To calculate the current on a delta to star transformer, first identify the line current in the delta configuration (I_line). The phase current in the star (wye) configuration (I_phase) can be calculated using the formula: I_phase = I_line / √3. This relationship arises because the line current in a delta system is √3 times the phase current in a star system. Therefore, knowing the line current allows you to easily find the phase current in the star configuration.
With a transformer...
To calculate the current in a Star-Delta configuration for a 30 kW, 415 V, 3-phase induction motor, you first determine the full load current (FLC) in Star configuration using the formula: ( I = \frac{P}{\sqrt{3} \times V \times \text{PF}} ), where ( P ) is power (30,000 W), ( V ) is line voltage (415 V), and PF is the power factor (assumed to be around 0.8 if not specified). For the Delta configuration, the current would be calculated as ( I_{Delta} = I_{Star} \times \sqrt{3} ). In the Star configuration, the current will be approximately 41.6 A, and in Delta, it will be around 72 A.
Full load current ofthe motor x 0.58
delta star
To calculate the current for a 10 HP three-phase motor operating at 415 volts in a star-delta configuration, you can use the formula: Current (I) = (HP × 746) / (√3 × Voltage × Power Factor). Assuming a typical power factor of 0.8, the full load current would be approximately 14.5 amps in star connection and about 28.9 amps in delta connection.
There is a problem called "neutral phase shift" in star-star transformer, if we connect unbalance load(single phase load at secondary), then the phase point is shifted towards neutral. we require sinusoidal secondary voltage at secondary, for this flux must be sinusoidal. Flux will be sinusoidal, if it contains the third harmonic component of exciting current. so third harmonic current can not flow in star-star transformer. so we use delta-star transformer,in delta , third harmonic component can flow & get sinusoidal output.
One must check the design of the transformer windings. STAR - Delta or Star to star or Delta - star or Delta Delta. Wiring must be done accordingly.
It is used in where the transformer are connected in star delta.
Yes, possible. NGR or earthing transformers are used when it is necessary to limit the fault current.
With a transformer...
With a transformer...
How to calculate current of star and delta moter with 55kw 380v 85%
To calculate the current in a Star-Delta configuration for a 30 kW, 415 V, 3-phase induction motor, you first determine the full load current (FLC) in Star configuration using the formula: ( I = \frac{P}{\sqrt{3} \times V \times \text{PF}} ), where ( P ) is power (30,000 W), ( V ) is line voltage (415 V), and PF is the power factor (assumed to be around 0.8 if not specified). For the Delta configuration, the current would be calculated as ( I_{Delta} = I_{Star} \times \sqrt{3} ). In the Star configuration, the current will be approximately 41.6 A, and in Delta, it will be around 72 A.
Full load current ofthe motor x 0.58
delta star
i thinkecause he like sit idkk
1. A three phase transformer with HV side star connected and LV side delta connected results in economical design. 2. However, if star winding is required on the LV side due to load / safety requirements, then it is common to connect the HV side as delta. See next item to know why a delta winding is necessary. 3. Delta winding provides a path for third harmonic current present in the magnetising current due to core saturation. Hence, delta winding acts a thrid harmonic filter. This will help to eliminate non-sinusoidal voltage on transformer load terminals. This is an important feature of transformer design. Hence, in practice, all transformers will invariably have a delta winding.