Yes, as long as there is enough typical/backup/standby power for both.
Mimic panel in fire alarm system 'mimics' or mirrors the signal of the Main Fire Control Panel.
Only if your building is required to have an interconnected fire alarm system. Your local and state fire codes and building codes will determine what kind of alarm system is required, if any. Many single or two-family dwellings are allowed to have individual smoke alarms that are not connected to an alarm panel, but they only give local audible/visual alarm. An alarm panel allows the system to call automatically for help, when necessary. When you have one connected in a building it will supply power to the smoke detectors and the rest of the fire alarm system and may indicate where the fire has been detected. This information can be relayed to the dispatchers, allowing the fire officer/brigade to find the source of the alarm quickly and attend to the cause.
Mimic panel in fire alarm system 'mimics' or mirrors the signal of the Main Fire Control Panel.
To open a fire alarm, you typically need to break the glass or press a button on the alarm panel. This will activate the alarm and alert others of a fire emergency.
Are you referring to the circuit supplying power to the control panel or the initiation/notification branch circuits controlled by the fire alarm system? The ampacity of the fire alarm control panel would determine the circuit size of the branch circuit supplying power to the control panel and the terminal on the control panel and fire alarm device would detrmine the size of conductor that it will accept. Most fire alarm control panels would require a minimum 15 amp circuit. The minimum conductor size allowed per the NEC would be 14 AWG. 22 AWG. is the smallest conductor that most control panels and device terminals will accept. These are considered Power Limited circuits.
The power load of a fire alarm will depend upon how many components are connected. A single smoke alarm may be a very small load on the AC power. However, a more sophisticated alarm panel with multiple sensors and annunciators (horns, strobes) and fire-alarm release systems (panic hardware release, fire doors, extinguisher systems) may require a lot of power. As a general rule, any alarm and function required by the fire code is also required to have a backup power source, whether from a battery or a motor-generator set.
In general, any device powered by the fire alarm panel must be listed as compatible with it. There are probably few, if any gas shutoff valves so listed, so probably not. The normal arrangement for this function is to use auxiliary contacts, either on the panel itself or an intelligent control module to switch an external power supply. This connection should be wired "fail safe" meaning the valve would close if the external power failed. If you asked this question, you are probably not qualified to design fire alarm systems. This is a life safety system! Get a qualified engineer or NICET IV designer to make sure you have it right. There are numerous codes, standards, and local amendments that must be followed, as well as the manufacturer's guidelines.
Yes.
To effectively shut off a fire alarm, locate the alarm panel and enter the code or use a key to silence the alarm. If you cannot do this, contact the fire department for assistance.
First you locate the source of the alarm, undo the condition (e.g., valve closed, inadequate pressure, etc), then reset the alarm condition on the sprinkler control panel and reset the alarm on the fire alarm control panel (assuming they're connected, as required by many fire codes).
The function of a water flow switch is to detect water flow in the sprinkler system, usually during a fire event, to signal a local electrical fire alarm, or fire alarm panel to activate the alarm devices in the building,and send an alarm signal to a central station or alarm company to alert the fire department.
Fire alarm control panels are powered by the mains power. Commonly, the fire alarm will have a battery back up power in place so that the system still remains functional and powered up when the mains fails. When the mains is powering the panel, the batteries are charged fully so that when a power cut occurs, they have enough power to operate the system for a certain amount of time. Generally, in the UK, a panel is powered by 240 Volts and is stepped down by a transformer to 24 Volts. The panel will usually have two, 12 Volt batteries installed in the panel- they are reffered to as SLA's. (Sealed Lead Acid). These batteries though will only last for about a day or two. Some systems are larger and have more power drain, so they may be required to have additional backup batteries connected and perhaps spares available on site. If the fire alarm system is non-operational, the local fire authorities may require a company to post a 24-hour "fire warden", in case of fire, with adequate training and equipment, or otherwise shutter the business until the alarm is working.