answersLogoWhite

0


Best Answer

Icu is really the maximum perspective fault which a circuit breaker can clear (with the fault current being expressed as rms for ac). This is verified by testing in accordance with the standard and is applicable at a specific set of electrical and environmental conditions. If these conditions change then it may be necessary to derate the circuit breaker. After clearing a fault the circuit breaker does not have to remain serviceable and could be dangerous to operate. This point is particularly important in circuit breakers when the Ics is lower than the Icu.

Ics is the maximum perspective fault current which the circuit breaker can clear and still remain serviceable. The standard does allow some minor welding of the contacts to take place, so after a large fault it would still be necessary to inspect the breaker. When specified as a percentage of Ics, the standard proposes ranges of 25%, 50%, 75% and 100%.

Icw is the perspective fault withstand rating (rms for ac). Circuit breakers may be subject to through fault which they are not intended to clear. While not clearing these faults, the breaker will still need to withstand the thermal and mechanical stress imposed by the fault current. The longer a fault is present the more the effects build up and Icw always has a time element associated with it (i.e. 50 kA for 1 second). The standard specified preferred time ranges of 0.05, 0.1, 0.25, 0.5 and 1 second (although 3 seconds is also often used in practice).

Icm is the peak current which the circuit breaker can safely break or make. It is expressed as the maximum perspective peak current at a rated voltage, frequency and power factor and is always greater than Icu. From a safety aspect this is particularly important as it will be the primary mechanism to protect the operator if the circuit breaker is closed on to a fault.

All ratings are derived under specific electrical and environmental conditions and are verified with the circuit breaker in free air. As soon as the breaker is enclosed in in any kind of panel or cabinet the ratings change and need to be re-assessed as part of the assembly testing.

User Avatar

Wiki User

11y ago
This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: What is Service short circuit breaking capacity?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Related questions

What is the 'short circuit capacity' of a 32A 60898 MCB?

Depends on manufacturer..Normally the ratings are as follows 1. Service short circuit breaking capacity is 7.5 kA 2. Rated short circuit breaking capacity is 10 kA.


What is ics icu icw of load breaker?

Ics: Service breaking capacity for a short circuit (in kA)Icu: Ultimate breaking capacity (in kA)Icw: Withstand capacity (usually in kA for 1 sec)


What is the difference between the rupturing capacity and the short circuit breaking capacity?

Rupturing capacity:Rupturing capacity or breaking capacity expresses the current that a circuit breaker is capable of breaking at a given recovery voltage under certain set conditions of operation. It is expressed in MVA The set conditions are power factor,recovery voltage and rate of rise of restriking voltage. When the current broken is symmetrical it is called symmetrical breaking capacity. When the current broken is asymmetrical it is called asymmetrical breaking capacity. It is common to designate circuit breaker capacity based on asymmetrical breaking capacity. Breaking capacity of a circuit breaker =√3xVxIx10-6MVA Short circuit breaking capacity: It is the highest value of short circuit current which a circuit breaker is capable of breaking under specified conditions of transient recovery voltage and power frequency voltage. It is expressed in kA. The breaking current is expressed in two ways1)The r.m.s value of a.c component of current at the instant of contact separtation.2)The percentage of d.c component of current at the instant of contact separtation. While selecting the circuit breaker for a particular location in the power system the fault level at that point is determined.


What is the rated short circuit capacity of the miniature circuit breaker used?

Breaking Current: The r.m.s value of short circuit current at the instant of contact separation.


Is a T2AH fuse the same as a T2L?

No. A T2AH fuse is a high-breaking capacity type whereas a T2L is low-breaking capacity. Often, High-breaking capacity fuses have ceramic (hence stronger) tubes and low-breaking capacity fuses have glass tubes. High-breaking capacity fuses are able to protect against higher short-circuit currents than low-breaking capacity ones (which could explode under the same conditions).


What is meant by rapture capacity as in HRC fuses?

HRC stands for 'high rupture capacity'. An alternative abbreviation is 'HBC, meaning 'high breaking capacity. The rupture (or breaking) capacity is a term describing the maximum short-circuit current that the fuse can safely interrupt at its rated voltage. Most fuses will safely interrupt any level of fault current between a current that just causes the fuse to operate (melt), up to their maximum breaking capacity- such fuses are called 'full-range'. HRC fuses usually have strong, ceramic bodies to withstand the huge pressure generated when the fuse has to interrupt a large short-circuit current. In contrast, low breaking capacity fuses have weaker bodies made from materials such as glass.


Rupturing capacity of a circuit breaker?

the maximum short current that can be safely break by the circuit breaker.


How do you calculate short circuit capacity of generator by using reactance of the winding?

(Generator kVA / Subtransient Reactance % ) / (1.73 x Voltage) = Short Circuit Current in kA


What is the difference between 1sec and 3sec duration of short-circuit withstand capacity?

The difference between 1 second and 3 seconds is 2 seconds. In terms of short-circuit withstand capacity, it can mean the difference between no damage and damage occurring to the equipment and wiring. Heat rises extremely fast in a short-circuit situation, and you want your protective device to trip before damage is done.


What does a ground fault circuit interrupter look like inside picture wise?

A mechanical switching device, capable of making, carrying and breaking currents under normal circuit conditions. Also capable of making and carrying for a specified time and breaking currents under specified abnormal circuit conditions, such as those of a short circuit.


What is the short circuit capacity of a BS 1361 60A cartridge fuse?

.38 for .4 disconnection time and .70 for .5


What is breaking capacity in mcb?

I haven't heard of this in relation to a breaker. Breakers will have ratings for short circuit interrupting, max voltage, line charging, etc. A load break switch will have a "breaking capacity", meaning it can be opened as long as the load current is below the breaking rating.