There is 220 volts between the two poles. If you are running 2 wires (black and white) + ground then you hook black to one pole and white to the other. Put red or black electric tape on each end of the white wire and wrap around wire for 3 inches or so next to the connection so the next person will be able to see that the wire is hot and not a neutral.
Sounds like it is a 220-240 Volt hot water heater. The black and red are connected to the 220 volts supply and the white is connected to Neutral. At the breaker panel red and black connect to the 2-pole 220 volt breaker and white goes to the neutral bus bar.
Typically the black wire is "hot", and the white wire is neutral. A 2 pole breaker is most commonly used for 240 V, and as such, you would typically use a 3 conductor wire, with black, red and white (+ ground). In a typical application, the black and red are used in the 2 pole breaker, and neutral is connected to the neutral bar in the breaker panel.
can a 20 amp double pole circuit breaker be used for 2 different 120 v circuits using 14 - 2 wire
You have a double pole breaker for 240Volt supply. The maximum current is 15 amp.
To wire a double pole breaker correctly, connect the hot wires to the breaker terminals and the neutral wire to the neutral bus bar. Make sure to follow the manufacturer's instructions and turn off the power before starting.
Yes, the rating of a 3 pole circuit breaker is the same for each conductor that is connected to it. A three pole breaker rated at 30 amps will have 3 #10 wires from it that connect to the load.
A single pole breaker controls one wire and is used for 120-volt circuits, while a double pole breaker controls two wires and is used for 240-volt circuits.
A single pole breaker controls one hot wire and is used for 120-volt circuits, while a double pole breaker controls two hot wires and is used for 240-volt circuits.
A double pole breaker controls two hot wires and provides 240 volts of power, while a single pole breaker controls one hot wire and provides 120 volts of power.
To properly wire a double pole breaker for 240V, connect the two hot wires to the breaker terminals, the neutral wire to the neutral bus bar, and the ground wire to the ground bus bar in the electrical panel. Make sure to follow the manufacturer's instructions and local electrical codes for safety.
Code only allows one wire to be connected to a single pole breaker. Any additional circuitry has to be done in a junction box downstream from the breaker.
If the load is single phase and the load requires 460 volts to operate, then two conductors will be needed and they will connect to a two pole breaker. If the load is three phase and the load requires 460 volts to operate, then three conductors will be needed and they will connected to a three pole breaker. The sizing of the wires will depend upon the current that is drawn by the loads.
To properly wire a 2 pole breaker in an electrical circuit, connect the hot wires to the breaker terminals, the neutral wire to the neutral bus bar, and the ground wire to the ground bus bar. Make sure to follow the manufacturer's instructions and turn off the power before starting the wiring process.
To properly wire a 2 pole breaker in your electrical system, you should first turn off the main power supply. Then, connect the hot wires to the breaker terminals and the neutral wire to the neutral bus bar. Make sure to follow the manufacturer's instructions and consult a licensed electrician if needed.
To properly wire a double pole breaker for your electrical circuit, you should connect the hot wires to the breaker terminals and the neutral wire to the neutral bus bar in the electrical panel. Make sure to follow the manufacturer's instructions and local electrical codes to ensure safe and correct installation.
Common usage of a three pole breaker is for use on a three phase distribution panel. Single phase distribution panels only use two pole breakers for a 240 volt load.Remember that the breaker must protect the conductors that connect to the load. If you want to try and use a three pole breaker in a single phase panel just because you have the breaker, this is not a good idea even if it will fit.Purchase the proper single phase two pole breaker to match the wire size and the amperage of the connected 240 volt load. Keep in mind that connected 240 volt motor loads have to be sized to 250% of the motor's full load amperage.By doing what you want to do and a fault occurs from this type of installation your insurance company might not cover the damage that it would cause.If the distribution panel is three phase then just connect the two load wires to any two of the three poles on the breaker.