In a three phase panel a double pole single throw breaker is definatly putting out 220v as two separate 110v circuits that are out of phase with each other. So from one leg to the other its 220v and from either leg to ground its 110v.
By definition it is 220v but it could be used as separate 110v circuits as well. The only way to know how its actually being used would be to open up the sign and see if both circuits are tied into one ballast as 220v or if they split and go to differant ballasts then they are 110v circuits using a common disconnect means.
Being that either way both circuits terminate in the same area they technically both require a double pole single throw breaker.
Sizing circuit breakers for motors falls into a different category. Because of the inrush of current when the motor is in the stopped position, the breaker has to be sized to allow for this. Breakers usually are 250% of the nameplate full load amp rating. The wires that feed the motor are sized to 125% of the full load amps of the motor.
A single pole circuit breaker can protect one hot wire to a given load where as a two pole circuit breaker can protect two hot wires to a given load. In the North American system this would equate to 120 volts on a single pole circuit breaker and 240 volts on a two pole circuit breaker.
This condition is commonly known as a "Double Tap", and is only permitted if the breaker specifically allows it. Some Square D breakers and possibly other manufacturers allow terminating two wires under the screw, and if the breaker allows it, it will be identified as such on the label. If your specific breakers do not allow two wires terminating under one screw, you will need to install another appropriately sized breaker for that circuit, assuming your panel has the space available for the additional breaker. As always, if you are in doubt about what to do, the best advice is to call a licensed electrician. Before you do any work yourself on electrical circuits, equipment or appliances, always use a test meter to ensure the circuit is, in fact, de-energized. IF YOU ARE NOT ALREADY SURE YOU CAN DO THIS JOB SAFELY AND COMPETENTLY REFER THIS WORK TO QUALIFIED PROFESSIONALS.
A Stadard washing machine uses a dedicated 15 Amp single pole breaker. Nothing else should be on the circuit.AnswerThe above answer applies to North America. In the UK, a washing machine is connected to the ring main system using a three-pin plug that requires a 13-A fuse.
The device that you are looking for is called a surge suppressor. It is a small device that can be mounted in one of the knock out holes in the distribution panel. They are a four wire device. It should be connected across a common tie double pole breaker. The two black leads from the suppressor connect to each of the terminals of the two pole breaker. The third white lead connects to the neutral bar of the distribution panel. The forth green wire connects to the ground buss, (not to be confused with the neutral bus). With the breaker turned on it continuously monitors the voltage of the distribution panel and automatically sends power spikes to ground.
Your ballast should show two wires for supply side of ballast. Make sure that neither side of this is grounded to the light and connect the 220 V from your breaker to these two wires and then connect a ground to the chassis of the light from the panel.
Sounds like a 240 volt sub panel feeding a well pump.
You have a double pole breaker for 240Volt supply. The maximum current is 15 amp.
A double breaker is a breaker that has 2 switches on it. One of the switches is 20 amps and the other is 30 amps.
The appropriate double pole 30 amp breaker to use for a dryer installation is a 30 amp double pole circuit breaker.
No, a double pole 50 amp breaker protects a 240 volt supply at 50 amps. The number that is on the handle of the breaker is the amperage that the breaker will trip at if an overload occurs on the circuit.
The maximum amperage rating for a double breaker 20 amp is 20 amps.
50 amp breaker wired with AWG # 6 wire.
A 60 amp double pole breaker can handle a maximum electrical load of 60 amps.
A single pole breaker controls one wire and is used for 120-volt circuits, while a double pole breaker controls two wires and is used for 240-volt circuits.
before the load
Yes!