connect the neutral point of the star (secondary) to u phase of primary, and now apply voltage to primary and measure the voltage between V&R, W&B, V&Y and V&B. when you measure voltage b/w

1. V&R the voltage must be maximum,

2. W&B Should be minimum and

3. voltage between V&Y and V&B should be same

U.V&W are primary (Delta)

R,Y&B are secondary (Star)

User Avatar

Wiki User

13y ago

What else can I help you with?

Continue Learning about Engineering

How can you test ZNyn11 Vector group transformer?

This vector group test is done to confirm whether the vector group provided in the name plate is correct or not and also to confirm that the winding has not been damaged during transport, installation and erection. Taking a particular example, for Dyn11 transformer we have to apply 3~ 400v to the primary, with primary 'U' & secondary 'u' shorted.... then check the voltage across different terminals such as V-v, V-w, W-w, W-v for Dyn11 configuration (V-v = V-w = W-w)less than W-v.... you can compare the results after drawing the vector diagram for the same...... the purpose of shorting the primary U & secondary u is to nullify the phase shift, to obtain a reference vector...


Using vector to add objects and display their member variables?

import java.util.Vector; suppose-:::: test t=new test(); /**this is how we add elements to vector*/ Vector v=new Vector(); v.addElements(t);


What is the meaning of test setup?

There may be faults in a design. Verification is required to any design before utilizing it for any application. The verification is done with a test vector or a test pattern. Applying these vectors is called test setup.


What is an elevator shunt trip test?

An elevator shunt trip test checks the heat detector placement. It also monitors power and wiring diagram of an elevator.


Write a program using c plus plus to whether the given square matrix is symmetric or not?

int sym_test (const int **a, int n) {int i, j, sym;i=1, j=0, sym=1;while (sym && i

Related Questions

How can you test ZNyn11 Vector group transformer?

This vector group test is done to confirm whether the vector group provided in the name plate is correct or not and also to confirm that the winding has not been damaged during transport, installation and erection. Taking a particular example, for Dyn11 transformer we have to apply 3~ 400v to the primary, with primary 'U' & secondary 'u' shorted.... then check the voltage across different terminals such as V-v, V-w, W-w, W-v for Dyn11 configuration (V-v = V-w = W-w)less than W-v.... you can compare the results after drawing the vector diagram for the same...... the purpose of shorting the primary U & secondary u is to nullify the phase shift, to obtain a reference vector...


How do you test Yyn0 vector group of transformer?

in electrical engineering


How can you test the vector group dyn5?

You can test a vector group DYn5 transformer by performing insulation resistance tests, turns ratio tests, winding resistance tests, and vector group verification tests using a suitable test set. It is recommended to follow the manufacturer's guidelines and relevant industry standards when conducting these tests.


What are precommissioning tests of transformers?

magnetising current test, magnetising balance test, s.c test, vector group test, winding resistance test, ratio test


Using vector to add objects and display their member variables?

import java.util.Vector; suppose-:::: test t=new test(); /**this is how we add elements to vector*/ Vector v=new Vector(); v.addElements(t);


Does vector marketing drug test?

no


How do you test a ignition coil with circuit diagram?

You cannot test it with a diagram. You will need a multimeter to test the coil. Click the link.


What is science test group?

Test Group when you test a project with a "GROUP"


Where can you find a diagram for load test of a DC shunt motor?

See the diagram linked below.


What is circuit diagram for ratio test of transformer?

Mechanauts


What can you determine from an electric field vector at one point?

From an electric field vector at one point, you can determine the direction of the electrostatic force on a test charge of known sign at that point. You can also determine the magnitude of the electrostatic force exerted per unit charge on a test charge at that point.


The group exposed to a newly created drug that is being tested in an experiment is called what?

The group is called the test group or test subjects.