It's not - I have seen 50kVA, 100kVA,...15000kVA, 36000kV, 180000kVA to name a few examples. Near where I live, I don't believe there are more than a few Transformers rated in multiples of 11 as you state.
transformer action doesn't depend on power factor that is why we indicate its rating in KVA
This is the rated output of the transformer, obtained by multiplying the rated secondary voltage by the rated secondary current. And it's 'kV.A', not 'kva'.
ka of mccb=transformer(KVA)x100/1.732xsecondary voltagex%impedence of transformer
The kVA rating will be listed on the transformer's nameplate, which is usually on the front of the transformer. The 480v to 120v is irrelevant, because many transformers with different kVA ratings convert 480 volts to 120 volts. The kVA ratings can be different and thus affect the rated current through the transformer.
Transformers are rated in VA or kVA. That is because the voltage is limited by the power loss in the magnetic core, and the current is limited by the power loss in the resistance of the windings. The rated voltage times the rated current gives the transformer's rating in kVA.
Depends on the kva rating of the devices to be tested using a transformer.
yah! definately affects, the kva of transformer is suitable for the certain load according to the rating.
transformer action doesn't depend on power factor that is why we indicate its rating in KVA
VA or KVA or MVA
You can tap off approximately 833 200 amp panels from a 250 kVA transformer. This calculation is based on dividing the kVA rating of the transformer by the current rating of the panel.
The result is that the transformer runs cool and contented. The '250 KVA' rating on the transformer is its maximum ability to transfer power from its input to its output without overheating, NOT an amount of power always running through it. If the 3 KVA load happens to be the only thing connected to the transformer at the time, then only 3 KVA flows into the transformer from the primary line, and only 3 KVA leaves the transformer secondary.
To calculate the kVA rating of the transformer, you can use the formula: kVA = (Voltage × Current) / 1000. In this case, the secondary winding delivers 10 amps at 480 volts. Therefore, the kVA rating is (480 V × 10 A) / 1000 = 4.8 kVA.
Yes, but your input current is going to be high at 133 amps. The output of the transformer is not going to be 16 KVA, that is the rating of the transformer.
This is the rated output of the transformer, obtained by multiplying the rated secondary voltage by the rated secondary current. And it's 'kV.A', not 'kva'.
ka of mccb=transformer(KVA)x100/1.732xsecondary voltagex%impedence of transformer
The kW rating of a transformer can be calculated by multiplying the kVA rating by the power factor. For example, if the power factor is 0.8, then the kW rating of a 100 kVA transformer would be 80 kW. You can also use the formula: kW = kVA x power factor.
The kVA rating will be listed on the transformer's nameplate, which is usually on the front of the transformer. The 480v to 120v is irrelevant, because many transformers with different kVA ratings convert 480 volts to 120 volts. The kVA ratings can be different and thus affect the rated current through the transformer.