An artificial neutral is crated in the CT of the line to be protected (for transmission lines) a CT is fixed in the neutral of the CT. if there is any imbalance in the 3 phase current then the relay will develop a difference in neutral.that can be sensed by the CT,then gives the trip command to relay
You can't have a three phase earth fault, you can have a phase to phase or a phase to earth fault. If you want the potential phase to earth fault current it will be your voltage times your impedance. If you want the phase to phase potential fault current then you should just double the above result.
by calculating the loop current
An earth-fault loop is the path taken by the fault current, when an earth-fault occurs within an electrical installation, and comprises a series circuit made up ofthe utility company tranformer's low-voltage winding,the utility company's distribution cable's line conductor,the consumer's line conductor to the point of an earth fault,the consumer's earthing conductor,and the resistance of the earth path back to the transformer.The combined opposition of this series circuit to the flow of fault current is termed the earth-fault loop impedance, expressed in ohms.
Criteria-in order to protect the stator core from damage during internal earth fault it is necessary to limit the stator earth fault current al low as possible.may be upto 10amp for generator. Basis for selection of ngtr- if generator is connected to the system through generator transformer then generator can be treated as an isolated system which is not influenced by the distribution earthing system. In this case you can select earth fault current as low as possible, but if we use ngr then in order to limit the low earth fault current size of the ngr will be increased.due to big size of ngr we required more space & also its too costly. V = ir means if v constant i is inversely proportional to r exp:-to limit 10amp current , v =11kv/root 3 r = 11/root 3/10*1000=635.10 ohm ( very high value) for overcome on this, general practice to use a ngtr so that we can limit low earth current without any extra cost. Exp:- ngtr 11/240v to limit 10amp current current reflect on secondary side of ngtr will be = (11000/root 3/240)*10=264.6 amp. Resistor value on secondary side r =240/264.6 =0.9 ohm ( approximately) which is much lower than 635.10 ohm. Basis for selection of ngr- if generator is directly connected to the system then we can not limit the earth fault current up to 10 amp. We have to select the earth fault current value above the residual capacitive charging current of system.also we need to check the possibility of relay setting operation with ct ratio. For exmp- if ct ratio is 2000/1amp & earth fault limit current is 100amp relay selected with 10 % setting. Then that relay will see only 200amp earth fault current it will not see 100amp current. Also we can not keep generator solidly grounded because of high earth fault current stator can damage same will happen with ht motor if it is connected to this system. So for this case we need to select the ngr with proper earth fault current
A current transformer is primarily used at the neutral point of a transformer for earth fault protection. A neutral current transformer will measure any ground fault current which will essentially flow from the star point of the transformer. A fault-detection device other devices is connected to the current transformer and, if the fault current exceeds a certain trigger value, the fault-detection device will give a trip command to an earth-fault relay to disconnect the supply of electricity to the transformer.
trh
transformer max earth fault current
You can't have a three phase earth fault, you can have a phase to phase or a phase to earth fault. If you want the potential phase to earth fault current it will be your voltage times your impedance. If you want the phase to phase potential fault current then you should just double the above result.
An earth fault relay is a relay that is activated by a fault current that flows from the power line to the earth. Earth fault relays are found in power distribution systems.
Earth fault relay and an over current relay Methods to energies an earth fault relay with simulation diagram?
by calculating the loop current
Temperature rise and fault levels.
If the fault is a direct short to ground, the fault current can be high enough to trip the upstream protection.
An earth-fault loop is the path taken by the fault current, when an earth-fault occurs within an electrical installation, and comprises a series circuit made up ofthe utility company tranformer's low-voltage winding,the utility company's distribution cable's line conductor,the consumer's line conductor to the point of an earth fault,the consumer's earthing conductor,and the resistance of the earth path back to the transformer.The combined opposition of this series circuit to the flow of fault current is termed the earth-fault loop impedance, expressed in ohms.
Criteria-in order to protect the stator core from damage during internal earth fault it is necessary to limit the stator earth fault current al low as possible.may be upto 10amp for generator. Basis for selection of ngtr- if generator is connected to the system through generator transformer then generator can be treated as an isolated system which is not influenced by the distribution earthing system. In this case you can select earth fault current as low as possible, but if we use ngr then in order to limit the low earth fault current size of the ngr will be increased.due to big size of ngr we required more space & also its too costly. V = ir means if v constant i is inversely proportional to r exp:-to limit 10amp current , v =11kv/root 3 r = 11/root 3/10*1000=635.10 ohm ( very high value) for overcome on this, general practice to use a ngtr so that we can limit low earth current without any extra cost. Exp:- ngtr 11/240v to limit 10amp current current reflect on secondary side of ngtr will be = (11000/root 3/240)*10=264.6 amp. Resistor value on secondary side r =240/264.6 =0.9 ohm ( approximately) which is much lower than 635.10 ohm. Basis for selection of ngr- if generator is directly connected to the system then we can not limit the earth fault current up to 10 amp. We have to select the earth fault current value above the residual capacitive charging current of system.also we need to check the possibility of relay setting operation with ct ratio. For exmp- if ct ratio is 2000/1amp & earth fault limit current is 100amp relay selected with 10 % setting. Then that relay will see only 200amp earth fault current it will not see 100amp current. Also we can not keep generator solidly grounded because of high earth fault current stator can damage same will happen with ht motor if it is connected to this system. So for this case we need to select the ngr with proper earth fault current
Transmission circuits are prone to earth faults.Only star connection permits flow of earth fault current and the operation of earth fault relays.
10mA