To calculate the output current of a 10 kVA three-phase UPS, you can use the formula:

[ I = \frac{P}{\sqrt{3} \times V} ]

where ( P ) is the power in kilowatts (10 kVA = 10 kW for a unity power factor) and ( V ) is the line-to-line voltage of the system (typically 400V for industrial applications). For example, if using 400V, the output current would be:

[ I = \frac{10,000 , \text{VA}}{\sqrt{3} \times 400 , \text{V}} \approx 14.43 , \text{A} ].

User Avatar

AnswerBot

1mo ago

What else can I help you with?

Continue Learning about Engineering

How do you calculate the load percentage of a three phase UPS?

output power/Rated power


What are advantages in THREE phase UPS over SINGLE phase UPS?

You need to match the UPS to the service. If it is three phase you need a three phase UPS, and vice versa for single phase. It isn't a case of being better, it is a situation where you need to match your application.


Can we connect ups to inverter?

Yes, you can connect an uninterruptible power supply (UPS) to an inverter, but it's important to ensure compatibility between the two devices. The UPS should be designed to handle the output from the inverter, and the inverter should provide a stable output voltage and frequency that the UPS can work with. Additionally, be cautious of the load and total wattage to avoid overloading either device. Always consult the manuals or a professional for specific configurations.


How many amps per phase provide 60 KVA UPS with 400 volts?

You have a 3-phase UPS consuming 60kVA at 400V, So, to determine the current per phase, apply the following formula: I= S / (U x sqrt[3]) where S is apparent power (in VA) U is line voltage (in V) I is current per phase (in A) thus, this gives I= 60 000/ (400 x sqrt[3]) I=86.6 amps


How can we run uninterrupted power supply in parallel?

Uninterruptible Power Supplies (UPSs) can be configured in parallel mode by connecting the output terminals of both UPSs. The capacity and all technical specifications and feautures of the UPS should match with another UPS. The UPS manufacturers ensure the synchronization of all UPSs connected in parallel using bus connectors that serve as frequency, phase, voltage, and current monitoring to maintain the stability of the systems.It can be paralleled more than 2 units which is usually up to 8 units depending on the manufacturer's specification. Before switching on the UPS make sure that all the parameter settings are all the same for the rest of units to be paralleled. If all units are now running, if one UPS fails the protected load should not be affected since there are still some units that can be able to support the entire loads.

Related Questions

What will be input and output current of 10 KVA 3 phase UPS?

A 10 KVA 3-phase UPS will have an input and output current that depends on the specific voltage of the system. You can calculate the current by dividing the apparent power (in this case 10 KVA) by the square root of 3 multiplied by the voltage. For example, for a 208V system, the input and output current would be approximately 28.8 amps.


How do you calculate the load percentage of a three phase UPS?

output power/Rated power


What is the difference between single and three phase on line UPS?

The difference between a single and a three phase online UPS is a 3 phase can supply a 100% unbalanced load on its output without affecting its performance. A single phase cannot supply a 100% unbalanced load on the output without affecting its performance.


What will be the full load current of single phase 5Kva ups?

Assuming single phase voltage 220 Volts AC, the maximum current would be approximately 25 amps.


What are advantages in THREE phase UPS over SINGLE phase UPS?

You need to match the UPS to the service. If it is three phase you need a three phase UPS, and vice versa for single phase. It isn't a case of being better, it is a situation where you need to match your application.


Why ups rating is in kva?

The kva rating includes the power factor of the connected load.KW * Power Factor = kva.AnswerThe above answer is incorrect, as it's actually kV.A x power factor = kW.The answer is straightforward, the output of the UPS is the product of its rated output voltage and its rated output current, and the product of voltage and current is 'apparent power', expressed in volt amperes.


Why ups rated in kva?

The kva rating includes the power factor of the connected load.KW * Power Factor = kva.AnswerThe above answer is incorrect, as it's actually kV.A x power factor = kW.The answer is straightforward, the output of the UPS is the product of its rated output voltage and its rated output current, and the product of voltage and current is 'apparent power', expressed in volt amperes.


How much current will 5 kva ups draws while charging?

- For a single phase supply @ 220 voltscurrent drawn by 5kva UPS = 22.7 amperes (at full load.)


Is ups input or output device?

UPS is Uninterruptable Power Supply. It is neither input not output. It supplies electrical power to a computer when the main electrical supply is interrupted. It does not handle data in any way.


How calculate ups battery backup time?

The UPS should be rated in Amps per Hour. Just divide that number by the current requirements of the device connected to the UPS. Say that the UPS is rated for 10 Ampere Hours and your device draws 2 amps. You could run the device for about 5 hours.


What is the amps of a 650 VA UPS?

To answer this question the voltage of the UPS has to be stated. Take that voltage and divide it into the 650 rating. The answer will be the output amperage of the UPS.


Is there any current at the input port of a ups if it is not connected to the main supply and the ups is on?

No, not at all. It will have current when it is charging only