' books.


How many kva to run a tea urn?

A typical tea urn would take 2-3 kW and the kVA would be the same.


How much load you can run on 62KVA Genset?

max.load that can run on 62 kva dg is of 86 amperes.


What kva generator to run 15Hp motor?

1HP = 746 watts 15 HP = 11190 watts = 11.19 kW You would need a generator of at least 13kW. UPS Distributor for 15 Years.


How many kva need to runs 6 conditioner 2 ton?

To determine the kVA needed to run six 2-ton air conditioners, first, calculate the total load. Each 2-ton AC unit typically consumes around 2.5 kW, so six units would require approximately 15 kW (2.5 kW x 6). To convert kW to kVA, divide by the power factor (usually around 0.8 for AC units), resulting in about 18.75 kVA (15 kW / 0.8). Therefore, you would need at least 19 kVA to safely run six 2-ton air conditioners.


What size generator is needed to run a 6HP compressor at 230V?

The electrical code book states that a single phase 3 HP motor at 230 volts draws 17 amps. This equates to 3910 watts. Allowing for starting inrush current a 5000 watt generator will run the motor but the generator will labor a bit until the motor gets up to speed. Generators with a higher wattage rating would have less trouble with the starting of the 3 horse power motor. <<>> One hp is 746 watts. 3*746=2238. It takes 3 to 6 times as much energy to start as it does to run.


Is a power supply needed to run an electric motor?

Yes. To make something move, you have to add energy. An electric motor won't turn by itself.


How much power of Gas Generator required to run 350 HP Motor Star Delta?

There is 746 watts per HP. So a 350 hp motor with a power factor of roughly 0.8 would require 261,000 W 261KW generator or 326 KVA.