AnswerYou cannot obtain 240 V from a 480-V three-phase supply, if you are describing a three-phase, four-wire, system. If 240 V is a phase voltage, then the corresponding line voltage must be 415 V. If 480 V is a line voltage, then the corresponding phase voltage must be 277 V.
No, you will not obtain 230 volts. From a wye connected three phase 480 volt supply, 277 volts can be obtained from one phase leg and the neutral on the wye connection. 480 volts/1.73 (sq. root of 3) = 277 volts.
If the heater is rated as a 3 phase 480 volt heater then a neutral is not needed. If the voltage stated is 277 volts three phase then a neutral is needed.
Across a 480 volt three phase system, 480 volts should appear across L1 and L2, L2 and L3 and L3 and L1.
Current in 200kw at 480 volts = 200,000/480 = 416.667 amps
Call your local utility.
240/220 480 volts 3 phase
The star point or wye voltage of a 480 volt three phase four wire system is 277 volts. The 480 voltage is divided by the sq root of 3 (for 3 phases). The sq root of 3 is 1.73. 480 volts/1.73 = 277 volts. The same formula is used on all three phase four wire systems. 208 volts /1.73 = 120 volts, 416 volts /1.73 = 240 volts, 600 volts / 1.73 = 347 volts.
No, you will not obtain 230 volts. From a wye connected three phase 480 volt supply, 277 volts can be obtained from one phase leg and the neutral on the wye connection. 480 volts/1.73 (sq. root of 3) = 277 volts.
If the heater is rated as a 3 phase 480 volt heater then a neutral is not needed. If the voltage stated is 277 volts three phase then a neutral is needed.
A three phase four wire commercial distribution service will not give you 240 volts. The nearest voltage you can get is 208 volts. It is a wye connection which gives you 208 volts between the three legs and 120 volt between any of the three legs and ground. This ground point is the systems neutral point.
Across a 480 volt three phase system, 480 volts should appear across L1 and L2, L2 and L3 and L3 and L1.
Current in 200kw at 480 volts = 200,000/480 = 416.667 amps
480 volts is probably 3-phase (Line to line) voltage, so: 1500K / (480 x 1.732) = I = 1804Amps
2 prong is a hot and neutral and a 4 prong is a 3 phase with a ground wire.3 pole 4 wire meaning 3 hots could be 240 volts or 480 volts
only way to convert from 3 phase to 240 would be to change the electric motor on the compressor
Call your local utility.
Rephrase your question, as it doesn't make any sense. If the primary side of the transformer is 480 volts 3 phase, this transformer can be supplied from a breaker as big as 180 amps. If 480 volts 3 phase is your secondary then you can supply up to 180 amps to your loads.