The reason 277v leg to leg does not measure 554 volts is each phase of the system is 120 degrees out of phase with each other and there fore will not read 554v leg to leg but 480v lag to leg. If you take 277 times the square root of 3 it will equal 480. The meters measure Root Mean Square or rms voltages and are designed to take this into their readings.

User Avatar

Wiki User

17y ago

What else can I help you with?

Related Questions

Can you get 120 volts from a 480 volts 3 phase Y generator?

NO, the 480 Volts Y -- is 4 wire system, with three wires which are hot legs @ 480 volts between each three hot legs. A mid tap is a neutral leg (ground) the white wire. Which gives 277 volts between it and any of the three hot legs. so a 4wire 480 volt Y system. Gives 480 /277 volts.


How do you read 277 volts on meter?

To read 277 volts on a meter, simply ensure the meter is set to the appropriate voltage scale (typically AC). Then, connect the meter leads to the circuit or outlet you are measuring. The display should show the voltage reading, which in this case would be 277 volts. Be sure to take appropriate safety precautions when working with electricity.


What voltage reading would you get from a 277 480 volt system?

From a three phase four wire distribution system the voltages would be as follows. From L1 to N - 277 volts. From L2 to N - 277 volts. From L3 to N - 277 volts. From L1 to L2 - 480 volts. From L2 to L3 - 480 volts. From L3 to L1 -480 volts.


What is the difference between 277 volts and 240 volts?

These voltages are both wye connection three phase voltages. The voltage difference comes from the primary three phase voltage supplies. 277 volts is obtained from 277 x 1.73 = 480 and 240 volts is obtained from 240 x 1.73 = 415. 480/277 volts is a common three phase American voltage. 415/240 volts is a European voltage. In Canada a common three phase voltage is 347/600. The 240 volts could also be a single phase voltage in North America derived from a split phase secondary on a distribution transformer that supplies 120/240 volts to homes.


Is 277 volt one hot wire?

No, 277 volts is the line to neutral of a 480 volt wye three phase system. L1- N, L2 - N and L3 - N will give you 277 volts. L1 to L2. L2 to L3 and L3 to L1 will give you 480 volts.


What is the purpose of 277 volts AC?

Commercial lighting. In a facility where 3 phase 480 volts is needed for machinery, 277 is also readily available because each leg of 480 to ground is 277 volts. This way numerous supply transformers are not needed in a commercial building.


Will a switching power supply work on 277 volts?

Not unless it is rated for that voltage. You can likely find a step down transformer from 277 volt sto 120 volts.


In WYE 480VAC each leg to neutral is equal to how many volts?

In WYE 480 VAC each leg to neutral is equal to 277 volts. 480 / 1.73 (sq root of 3) = 277.


Can you get 110 volts from 277volts?

The voltage of 277 is the wye connection of a 480 volt three phase supply. The only way to reduce 277 to 120 volts is with a step down transformer.


How do you come up with 277 volts?

The star point or wye voltage of a 480 volt three phase four wire system is 277 volts. The 480 voltage is divided by the sq root of 3 (for 3 phases). The sq root of 3 is 1.73. 480 volts/1.73 = 277 volts. The same formula is used on all three phase four wire systems. 208 volts /1.73 = 120 volts, 416 volts /1.73 = 240 volts, 600 volts / 1.73 = 347 volts.


How can 240 vOLTS power a 277 vOLT light?

Slightly dimmly


How do you wire a 277 volt heater from 480 volt box?

Answer for USA, Canada and countries running a 60 Hertz supply service.The 277 volt heater can be wired to a single pole breaker in a 3 phase 4 wire 480 volt distribution panel. The breaker should be sized to the amperage draw of the heater. 277 volts is the star point (wye) voltage of a 480 3 phase system. 480 / 1.73 = 277 volts. The third answer is not correct, two phase legs of a 480 volt system will give you 480 volts. It is the phase leg to ground (neutral) that gives you the 277 volts.A 277 Volt heater or device may not be wired to a 480 Volt circuit or box. A 277 Volt device may only be wired to a circuit rated for 277V/480V equipment.2 legs of 480 volts will give you 277. But since you don't know the answer you probably shouldn't be doing it! Please don't kill yourself, hire a licensed electrician.Before you do any work yourself,on electrical circuits, equipment or appliances,always use a test meter to ensure the circuit is, in fact, de-energizedIF YOU ARE NOT REALLY SURE YOU CAN DO THIS JOBSAFELY AND COMPETENTLYREFER THIS WORK TO QUALIFIED PROFESSIONALS.