answersLogoWhite

0


Best Answer

Littlewatts:

If your question is "Why doesn't the neutral carry current to ground, instead of back to the transformer?" then:

It's important to remember current flows in loops. "Ground" is a reference. If you have a single phase transformer, power will flow out of the transformer, through the hot wire to your wall outlet, and back out the neutral wire, then back to the transformer (likely the center tap of the transformer so you have 120 and 240 volts to your house). It is likely the transformer is grounded, so the center tap is at the same voltage as ground, but since there's a perfectly good wire connecting the return wire to the transformer, the current doesn't have to try to go through the ground back to the transformer.

If your question is "Why isn't current flowing in the neutral wire?", then:

In three phase power, with a three phase 4 wire system (the fourth wire is the wye-neutral) there should be little to no current flowing in the neutral. This is because the three phases are balanced - they are of the same magnitude, 120 degrees apart. If you took an instantaneous snapshot of this and referenced to one of the three currents, you would see something like this: Phase 1 = 10Amps, 0 degrees, Phase 2 = 10Amps, -120 degrees, Phase 3 = 10Amps, 120 degrees. If you summed these together, you will see they sum to zero. This summation is what will flow in the neutral. If there is a slight unbalance between the three (say one is 10.1 Amps), you will see some current in the neutral.

If you're referring to your home, where you likely have single phase, and have three prong outlets, the neutral should be carrying the return current from the hot wire. This is not to be confused with the ground plug (the round one), which should not be carrying any current. The purpose of this plug is to provide a low resistance path to ground in the event something bad happens (so the current chooses this wire to flow in instead of you).

There is the chance that you're connected to an ungrounded system. This would likely have three wires instead of four. In this case, there is no neutral. Without knowing exactly what you're measuring it's difficult to provide a clear, short and concise answer.

<><><><><>

Alex156:

Other answer (explains how a circuit works in detail): Because it is not designed to. The neutral line carries the 'return' current; whereas the ground line is reserved as an unobstructed bypass for emergency current drain.

Neutral does not "carry current to ground". Neutral carries current to some return point, which may or may not be grounded. Neutral, however, is always grounded at some point which, conversely, may or may not be the return point.

Confusing? Seemingly reverse defined? Then you better pay attention, because understanding is critical.

Take a light bulb, a switch, a battery, and three pieces of wire, and series connect them. You can turn the lamp on and off by closing and opening the switch.

This is a standalone circuit, and it is not grounded anywhere. It works just fine.

What is the voltage on the battery anode?

Wait! Before you say 1.5VDC you better be asking "with respect to what?"

Well, lets connect battery cathode to ground. Stop and think about this little circuit. You can still turn the bulb off and on by opening and closing the switch.

What did the ground do?

Absolutely nothing - or absolutely something - depending on your point of view...

There is no current on the grounding wire. None. Nada. Zilch. Try it with a micro-ammeter; except for parasitic leakage, there will be nothing.

Now what about that wire going from the cathode to the near terminal of the switch or bulb (depending on how you wired it)? That carries current, don't you say. More on this later.

Back to the "absolutely something" part... That grounding wire provided a connection from some arbitrarily chosen point in the circuit (it could have been the anode, for all I care) to some well defined ground, ground being defined as the common connection between multiple connections that all wind up connected together to the dirt, i.e. ground.

If you measure the voltage on the anode with respect to ground then, lo and behold, you have 1.5VDC. Why? Because you created a circuit with the meter.

Now, go back twelve paragraphs, to my (Alex146) second paragraph... I said "at some point". I'm going to get picky and say "at one and only one point". This point CANNOT be overemphasized, because, with only one point, there can be no current; and with more than one point, there can be no safety

Hence, the neutral does not carry current to ground - it carries current back to the power return point. Conversely, the grounding conductor never carries current except in a fault condition.

Oh - a new word - fault...

Lets modify the circuit and put a 1 ampere fuse between the battery anode and the rest of the circuit. That fuse is effectively a piece of wire because its resistance is very much lower than the bulb, but not as low as the wires. Things still turn on and off. OK?

Now, lets create a fault by connecting a wire between the load side of the switch and ground (across the light bulb). This is a short circuit.

With the switch open, nothing happens. With the switch closed, two things happen. The battery attempt to deliver infinite current, which it cannot, and the extra piece of wire, be a machine frame or whatever, becomes electrified, potentially creating an electrocution/fire hazard, i.e. extra voltage/current where it should not be.

If the original circuit was still ungrounded, the lamp would still light, but the battery cathode would become -1.5VDC with respect to ground. This offsetting of voltage isn't a big deal in single phase power, but can raise three phase power voltage levels with reference to ground to 1.732 times what they should be, which can initiate fault conditions in other phases. Computer like equipment (called protective relays) are used to detect these overvoltage conditions and hopefully warn operators and take care of any potential problems before a full fault develops.

If, on the other hand, the circuit were grounded, then the short circuit would cause the fuse to blow before any wiring could be damaged and, hopefully, before anyone could get electrocuted.

This all sounds trite doesn't it? Well, it turns out that a lot of engineers spend time designing adequate grounding systems, as well as designing the National Electrical Code (US); and I will assure you that they do not do so just because they "want to".

User Avatar

Wiki User

13y ago
This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: Why doesnt the neutral carry current to ground?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Continue Learning about Electrical Engineering

Why not hook ground to neutral since they are hooked on same spot in breaker box why not in outlet box.?

The "hot" wire and the neutral wire both carry current (the same amount, in fact) when a load is connected to complete the circuit. The ground wire never carries current except when a fault-to-ground situation occurs. Yes, neutral and ground wires should both be at ground potential, but NO they should not be connected at the outlet.


Why do you need neutral if things work with earth connection since both r at same potential?

Neutral is the common return, and it expected to be a current carrying conductor. Earth (or ground), on the other hand, is a protective conductor that is not expected to carry current. It is there to provide a path for current in the event of fault, and to trip the protective device, i.e. fuse or circuit breaker. Earth is also not usually insulated, so it is not rated to carry current other than long enough to trip the protective device.


What is difference between nutral and earth wire?

A neutral wire provides a return path for the hot lead while an earth or &quot;ground&quot; wire is provided as a safety function only that is not normally intended to carry current except for the purpose of operator protection.


What is the Acceptable current in ground cable?

A ground is not expected to carry any current. It's only there in case of a fault condition. If you have a current reading through a ground wire there is a fault that needs to be corrected. Many times a lazy electrician who couldn't find a broken neutral connected a receptacle or light fixture to ground to make it work. This is not a proper use of the grounding system, and it is dangerous and should be corrected if encountered. The grounding conductor should have at least the same ampacity of the largest phase conductor connected to the circuits it protects. That way it is capable of carrying the full current of the largest conductor in case of a fault.


How do you carry out short circuit test on power transformers?

For carrying Short Circuit Test on Power Transformer Do the following: 1] Isolate the Power Transformer from service. 2] Remove HV/LV Jumps and Disconnect Neutral from Earth/Ground. 3] Short LV Phases by Cu/Al plate which could withstand short circuit current and connect these short circuited terminals to Neutral 4] Energise HV side by LV supply (440 3ph Supply) with OLTC tap position on Normal. 5] Measure Current in Neutral, LV line voltages, HV Volatage and HV Line Currents on various OLTC Tap position. Analysis: If Neutral current is near to zero transformer windings are OK If Neutral current is higher or equal to Line current between LV Phase one of the winding is Open.

Related questions

Can ground conductor use as a neutral conductor in a house wiring?

No. Absolutely not. The ground conductor is not rated to carry constant current flow. It is only rate to carry fault current flow.


Why not hook ground to neutral since they are hooked on same spot in breaker box why not in outlet box.?

The "hot" wire and the neutral wire both carry current (the same amount, in fact) when a load is connected to complete the circuit. The ground wire never carries current except when a fault-to-ground situation occurs. Yes, neutral and ground wires should both be at ground potential, but NO they should not be connected at the outlet.


In the electrical system of the US what is the difference between the neutral and the PE Ground?

US NEC: The neutral conductor is an insulated grounded conductor used as the current return in a circuit. The color designation for neutral is white. The protective ground (PE, protective - earth) is a non-insultated grounding conductor used to shunt fault current to ground, tripping the protective device. The color designation for PE ground is green. Neutral and PE ground are tied together at the distribution panel. PE ground is also connected to a solid earth ground, such as grounding rods driven into the earth. Downstream of the distribution panel, PE ground is never used to carry operational current. Any current flow on PE Ground, other than parasitic current, is considered a ground fault, which must be corrected. In fact, GFCI (Ground Fault Current Interrupting) breakers will trip when neutral current does not match hot current, an indication of PE ground current flow.


Does neutral wire carry voltage in a closed circuit?

The ground wire should carry no current at all, it is there in case of a short circuit to carry the (short circuit) current back to the breaker panel to trip the breaker. The neutral will carry the unbalanced load current between the 240 volt legs. e.g. L1 and N (neutral) 120 volts the load draws 8 amps. L2 and N (same neutral) 120 volts the load draws 12 amps. The difference between the two amperages is what the neutral will carry 12 - 8 = 4 amps.


Why dont you use earth wire place of neutral?

Earth is neutral, but only at the distribution panel and upstream from it. Downstream of the distribution panel, earth and neutral shall not interchange or cross connect their connections or their roles - earth is protective ground - and neutral the current carrying return conductor.


Why neutral wire does not carry current in closed ac circuit?

The neutral wire does carry current in a closed AC circuit. Clamp a clamp on amp meter around the neutral wire directly after the circuit load and it will read the same current as is on the "hot" wire.


What is a neutral wires' function?

To carry the unbalanced load current.


What will be happen if you use earthing in place of neutral in any circuit?

* * * DANGER * * * DANGER * * * DANGER * * *Do not, under any circumstances, use earth ground instead of neutral in a circuit. Besides being a violation of the US National Electrical Code, and probably the applicable electrical code for any country that has an existing neutral system in place, it constitutes a hazard because the earth ground conductor is not rated to carry operational current. It is only there to carry momentary fault current so as to trip the protective device (fuse or circuit breaker) in the distribution panel. Also, placing operational current on protective earth ground can raise the voltage on that conductor, creating the potential for an electrocution hazard.


Why we don't get shock if we touch neutral wire..we need two wires to close circuit pH and n when circuit closes current will flow around the circuit and one wire gets shocked other not why?

We don't get shocked when we touch neutral and ground because neutral is grounded back at the distribution panel, so the effective voltage between neutral and ground is very low. It won't be zero, because there is current flowing on neutral, causing a voltage difference between the load and the distribution panel, but it is low enough, assuming there is no malfunction, to not cause a shock.In the case of touching hot and neutral, or hot and ground, you will get shocked because there is line voltage between hot and neutral, and because neutral and ground are connected together, there is also line voltage between hot and ground.Note, however, that connecting a load between hot and ground is a violation of the code and the intent of the design, because ground is not rated to carry current except in short term fault conditions - you must always connect a load between hot and neutral, or between hot and hot, as the case may be.


Why do you need neutral if things work with earth connection since both r at same potential?

Neutral is the common return, and it expected to be a current carrying conductor. Earth (or ground), on the other hand, is a protective conductor that is not expected to carry current. It is there to provide a path for current in the event of fault, and to trip the protective device, i.e. fuse or circuit breaker. Earth is also not usually insulated, so it is not rated to carry current other than long enough to trip the protective device.


Why neutral wire current is more in 1-phase than the 3-phase?

On a typical house plug, there are three wires - the positive, neutral, and ground. Ideally, the positive and neutral wires carry the current (the neutral wire provides the return path for the current from the positive wire), and the ground wire carries no current. In a three phase system, you have three phase voltages of the same magnitude (ideally), but the three phase voltages are out of phase with each other by 120 degrees - meaning one is at 0 degrees, one is at 120 degrees, and one is at -120 degrees if you looked at them on an oscilloscope, and referenced to one phase. If you take (1 at an angle of 0 degrees) + (1 at an angle of 120 degrees) + (1 at an angle of -120 degrees), you will get zero. Thus the return path in three phase power is shared between the three phases, and the neutral wire in a 4 wire, three phase system is equivalent to the ground wire connected to your wall plug. The ground wire will only carry current when the "vector sum of the phase voltages does not equal zero" (meaning the simple equation at the beginning of this paragraph does not sum to zero - whatever it sums to is what is flowing in the neutral).


Why can't the ground wire be connected to neutral at the receptacle instead of in the main panel?

First off, this is for a single phase 120/240V system only. The ground and neutral can be bonded at the receptacle but not instead of bonding them at the panel.You should always have them bonded together at the panel in a single phase 120/240V system. Otherwise you risk having a floating neutral in your system.