One horsepower electric is defined as 746 watts, so 300 horsepower is 224 KW. You don't say what the power factor is, so lets assume 0.85. Divide 224 KW by 0.85, and you get 263 KVA. You are running three phase, no doubt, so divide by 3 to get 88 KVA per winding. Lets assume 480 three phase delta, so divide by 480 to get 183 amperes per winding. Finally, look at motor efficiency. Lets assume 0.95, giving 192 amperes per winding.

To translate between winding current and phase current in balanced three phase delta, multiply by the square root of 3, giving a phase current of 333 amperes per phase.

That's a lot of current, requiring very large windings and conductors, and it would be a very large motor. I would use a motor with a higher voltage, perhaps 4160. This would bring the current down to around 22 amperes per winding, or 38 amperes per phase, a more reasonable value for such a large motor.

User Avatar

Wiki User

13y ago
This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: What is the formula for calculating the full load current of 300 HP motor?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Related questions

What is the formula for calculating the full load current of 3kW motor?

The formula you are looking for is I = Watts/ Voltage, I = 3000/voltage.


What is the Full load motor current of a 75KW motor?

Full load starting current is typically in the region of 5or 6 times the full load motor current;.


What is the formula to calculate the overload setting for a star delta starter?

Full load current ofthe motor x 0.58


What is the formula for calculating the full current load of a 400 watt light?

Assuming an incandescent bulb and a 120 volt supply the formula is Watts = Volts x Amps x Power Factor where PF = 1 for resistive load. Amps = 400 / 120.


Why is motor current draw lower at full speed?

Because full speed is unloaded. As you load the motor, speed decreases, and slip increases, with an accompanying increase in current.


What is Full load current for 40 HP star delta motor?

What is the continuous current of 10HP star delta motor


How is the full load current different to the starting current- is the full load current higher or lower than the starting current?

While starting a motor from standstill to its rated speed, the motor has to overcome the inertia and generate enough torque to over come it. In the process the motor takes higher current during the starting. Once started and set in motion the current reduces ti its normal value. Full load current is lower than the starting current normally.


What is Fla on motor nameplate?

FLA: Full Load Ampere. Its the current drawn by the motor when the motor is running at full load FLA = kW / (1.732*V*pf*efficiency*100)


Are motor conductors sized to the locked rotor current?

According to 2011 nfpa 70 nec Motor conductors are sized with the flc- full load current or the nameplate rating fla- full load amperes


What is the Full load motor current with a 75 KW drive?

3phese 460 volt 75 kw a/c drivi full load current


How do you make correct setting for overload of a 3 phase motor?

125 percent of full current rating of the motor


What is locked rotor current?

"Locked Rotor Current" also called LRA which stands for Locked Rotor Amps, is commonly found on electric motor nameplates. Locked Rotor essentially means the motor is not turning. The current or amps in this case have to do with the amount of electrical energy required to start the motor. At the instant the motor is switched on, it is not turning, and draws the maximum current. As the motor starts to turn, the current goes down. This required energy is much greater than the Full Load Amps or Running Amps, which is the current drawn when the motor is running at normal speed under full load. The current required to start the motor will depend on the type of motor as well as the specified design voltage required for the motor, typically the higher the voltage, the lower the required amperage or current. The term also applies to equipment such as Air Conditioners which have an enclosed motor inside the compressor, as well as the condenser fan(s) etc. Depending on the type of motor, LR current can be anywhere from 3 to 8 times the normal running current, also called RLA, or running load amps.